01 Operational parameters & standard limits
Target operating windows for a direct-to-chip CDU secondary (technology) loop. Use these as the acceptance band during commissioning and the alarm band during operation. Site values may differ per vendor data sheet and chip TDP — always confirm against the unit's manual and the IT hardware spec. To compute these targets (flow, ΔT, velocity, dP, approach, NPSH, dew-point) for your own load, use the CDU Calculator.
| Parameter | Typical target / limit | Notes & standard |
|---|---|---|
| Secondary supply temp (TCS supply) | ~17–45 °C | ASHRAE TC 9.9 W17–W45 classes; lower for high-TDP GPUs. Number = max supply °C. |
| Secondary ΔT (supply→return) | ~8–12 °C | Sized with flow to the rack heat load (Q = 4.186 × L/s × ΔT). |
| Coolant flow rate | ~1.0–1.5 LPM / kW | OCP guidance ~1.5 LPM/kW at a 10 °C rise; per-cold-plate min flow per chip vendor. |
| Differential pressure (CDU/manifold) | ~0.5–3.0 bar | Within the cold-plate's min/max dP window; watch for filter-clog rise. |
| System (loop) pressure | ~2–6 bar | Below component PN rating; maintain with expansion/make-up control. |
| Coolant / fluid | 25–30% PG (or DI / dielectric) | Propylene-glycol mix for freeze/biocide; DI water (ASTM Type II) for some TCS; dielectric for immersion. Per vendor wetted-material list. |
| Water quality | ASHRAE W1–W4 | Conductivity, pH, hardness, particulate per ASHRAE liquid-cooling guidelines. |
| Filtration rating | ~50 micron (integrated) | e.g. Vertiv CoolChip integrated 50-micron filter; supplement with side-stream if specified. |
| Pump redundancy | N+1 | Dual/redundant pumps + dual power feeds (e.g. CoolIT CHx N+1 pumps + N+1 PSUs). |
| Leak detection | 0 leaks · rope/zone | Leak-detection rope/sensors at CDU base, manifolds, QDs; alarm → isolate. |
| Approach temp (ATD, L2L) | ~3–5 °C | Heat-exchanger approach (e.g. Boyd 3 °C, CoolIT 5 °C ATD). Higher ATD = fouling. |
| Supply vs room dew point | ≥ +2–3 °C above dew point | Dew-point-aware reset prevents condensation on plates/pipe. Critical safety interlock. |
| Pipe velocity (sizing) | ~1.5–3 m/s | Too slow → fouling/air; too fast → erosion + high dP. Sets pipe DN for the flow. |
| Corrosion inhibitor reserve | > 100 ppm azole | No nitrites; depletes over time. Cu < 0.2 ppm / Fe < 0.1 ppm = corrosion indicators. |
| Pump NPSH margin | ≥ 10–20% | Below margin → cavitation + impeller erosion. Maintain system pressure + de-air. |
| Footprint / clearance / weight | per model (e.g. 2400×1200×1200 mm · ~1793 kg wet) | Service clearance front/rear per manual; floor loading checked for filled weight. |
02 Water quality — acceptance criteria & standard limits
The single biggest driver of cold-plate reliability is fluid chemistry. Two loops have different limits — the secondary Technology Cooling System (TCS) that touches the chips, and the primary Facility Water System (FWS) — because the fluids differ (inhibited PG25 glycol vs treated facility water). Use the table that matches your loop as the commissioning acceptance criteria and the operational monitoring band.
