CDU Operations · Reference Document

CDU Installation, Inspection & Maintenance Checklist

The companion document to the CDU Selection Guide. Every operational parameter — flow, differential pressure, supply/return temperatures, system pressure, coolant chemistry, leak limits, dimensions and clearances — with installation and PM checklists, a symptom→action troubleshooting table, and printable fill-in forms for site sign-off.

DC SolutionsCDU Guide → Checklist

01 Operational parameters & standard limits

Target operating windows for a direct-to-chip CDU secondary (technology) loop. Use these as the acceptance band during commissioning and the alarm band during operation. Site values may differ per vendor data sheet and chip TDP — always confirm against the unit's manual and the IT hardware spec. To compute these targets (flow, ΔT, velocity, dP, approach, NPSH, dew-point) for your own load, use the CDU Calculator.

ParameterTypical target / limitNotes & standard
Secondary supply temp (TCS supply)~17–45 °CASHRAE TC 9.9 W17–W45 classes; lower for high-TDP GPUs. Number = max supply °C.
Secondary ΔT (supply→return)~8–12 °CSized with flow to the rack heat load (Q = 4.186 × L/s × ΔT).
Coolant flow rate~1.0–1.5 LPM / kWOCP guidance ~1.5 LPM/kW at a 10 °C rise; per-cold-plate min flow per chip vendor.
Differential pressure (CDU/manifold)~0.5–3.0 barWithin the cold-plate's min/max dP window; watch for filter-clog rise.
System (loop) pressure~2–6 barBelow component PN rating; maintain with expansion/make-up control.
Coolant / fluid25–30% PG (or DI / dielectric)Propylene-glycol mix for freeze/biocide; DI water (ASTM Type II) for some TCS; dielectric for immersion. Per vendor wetted-material list.
Water qualityASHRAE W1–W4Conductivity, pH, hardness, particulate per ASHRAE liquid-cooling guidelines.
Filtration rating~50 micron (integrated)e.g. Vertiv CoolChip integrated 50-micron filter; supplement with side-stream if specified.
Pump redundancyN+1Dual/redundant pumps + dual power feeds (e.g. CoolIT CHx N+1 pumps + N+1 PSUs).
Leak detection0 leaks · rope/zoneLeak-detection rope/sensors at CDU base, manifolds, QDs; alarm → isolate.
Approach temp (ATD, L2L)~3–5 °CHeat-exchanger approach (e.g. Boyd 3 °C, CoolIT 5 °C ATD). Higher ATD = fouling.
Supply vs room dew point≥ +2–3 °C above dew pointDew-point-aware reset prevents condensation on plates/pipe. Critical safety interlock.
Pipe velocity (sizing)~1.5–3 m/sToo slow → fouling/air; too fast → erosion + high dP. Sets pipe DN for the flow.
Corrosion inhibitor reserve> 100 ppm azoleNo nitrites; depletes over time. Cu < 0.2 ppm / Fe < 0.1 ppm = corrosion indicators.
Pump NPSH margin≥ 10–20%Below margin → cavitation + impeller erosion. Maintain system pressure + de-air.
Footprint / clearance / weightper model (e.g. 2400×1200×1200 mm · ~1793 kg wet)Service clearance front/rear per manual; floor loading checked for filled weight.

02 Water quality — acceptance criteria & standard limits

The single biggest driver of cold-plate reliability is fluid chemistry. Two loops have different limits — the secondary Technology Cooling System (TCS) that touches the chips, and the primary Facility Water System (FWS) — because the fluids differ (inhibited PG25 glycol vs treated facility water). Use the table that matches your loop as the commissioning acceptance criteria and the operational monitoring band.

STANDARD published code / spec figure  ·  TYPICAL/VENDOR typical or vendor range, not a fixed standard

ASHRAE facility-water (W) classes — max supply temperature

ASHRAE TC 9.9 liquid-cooling classes. The number is the max facility supply temperature in °C; all classes share a 2 °C lower limit. Higher class → more free-cooling / chiller-less operation. STANDARD ASHRAE TC 9.9 (2021)

Class (new)OldMax supply tempTypical plant
W17W1≤ 17 °C (62.6 °F)Chiller + tower, water-side economizer
W27W2≤ 27 °C (80.6 °F)Chiller + tower, more economizer hours
W32W3≤ 32 °C (89.6 °F)Chiller-less in most climates
W40≤ 40 °C (104 °F)Chiller-less (added 2021)
W45W4≤ 45 °C (113 °F)Chiller-less for capex/efficiency
W+W5> 45 °CWarmest-water designs

TCS (secondary / cold-plate loop) — fluid acceptance criteria

For single-phase water-based cold-plate racks. STANDARD OCP, Guidelines for Using Water-Based Transfer Fluids in Single-Phase Cold-Plate Racks, Rev 1.0, Table 1

ParameterAcceptance limitNotes
pH8.0 – 10.5Inhibited/glycol TCS runs alkaline; >9.5 may reduce biocide need. (Don't apply the older generic "7–8.5" water figure here.)
Conductivity< 1,500 µS/cm @25 °CAfter treatment, then monitor rate-of-rise. Inhibited fluid is intentionally conductive — the <5–10 µS/cm target is for DI-water loops only.
TDS (total dissolved solids)< 1,000 ppm
TSS (suspended solids)< 5 ppm op · < 1 ppm fillTighter at initial fill.
Total hardness (CaCO₃)< 30 ppm · < 2 ppm fillScale prevention.
Chloride< 50 ppm (304SS) · < 500 ppm (316SS)Pitting risk — limit depends on wetted stainless grade.
Turbidity< 5 NTU
Bacteria< 1 CFU/mL fill · < 100 CFU/mL opBiofilm clogs microchannels.
Corrosion inhibitor (azoles/TTA)> 100 ppmNo nitrites. Depletes over time — dose per sample.
Cu / Fe ions< 0.2 ppm / < 0.1 ppmCorrosion indicators — rising = active attack.
Side-stream filtrationdown to < 5 µmPolishing loop keeps particulate low.

TCS vs FWS — side-by-side limits

STANDARD ASHRAE TC 9.9, reproduced in Dell "Liquid Coolants Guidance for TCS and FWS", Table 2

ParameterTCS (PG25 secondary)FWS (facility primary)
pH8.0 – 10.57.0 – 9.0
Total hardness (CaCO₃)< 50 ppm< 200 ppm
Chloride< 25 ppm< 50 ppm
Sulfate< 25 ppm< 100 ppm
Sulfide< 10 ppm
Cu / Fe< 2 ppm each
Make-up / top-off water (OCP sub-spec). STANDARD chloride < 25 ppm · sulfate < 25 ppm · Ca < 25 ppm · Mg < 25 ppm · total hardness < 50 ppm CaCO₃ · < 1 CFU/mL. Blend/dilution water benchmark: ASTM D1193 Type II (resistivity > 1 MΩ·cm, ≈ < 1 µS/cm). Not over-stated: TOC has no published numeric cold-plate limit (treat as TYPICAL/VENDOR); the biostatic glycol % is a freeze/viscosity choice, not a fixed biocide standard.

03 Installation & commissioning — numeric procedure

The numbers behind the §04 checklist ticks. Where a value is a published code/spec it is tagged STANDARD; where it is common engineering practice it is tagged TYPICAL/VENDOR so you don't over-cite it in a design package.

Pressure test (hydrostatic)

  • Hydrostatic test pressure = 1.5 × design pressure, temperature-corrected PT = 1.5 × PD × (ST/SD).STANDARD — ASME B31.3 / B31.1
  • Hold ≥ 10 min at test pressure before/while examining joints, then for the full inspection duration.STANDARD — ASME B31.x minimum (a 4-hr hold is a TYPICAL/VENDOR DC practice)
  • Acceptance = no leakage / no visible decay. ASME does not set a "% drop over N hours" — any such figure is project/vendor.pneumatic alt: B31.3 1.1× · B31.1 1.2×

Flush & cleanliness

  • Turbulent flush — sustain Re > 4,000 (≈ 2–3 m/s) to scour debris before connecting cold plates.STANDARD flushing convention · velocity TYPICAL
  • Cleanliness target by ISO 4406 (>4/>6/>14 µm code) or NAS 1638; sensitive loops aim ~16/14/11 or better.STANDARD frameworks · target TYPICAL
  • Flush until clean — common gate: conductivity stabilises < ~5 µS/cm (DI loops); TCS in-loop turbidity < 5 NTU (OCP fluid spec).VENDOR gate · OCP turbidity STANDARD

Filtration sizing

LoopFilter ratingSource
FWS / primary150 – 500 µmTYPICAL/VENDOR
TCS / secondary (main)25 – 50 µm50 µm ≈ 288 mesh VENDOR (Lenovo Neptune citing ASHRAE)
Cold-plate side-stream< 5 – 10 µmOCP (< 5 µm)
Polishing (fine side-stream)down to 0.2 µmVENDOR (Boyd/Eaton)