ASHRAE facility-water (W) classes — max supply temperature
ASHRAE TC 9.9 liquid-cooling classes. The number is the max facility supply temperature in °C; all classes share a 2 °C lower limit. Higher class → more free-cooling / chiller-less operation. STANDARD ASHRAE TC 9.9 (2021)
| Class (new) | Old | Max supply temp | Typical plant |
|---|---|---|---|
| W17 | W1 | ≤ 17 °C (62.6 °F) | Chiller + tower, water-side economizer |
| W27 | W2 | ≤ 27 °C (80.6 °F) | Chiller + tower, more economizer hours |
| W32 | W3 | ≤ 32 °C (89.6 °F) | Chiller-less in most climates |
| W40 | — | ≤ 40 °C (104 °F) | Chiller-less (added 2021) |
| W45 | W4 | ≤ 45 °C (113 °F) | Chiller-less for capex/efficiency |
| W+ | W5 | > 45 °C | Warmest-water designs |
TCS (secondary / cold-plate loop) — fluid acceptance criteria
For single-phase water-based cold-plate racks. STANDARD OCP, Guidelines for Using Water-Based Transfer Fluids in Single-Phase Cold-Plate Racks, Rev 1.0, Table 1
| Parameter | Acceptance limit | Notes |
|---|---|---|
| pH | 8.0 – 10.5 | Inhibited/glycol TCS runs alkaline; >9.5 may reduce biocide need. (Don't apply the older generic "7–8.5" water figure here.) |
| Conductivity | < 1,500 µS/cm @25 °C | After treatment, then monitor rate-of-rise. Inhibited fluid is intentionally conductive — the <5–10 µS/cm target is for DI-water loops only. |
| TDS (total dissolved solids) | < 1,000 ppm | — |
| TSS (suspended solids) | < 5 ppm op · < 1 ppm fill | Tighter at initial fill. |
| Total hardness (CaCO₃) | < 30 ppm · < 2 ppm fill | Scale prevention. |
| Chloride | < 50 ppm (304SS) · < 500 ppm (316SS) | Pitting risk — limit depends on wetted stainless grade. |
| Turbidity | < 5 NTU | — |
| Bacteria | < 1 CFU/mL fill · < 100 CFU/mL op | Biofilm clogs microchannels. |
| Corrosion inhibitor (azoles/TTA) | > 100 ppm | No nitrites. Depletes over time — dose per sample. |
| Cu / Fe ions | < 0.2 ppm / < 0.1 ppm | Corrosion indicators — rising = active attack. |
| Side-stream filtration | down to < 5 µm | Polishing loop keeps particulate low. |
TCS vs FWS — side-by-side limits
STANDARD ASHRAE TC 9.9, reproduced in Dell "Liquid Coolants Guidance for TCS and FWS", Table 2
| Parameter | TCS (PG25 secondary) | FWS (facility primary) |
|---|---|---|
| pH | 8.0 – 10.5 | 7.0 – 9.0 |
| Total hardness (CaCO₃) | < 50 ppm | < 200 ppm |
| Chloride | < 25 ppm | < 50 ppm |
| Sulfate | < 25 ppm | < 100 ppm |
| Sulfide | — | < 10 ppm |
| Cu / Fe | < 2 ppm each | — |
03 Installation & commissioning — numeric procedure
The numbers behind the §04 checklist ticks. Where a value is a published code/spec it is tagged STANDARD; where it is common engineering practice it is tagged TYPICAL/VENDOR so you don't over-cite it in a design package.
Pressure test (hydrostatic)
- Hydrostatic test pressure = 1.5 × design pressure, temperature-corrected PT = 1.5 × PD × (ST/SD).STANDARD — ASME B31.3 / B31.1
- Hold ≥ 10 min at test pressure before/while examining joints, then for the full inspection duration.STANDARD — ASME B31.x minimum (a 4-hr hold is a TYPICAL/VENDOR DC practice)
- Acceptance = no leakage / no visible decay. ASME does not set a "% drop over N hours" — any such figure is project/vendor.pneumatic alt: B31.3 1.1× · B31.1 1.2×
Flush & cleanliness
- Turbulent flush — sustain Re > 4,000 (≈ 2–3 m/s) to scour debris before connecting cold plates.STANDARD flushing convention · velocity TYPICAL
- Cleanliness target by ISO 4406 (>4/>6/>14 µm code) or NAS 1638; sensitive loops aim ~16/14/11 or better.STANDARD frameworks · target TYPICAL
- Flush until clean — common gate: conductivity stabilises < ~5 µS/cm (DI loops); TCS in-loop turbidity < 5 NTU (OCP fluid spec).VENDOR gate · OCP turbidity STANDARD
Filtration sizing
| Loop | Filter rating | Source |
|---|---|---|
| FWS / primary | 150 – 500 µm | TYPICAL/VENDOR |
| TCS / secondary (main) | 25 – 50 µm | 50 µm ≈ 288 mesh VENDOR (Lenovo Neptune citing ASHRAE) |
| Cold-plate side-stream | < 5 – 10 µm | OCP (< 5 µm) |