Coolant & flow

  • PG25 (25 vol% propylene glycol) is the de-facto DTC grade (freeze ≈ −10 °C); practical band 20–35%.PG25 STANDARD (OCP-listed) · band TYPICAL
  • Design flow ≈ 1.5 LPM/kW at ~10 °C rise; published band 1.25–2.0 LPM/kW (7.5–12 °C ΔT). Physics: Q = ṁ·cp·ΔT, cp(PG25) ≈ 3.9–4.0 kJ/kg·K.STANDARD — OCP cold-plate design point
  • 2-phase / refrigerant DLC fluids: R-1233zd(E) (GWP 1, A1, boil ≈ 18 °C) · R-515B (GWP ≈ 293, A1) · R-1336mzz(Z).vendor datasheet figures

Quick-disconnects (QD) — OCP UQD / UQDB

  • Match the QD standard across the loop — no mixed couplers. UQD = hand-mate, drip-free, hot-pluggable; UQDB = blind-mate with ±1 mm radial tolerance for rack/manifold insertion.STANDARD — OCP UQD/UQDB
  • Sizes UQD02/04/06/08 · max working 100 psi (6.9 bar) · min burst 300 psi (20.7 bar) · op 17–65 °C · ≥ 5,000 mating cycles · dripless spillage ~0.02–0.07 mL/connect.cross-checked vs Parker/CPC datasheets
  • No standardised coupler torque (push-to-connect). Torque applies only to threaded fitting/manifold ports — per vendor.TYPICAL/VENDOR

Leak detection & response

  • Two sensing types: rope/cable zone sensing (area coverage under floor / along runs) + point/spot sensors (CDU drains, QD manifolds, headers).industry practice
  • Response sequence: detect → alarm to BMS/DCIM → isolate / auto-shutoff valves → contain. Guidance: OCP OAI Liquid Cooling Guidelines + ASHRAE TC 9.9 5th ed.STANDARD guidance · timing figures TYPICAL

04 Installation checklist

Phased from delivery to handover. Tick each item; the printable form (§06) captures readings + sign-off.

Site preparation

  • Floor loading verified for the CDU's filled, operating weight + service access.confirm point load vs raised-floor / slab rating
  • Service clearances front/rear/sides per the unit manual.e.g. ≥1 m service aisle; door swing + tube routing
  • Facility water available (L2L) with isolation valves, strainer, flow/temp at design point — or confirm L2A room-air budget.CDW supply/return temp + flow per data sheet
  • Dual power feeds available (A/B), correct breaker rating + earthing.N+1 PSU; verify voltage/phase
  • BMS / leak-detection integration points identified (Modbus/BACnet/SNMP).

Mechanical install

  • CDU set + levelled, anti-vibration mounts seated.
  • Primary & secondary piping connected; pipe spec/insulation per design; supports fitted.no strain on CDU ports; correct DN size
  • Manifolds + quick-disconnects installed; QD standard matched (no mixed couplers).verify drip-less QD type per vendor
  • Leak-detection rope/sensors routed at base, manifolds, QDs.

Fill, flush & commission

  • Pressure test primary + secondary to spec; hold + record (no decay).test pressure + hold time per manual
  • Flush secondary loop to remove debris before connecting cold plates.flush until clean / target turbidity
  • Fill with correct coolant (PG% / DI / dielectric) and de-air the loop.record fluid type + concentration
  • Set flow + dP + supply temp to design; verify against rack heat load.
  • Leak-detection + alarm test; confirm auto-isolation behaviour.
  • Redundancy test — fail one pump / one PSU, confirm N+1 hold.
  • BMS points verified (flow, temps, dP, pressure, alarms reading correctly).
  • Handover pack — as-built, fill record, commissioning sheet, O&M manual filed.

05 Routine inspection checklist

Walk-down checks. Anything outside the §01 band → log + see the symptom table (§05).

  • No leak alarm; visually dry at base, manifolds, QDs, HX, pump seals.0 leaks · check for glycol residue / drips
  • Flow within band.~1.0–1.5 LPM/kW
  • Differential pressure stable (no clog rise).~0.5–3.0 bar
  • Supply / return temps + ΔT at target.supply ~17–45 °C · ΔT ~8–12 °C
  • System pressure in band; expansion / make-up healthy.~2–6 bar
  • Pump status — duty running, standby ready (N+1); no noise/vibration.
  • Filter dP within clean range; no clog warning.
  • No alarms on HMI; data quality live (not stale).