| Polishing (fine side-stream) | down to 0.2 µm | VENDOR (Boyd/Eaton) |
Coolant & flow
- PG25 (25 vol% propylene glycol) is the de-facto DTC grade (freeze ≈ −10 °C); practical band 20–35%.PG25 STANDARD (OCP-listed) · band TYPICAL
- Design flow ≈ 1.5 LPM/kW at ~10 °C rise; published band 1.25–2.0 LPM/kW (7.5–12 °C ΔT). Physics: Q = ṁ·cp·ΔT, cp(PG25) ≈ 3.9–4.0 kJ/kg·K.STANDARD — OCP cold-plate design point
- 2-phase / refrigerant DLC fluids: R-1233zd(E) (GWP 1, A1, boil ≈ 18 °C) · R-515B (GWP ≈ 293, A1) · R-1336mzz(Z).vendor datasheet figures
Quick-disconnects (QD) — OCP UQD / UQDB
- Match the QD standard across the loop — no mixed couplers. UQD = hand-mate, drip-free, hot-pluggable; UQDB = blind-mate with ±1 mm radial tolerance for rack/manifold insertion.STANDARD — OCP UQD/UQDB
- Sizes UQD02/04/06/08 · max working 100 psi (6.9 bar) · min burst 300 psi (20.7 bar) · op 17–65 °C · ≥ 5,000 mating cycles · dripless spillage ~0.02–0.07 mL/connect.cross-checked vs Parker/CPC datasheets
- No standardised coupler torque (push-to-connect). Torque applies only to threaded fitting/manifold ports — per vendor.TYPICAL/VENDOR
Leak detection & response
- Two sensing types: rope/cable zone sensing (area coverage under floor / along runs) + point/spot sensors (CDU drains, QD manifolds, headers).industry practice
- Response sequence: detect → alarm to BMS/DCIM → isolate / auto-shutoff valves → contain. Guidance: OCP OAI Liquid Cooling Guidelines + ASHRAE TC 9.9 5th ed.STANDARD guidance · timing figures TYPICAL
04 Installation checklist
Phased from delivery to handover. Tick each item; the printable form (§06) captures readings + sign-off.
Site preparation
- Floor loading verified for the CDU's filled, operating weight + service access.confirm point load vs raised-floor / slab rating
- Service clearances front/rear/sides per the unit manual.e.g. ≥1 m service aisle; door swing + tube routing
- Facility water available (L2L) with isolation valves, strainer, flow/temp at design point — or confirm L2A room-air budget.CDW supply/return temp + flow per data sheet
- Dual power feeds available (A/B), correct breaker rating + earthing.N+1 PSU; verify voltage/phase
- BMS / leak-detection integration points identified (Modbus/BACnet/SNMP).
Mechanical install
- CDU set + levelled, anti-vibration mounts seated.
- Primary & secondary piping connected; pipe spec/insulation per design; supports fitted.no strain on CDU ports; correct DN size
- Manifolds + quick-disconnects installed; QD standard matched (no mixed couplers).verify drip-less QD type per vendor
- Leak-detection rope/sensors routed at base, manifolds, QDs.
Fill, flush & commission
- Pressure test primary + secondary to spec; hold + record (no decay).test pressure + hold time per manual
- Flush secondary loop to remove debris before connecting cold plates.flush until clean / target turbidity
- Fill with correct coolant (PG% / DI / dielectric) and de-air the loop.record fluid type + concentration
- Set flow + dP + supply temp to design; verify against rack heat load.
- Leak-detection + alarm test; confirm auto-isolation behaviour.
- Redundancy test — fail one pump / one PSU, confirm N+1 hold.
- BMS points verified (flow, temps, dP, pressure, alarms reading correctly).
- Handover pack — as-built, fill record, commissioning sheet, O&M manual filed.
05 Routine inspection checklist
Walk-down checks. Anything outside the §01 band → log + see the symptom table (§05).
- No leak alarm; visually dry at base, manifolds, QDs, HX, pump seals.0 leaks · check for glycol residue / drips
- Flow within band.~1.0–1.5 LPM/kW
- Differential pressure stable (no clog rise).~0.5–3.0 bar
- Supply / return temps + ΔT at target.supply ~17–45 °C · ΔT ~8–12 °C
- System pressure in band; expansion / make-up healthy.~2–6 bar
- Pump status — duty running, standby ready (N+1); no noise/vibration.
- Filter dP within clean range; no clog warning.
- No alarms on HMI; data quality live (not stale).