06 Preventive-maintenance (PM) checklist

PM tasks by cadence. DAILY WEEKLY MONTHLY QUARTERLY ANNUAL. Intervals are a baseline — follow the vendor PM schedule and adjust to fluid-sample results. The Parts / consumable column points to the line in §07 — Spare-parts register with part reference, critical-spare class and cost band.

TaskFrequencyAcceptance / actionParts / consumable
Read & log flow / dP / temps / pressure; check alarmsDAILYAll within §01 band; trend for drift.none
Visual leak walk-down (base, QDs, manifolds, seals)DAILYDry; any glycol residue → investigate.none
Verify N+1 (standby pump/PSU healthy)WEEKLYStandby ready; exercise per vendor.none
Check make-up rate & expansion-tank level/pressureWEEKLYMake-up minimal; level/pressure in band — rising make-up = slow leak.PG25 top-up · bladder
Verify dew-point reset active (supply ≥ room dew point +2–3 °C)WEEKLYNo condensation risk; RH sensor reading true.RH sensor
Leak-detection function testMONTHLYAlarm + isolation confirmed.leak rope/controller
Filter / strainer dP check — replace element if cloggedMONTHLYReplace when filter dP > vendor threshold (typ. >+0.3–0.5 bar above clean); record.filter element
Coolant sample — pH, conductivity, glycol%, biology, particulateQUARTERLYWithin ASHRAE W-quality; dose/replace per result.PG25 · inhibitor/biocide
Flow & dP sensor calibration checkQUARTERLYWithin sensor tolerance; re-cal if drift.flow · dP xmtr
Pump seal / bearing inspection (vibration, noise)QUARTERLYService per runtime hours / vendor; weep or rising vibration → reseal.seal kit · pump
Control-valve stroke / actuator demand-vs-feedback testQUARTERLYDeviation <10%; fail-safe (bypass) confirmed.TCV actuator
BMS/DCIM telemetry & alarm-point verificationQUARTERLYAll points live + correct; no stale data; alarms route.none
Corrosion-inhibitor reserve + Cu/Fe ion testQUARTERLYInhibitor >100 ppm; Cu <0.2 / Fe <0.1 ppm (rising = active corrosion).inhibitor
QD / gasket / O-ring seal inspection (glycol-compatible EPDM)QUARTERLYNo weep; replace any seal showing compression-set or leak.QD · EPDM kit
Pressure-relief valve (PSV/PRV) testANNUALRelieves at set pressure < component PN; reseats. Replace if passing/stuck.PSV
Heat-exchanger approach (ATD) check / cleanANNUALRising ATD = fouling → clean / CIP the fouled side.HX gaskets (if opened)
Coolant replacement (or per sample)ANNUALReplace full charge if chemistry out of band.PG25 full charge
Air-side coil & filter service (L2A only)ANNUALClean coil; replace air filter at dP threshold — restores room-reject capacity.air filter
Full redundancy + failover drill; firmware/controls reviewANNUALN+1 holds under fault; backups current.none

07 Spare-parts & consumables register

Every PM line that consumes a part maps to a row here: what to replace, the acceptance / replace-when trigger, the interval, a part reference / spec (commodity manufacturer family or OEM service-part class — exact OEM part numbers are proprietary and obtained from the unit's IPB, see §08), a critical-spare class, and an estimated unit-cost band. CRITICAL = hold on site (failure stops cooling). RECOMMENDED = short-lead consumable. ON-DEMAND = order when condition-flagged.