06 Preventive-maintenance (PM) checklist
PM tasks by cadence. DAILY WEEKLY MONTHLY QUARTERLY ANNUAL. Intervals are a baseline — follow the vendor PM schedule and adjust to fluid-sample results. The Parts / consumable column points to the line in §07 — Spare-parts register with part reference, critical-spare class and cost band.
| Task | Frequency | Acceptance / action | Parts / consumable |
|---|---|---|---|
| Read & log flow / dP / temps / pressure; check alarms | DAILY | All within §01 band; trend for drift. | none |
| Visual leak walk-down (base, QDs, manifolds, seals) | DAILY | Dry; any glycol residue → investigate. | none |
| Verify N+1 (standby pump/PSU healthy) | WEEKLY | Standby ready; exercise per vendor. | none |
| Check make-up rate & expansion-tank level/pressure | WEEKLY | Make-up minimal; level/pressure in band — rising make-up = slow leak. | PG25 top-up · bladder |
| Verify dew-point reset active (supply ≥ room dew point +2–3 °C) | WEEKLY | No condensation risk; RH sensor reading true. | RH sensor |
| Leak-detection function test | MONTHLY | Alarm + isolation confirmed. | leak rope/controller |
| Filter / strainer dP check — replace element if clogged | MONTHLY | Replace when filter dP > vendor threshold (typ. >+0.3–0.5 bar above clean); record. | filter element |
| Coolant sample — pH, conductivity, glycol%, biology, particulate | QUARTERLY | Within ASHRAE W-quality; dose/replace per result. | PG25 · inhibitor/biocide |
| Flow & dP sensor calibration check | QUARTERLY | Within sensor tolerance; re-cal if drift. | flow · dP xmtr |
| Pump seal / bearing inspection (vibration, noise) | QUARTERLY | Service per runtime hours / vendor; weep or rising vibration → reseal. | seal kit · pump |
| Control-valve stroke / actuator demand-vs-feedback test | QUARTERLY | Deviation <10%; fail-safe (bypass) confirmed. | TCV actuator |
| BMS/DCIM telemetry & alarm-point verification | QUARTERLY | All points live + correct; no stale data; alarms route. | none |
| Corrosion-inhibitor reserve + Cu/Fe ion test | QUARTERLY | Inhibitor >100 ppm; Cu <0.2 / Fe <0.1 ppm (rising = active corrosion). | inhibitor |
| QD / gasket / O-ring seal inspection (glycol-compatible EPDM) | QUARTERLY | No weep; replace any seal showing compression-set or leak. | QD · EPDM kit |
| Pressure-relief valve (PSV/PRV) test | ANNUAL | Relieves at set pressure < component PN; reseats. Replace if passing/stuck. | PSV |
| Heat-exchanger approach (ATD) check / clean | ANNUAL | Rising ATD = fouling → clean / CIP the fouled side. | HX gaskets (if opened) |
| Coolant replacement (or per sample) | ANNUAL | Replace full charge if chemistry out of band. | PG25 full charge |
| Air-side coil & filter service (L2A only) | ANNUAL | Clean coil; replace air filter at dP threshold — restores room-reject capacity. | air filter |
| Full redundancy + failover drill; firmware/controls review | ANNUAL | N+1 holds under fault; backups current. | none |
07 Spare-parts & consumables register
Every PM line that consumes a part maps to a row here: what to replace, the acceptance / replace-when trigger, the interval, a part reference / spec (commodity manufacturer family or OEM service-part class — exact OEM part numbers are proprietary and obtained from the unit's IPB, see §08), a critical-spare class, and an estimated unit-cost band. CRITICAL = hold on site (failure stops cooling). RECOMMENDED = short-lead consumable. ON-DEMAND = order when condition-flagged.
| Item | Function / where | Replace-when (acceptance trigger) | Interval | Part reference / spec | Critical | Est. unit cost | Src |
|---|---|---|---|---|---|---|---|
| Secondary-loop filter / strainer element | Y-strainer or cartridge on the TCS loop — protects cold-plate micro-channels. | Filter dP > clean +0.3–0.5 bar, or monthly. | MONTHLY | 50 µm SS mesh (Y-strainer) / 25–50 µm pleated cartridge e.g. Parker, 3M, Eaton families | CRITICAL | $25–120 | VENDOR EST |
| Heat-transfer fluid — inhibited PG25 | Secondary coolant (25 % inhibited propylene glycol) touching the cold plates. | Chemistry out of band (pH/conductivity/glycol %/biology) or annual. | QUARTERLY top-up · ANNUAL charge | 25 % inhibited PG, low-conductivity e.g. Dynalene PG, DOWFROST, ClearTech 25-PG; charge ≈ 60–200 L/unit | RECOMMENDED | $8–25 / L (charge $1k–4k) | VENDOR EST |
| Quick-disconnect coupling (dry-break) | Rack-manifold & CDU service connections — no-spill on de-mate. | Seal weep, drip on de-mate, or compression-set on inspection. | QUARTERLY inspect | Dripless / dry-break QD e.g. Stäubli CGO/SPT, CPC LQ, Parker Non-Spill; EPDM seals | CRITICAL | $40–180 | VENDOR EST |
| EPDM gasket / O-ring kit | Manifold, HX ports, flange & QD seals — must be glycol-compatible EPDM, not NBR. | Any weep; replace whenever a joint is broken for service. | QUARTERLY inspect | EPDM O-ring / gasket set per unit seal schedule (peroxide-cured EPDM) | CRITICAL | $40–150 / kit | VENDOR EST |
| Pump mechanical / cartridge seal kit | Circulation pump shaft seal (duty & standby). | Weep at seal, rising vibration/noise, or per runtime-hour limit. | QUARTERLY inspect | Mechanical seal kit per pump model e.g. Grundfos / Wilo / canned-rotor service kit | RECOMMENDED | $80–400 | VENDOR EST |
| Spare circulation pump (N+1) | Duty/standby secondary pump — the unit holds N+1 with auto-changeover. | Bearing/seal failure, persistent low flow after reseal. | condition | EC/wet-rotor or canned pump per CDU e.g. Grundfos CRE / Wilo-Stratos class | RECOMMENDED (1/fleet) | $600–3,500 | VENDOR EST |
| Expansion-tank bladder / diaphragm | Holds loop pressure & absorbs thermal expansion. | Waterlogged tank, pressure won't hold, air on bladder side. | condition | EPDM bladder per tank model | ON-DEMAND | $60–300 | VENDOR EST |
| Leak-detection rope + controller | Sensing cable at base/manifolds/QDs feeding the leak alarm & isolation. | Fails monthly function test, contamination, or physical damage. | MONTHLY test | Water/glycol-sensing rope + zone controller e.g. TTK, RLE SeaHawk, nVent Raychem | CRITICAL | rope $15–40/m · ctrl $300–900 | VENDOR EST |
| Flow sensor (turbine / vortex / ultrasonic) | Secondary flow measurement — the primary cooling-delivery proof. | Drift beyond sensor tolerance vs reference; signal loss. | QUARTERLY cal | Inline flow sensor e.g. ifm SM-series, Grundfos VFS | RECOMMENDED | $150–600 | VENDOR EST |
| Pressure / differential-pressure transmitter | Loop & filter dP, system pressure (drives VFD & filter alarm). | Drift vs gauge, signal loss, out-of-range. | QUARTERLY cal | 4–20 mA P / ΔP transmitter e.g. ifm PN/PT, Danfoss MBS | RECOMMENDED | $120–450 | VENDOR EST |
| Temperature / RH sensor (+ thermowell) | Supply/return temp & room dew-point reset reference. | Drift vs reference; dew-point reset depends on a true RH reading. | QUARTERLY cal | PT100/PT1000 + thermowell; RH probe | ON-DEMAND | $25–120 | VENDOR EST |
| Control-valve actuator (TCV / PICV) | Modulates supply temp / bypass — fail-safe to a safe (cooling) position. | Demand-vs-feedback >10 %, stiction, signal loss. | QUARTERLY test | Modulating actuator per valve e.g. Belimo class | ON-DEMAND | $200–900 | VENDOR EST |
| Corrosion inhibitor / biocide dosing | Maintains inhibitor reserve & controls biology in the loop. | Inhibitor <100 ppm; biology positive; Cu/Fe rising. | QUARTERLY | Glycol-compatible inhibitor + isothiazolinone biocide e.g. Dynalene inhibitor pack | RECOMMENDED | $20–60 / L | VENDOR EST |
| Pressure-relief valve (PSV / PRV) | Over-pressure protection below component pressure rating (PN). | Fails annual lift test, passes/weeps, or stuck. | ANNUAL test | Set-pressure relief valve < loop PN | ON-DEMAND | $80–300 | STD EST |
| Air-side coil filter (L2A only) | Protects the liquid-to-air reject coil; L2A rejects to room air. | Air-side dP at threshold; reduced room-reject capacity. | ANNUAL | Panel / pleated air filter per unit | ON-DEMAND | $15–60 | VENDOR EST |
Spares planning — stock levels, service life & annual budget
The register turned into a stocking plan: min stock to hold on site, typical service life (how often the part actually needs replacing, not just inspecting), lead time (which is what really forces you to stock a critical item), and an estimated annual spend per CDU. Quantities assume one CDU; RECOMMENDED/fleet items are shared across the fleet.
| Item | Min stock (per CDU) | Typical service life | Lead time | Annual spend / CDU (EST) |
|---|---|---|---|---|
| Filter / strainer element CRIT | 2 | ~1 month (replace at dP) | 1–2 wk | $300–1,440 |
| PG25 fluid REC | 10–20 % of charge | top-up quarterly · full charge 1–3 yr | 1–3 wk | $350–2,000 amortised |
| Dry-break QD CRIT | 2 | 5+ yr / on failure | 2–6 wk | in kit |
| EPDM gasket / O-ring kit CRIT | 1 kit | 2–5 yr / on each joint break | 2–4 wk | $100–400 |
| Pump seal kit REC | 1 | 1–3 yr (runtime) | 2–4 wk | $100–300 amortised |
| Spare pump REC | 1 / fleet | 5–10 yr | 4–12 wk | capex $600–3,500/fleet |
| Inhibitor / biocide REC | 1 dose pack | per quarterly sample | 1–3 wk | $100–400 |
| Flow / dP / temp sensors REC | 1 of each | 5–10 yr | 2–6 wk | $100–500 amortised |
| Leak rope + controller CRIT | 1 rope spare | 7–10 yr / on failure | 2–6 wk | on failure |
08 Exploded-view & IPB resources — per CDU type
Exact service-part numbers live in each unit's Illustrated Parts Breakdown (IPB) / service manual — request it from the OEM for your model (it is not public for most CDUs). Below, per CDU type, are the representative manufacturers and where to obtain the exploded-view / parts documentation. Match your unit to a row in the CDU comparison to find its OEM, then pull that OEM's manual.
In-Rack
L2L · in-cabinet 3U–4UCompact in-rack CDU. Exploded views cover the pump module, plate-HX, filter and QD manifold. Request the model's service manual / IPB.
In-Row
L2L · between-rack cabinetThe density workhorse. IPB covers dual-pump skid, expansion tank, dual-stage filtration, instrumentation & control valve.
Sidecar
L2L · rack-side slim unitSlim rack-mounted unit. Exploded views focus on the side-mounted HX/pump pack and rack-manifold QDs.
L2L · End-of-Row
L2L · facility-scaleLarge facility-coupled CDU (e.g. ≈2.3 MW). IPB covers large plate-HX, N+1 pump bank, facility-water interface & PSV.
L2A · Air-cooled
L2A · room-air rejectLiquid-to-air unit — no facility water. Exploded views add the air-side reject coil, fans & air filter to the standard liquid pack.
09 Symptom → cause → action
Troubleshooting reference. On any active symptom: protect the IT load first (the CDU's N+1 / isolation logic), then diagnose.
| Symptom | Likely cause | Immediate action | Corrective action |
|---|---|---|---|
| High differential pressure | Filter clogging; valve throttled; air pocket | Check filter dP; confirm valves open; bleed air | Replace filter; re-balance; full de-air |
| Low / no flow | Pump fault; closed valve; QD not seated; airlock | Confirm standby pump took over (N+1); check valves/QD | Service/replace pump; reseat QD; purge air |
| Leak alarm | Loose QD; failed seal/gasket; manifold/HX leak | Acknowledge → isolate affected zone; locate via rope/zone | Tighten/replace QD or seal; pressure-test; refill + de-air |
| High coolant supply temp | Facility water warm/low flow (L2L); HX fouling; high ATD | Check primary supply temp/flow; check ATD | Restore CDW; clean HX; verify control setpoint |
| High room temp (L2A) | Room CRAH can't absorb rejected heat; coil dirty | Check CRAH capacity/airflow; clean coil | Add room cooling / move to L2L; coil service |
| Rising ATD (approach) | Heat-exchanger fouling; reduced flow one side | Compare primary/secondary ΔT; check flows | Clean/flush HX; restore flow |
| Pump fault / vibration | Bearing/seal wear; cavitation (low pressure/air) | Switch to standby; raise system pressure; de-air | Replace pump/seal; correct expansion control |
| Coolant chemistry out of band | Biology growth; glycol degradation; contamination | Sample; dose biocide / inhibitor | Partial/full coolant replacement; side-stream filtration |
| Air in loop (gurgling, unstable dP) | Incomplete de-air; make-up drawing air; leak | Bleed at high points; check make-up | Find/seal air ingress; re-fill correctly |
| Stale / lost telemetry | Sensor fault; comms loss to BMS | Treat values as suspect; local gauge check | Replace sensor; restore comms; re-cal |
| Condensation / sweating on plates & pipe | Supply temp driven below room dew point; dew-point reset disabled / RH sensor fault | Raise supply setpoint above room dew point; check RH sensor | Enable dew-point-aware reset (≥2–3 °C above dew point); fix humidity sensor; insulate |
| GPU throttling / hot sleds | Flow maldistribution across the manifold; under-provisioned flow vs chip TDP | Compare per-branch flow; verify total flow ≥ design L/min/kW | Balance manifold (balancing valves / flow restrictors); raise flow setpoint |
| Two-phase cold-plate dry-out (2-phase) | Vapour quality too high in hot sleds; uneven 2-phase distribution | Check refrigerant charge / sub-cooling; inspect distribution | Re-balance flow restrictors; restore charge; correct manifold geometry |
| Frequent make-up / falling level | Slow leak; air being purged; expansion bladder fault | Trend make-up rate + level (LT); leak walk-down | Find/seal leak; recharge / replace expansion bladder; re-pressurise |
| Control valve fault (TCV) | Actuator demand vs feedback >10%; signal loss → fail to bypass = no cooling | Switch to manual / verify fail-safe position; protect IT load | Re-stroke / replace actuator; re-tune PID (Ziegler-Nichols) |
| System over-pressure | Thermal expansion with closed expansion path; PSV not relieving | Verify expansion/relief path open; check PT vs component PN | Restore expansion control; test/replace PSV; re-set fill pressure |
10 FMECA fault reference — liquid cooling (F11.x)
The five direct-to-chip liquid-cooling fault modes from the site's FMECA knowledge graph, ordered by RPN (Risk Priority Number = Severity × Occurrence × Detectability, per IEC 60812). These are the same faults the Mini-BMS injects and the §07 register stocks against. Higher RPN → act first — but RPN can understate a high-severity, rarely-occurring fault: F11.2 (pump failure) scores S=10 yet RPN=60 because it's detectable and infrequent. Expand a card for component, mechanism, effect chain, detection, and corrective/preventive actions.
F11.1Coolant chemistry driftRPN 140ASME · HIGH
F11.4Dielectric fluid degradationRPN 1203M · THIN
F11.3Manifold / hose leakRPN 108OCP · MEDIUM
F11.2CDU pump failure · S=10 catastrophicRPN 60Vertiv · THIN
F11.5Filter cloggingRPN 60OCP · MEDIUM
docs/research/csv/. S·O·D + RPN per IEC 60812; confidence tiers (HIGH / MEDIUM / THIN) reflect data provenance — vendor MTBF is often confidential. Full knowledge base + ML advisory concept: AI Engineering Maintenance.11 CDU service record — printable form
Fill on-screen and Print / Save as PDF. Captures site identity, readings against the §01 band, checklist pass/fail, and sign-off. Stored on the RZ site as the standard CDU service-record form.
Readings vs target band
| Parameter | Target band | Reading | Pass / Fail |
|---|---|---|---|
| Supply temp (°C) | ~17–45 | ||
| ΔT (°C) | ~8–12 | ||
| Flow (LPM/kW) | ~1.0–1.5 | ||
| Differential pressure (bar) | ~0.5–3.0 | ||
| System pressure (bar) | ~2–6 | ||
| Coolant pH / cond. / glycol% | ASHRAE W1–W4 | ||
| Filter dP / status | clean range | ||
| Leak detection | 0 leaks | ||
| Pump N+1 (duty/standby) | both healthy |