STD published standard / spec VENDOR typical vendor part family EST illustrative cost band — representative market range, not a quote
ItemFunction / whereReplace-when (acceptance trigger)IntervalPart reference / specCriticalEst. unit costSrc
Secondary-loop filter / strainer elementY-strainer or cartridge on the TCS loop — protects cold-plate micro-channels.Filter dP > clean +0.3–0.5 bar, or monthly.MONTHLY50 µm SS mesh (Y-strainer) / 25–50 µm pleated cartridge e.g. Parker, 3M, Eaton familiesCRITICAL$25–120VENDOR EST
Heat-transfer fluid — inhibited PG25Secondary coolant (25 % inhibited propylene glycol) touching the cold plates.Chemistry out of band (pH/conductivity/glycol %/biology) or annual.QUARTERLY top-up · ANNUAL charge25 % inhibited PG, low-conductivity e.g. Dynalene PG, DOWFROST, ClearTech 25-PG; charge ≈ 60–200 L/unitRECOMMENDED$8–25 / L (charge $1k–4k)VENDOR EST
Quick-disconnect coupling (dry-break)Rack-manifold & CDU service connections — no-spill on de-mate.Seal weep, drip on de-mate, or compression-set on inspection.QUARTERLY inspectDripless / dry-break QD e.g. Stäubli CGO/SPT, CPC LQ, Parker Non-Spill; EPDM sealsCRITICAL$40–180VENDOR EST
EPDM gasket / O-ring kitManifold, HX ports, flange & QD seals — must be glycol-compatible EPDM, not NBR.Any weep; replace whenever a joint is broken for service.QUARTERLY inspectEPDM O-ring / gasket set per unit seal schedule (peroxide-cured EPDM)CRITICAL$40–150 / kitVENDOR EST
Pump mechanical / cartridge seal kitCirculation pump shaft seal (duty & standby).Weep at seal, rising vibration/noise, or per runtime-hour limit.QUARTERLY inspectMechanical seal kit per pump model e.g. Grundfos / Wilo / canned-rotor service kitRECOMMENDED$80–400VENDOR EST
Spare circulation pump (N+1)Duty/standby secondary pump — the unit holds N+1 with auto-changeover.Bearing/seal failure, persistent low flow after reseal.conditionEC/wet-rotor or canned pump per CDU e.g. Grundfos CRE / Wilo-Stratos classRECOMMENDED (1/fleet)$600–3,500VENDOR EST
Expansion-tank bladder / diaphragmHolds loop pressure & absorbs thermal expansion.Waterlogged tank, pressure won't hold, air on bladder side.conditionEPDM bladder per tank modelON-DEMAND$60–300VENDOR EST
Leak-detection rope + controllerSensing cable at base/manifolds/QDs feeding the leak alarm & isolation.Fails monthly function test, contamination, or physical damage.MONTHLY testWater/glycol-sensing rope + zone controller e.g. TTK, RLE SeaHawk, nVent RaychemCRITICALrope $15–40/m · ctrl $300–900VENDOR EST
Flow sensor (turbine / vortex / ultrasonic)Secondary flow measurement — the primary cooling-delivery proof.Drift beyond sensor tolerance vs reference; signal loss.QUARTERLY calInline flow sensor e.g. ifm SM-series, Grundfos VFSRECOMMENDED$150–600VENDOR EST
Pressure / differential-pressure transmitterLoop & filter dP, system pressure (drives VFD & filter alarm).Drift vs gauge, signal loss, out-of-range.QUARTERLY cal4–20 mA P / ΔP transmitter e.g. ifm PN/PT, Danfoss MBSRECOMMENDED$120–450VENDOR EST
Temperature / RH sensor (+ thermowell)Supply/return temp & room dew-point reset reference.Drift vs reference; dew-point reset depends on a true RH reading.QUARTERLY calPT100/PT1000 + thermowell; RH probeON-DEMAND$25–120VENDOR EST
Control-valve actuator (TCV / PICV)Modulates supply temp / bypass — fail-safe to a safe (cooling) position.Demand-vs-feedback >10 %, stiction, signal loss.QUARTERLY testModulating actuator per valve e.g. Belimo classON-DEMAND$200–900VENDOR EST
Corrosion inhibitor / biocide dosingMaintains inhibitor reserve & controls biology in the loop.Inhibitor <100 ppm; biology positive; Cu/Fe rising.QUARTERLYGlycol-compatible inhibitor + isothiazolinone biocide e.g. Dynalene inhibitor packRECOMMENDED$20–60 / LVENDOR EST
Pressure-relief valve (PSV / PRV)Over-pressure protection below component pressure rating (PN).Fails annual lift test, passes/weeps, or stuck.ANNUAL testSet-pressure relief valve < loop PNON-DEMAND$80–300STD EST
Air-side coil filter (L2A only)Protects the liquid-to-air reject coil; L2A rejects to room air.Air-side dP at threshold; reduced room-reject capacity.ANNUALPanel / pleated air filter per unitON-DEMAND$15–60VENDOR EST
Stocking logic. Hold every CRITICAL item on site (a clogged filter, failed QD, weeping seal or dead leak-rope can stop cooling or trip the rack). Keep a charge-fraction of PG25, one seal kit and one spare pump per fleet as RECOMMENDED. Cost bands are EST illustrative market ranges for budgeting — confirm against your OEM service-parts quote and the unit's IPB before purchase.

Spares planning — stock levels, service life & annual budget

The register turned into a stocking plan: min stock to hold on site, typical service life (how often the part actually needs replacing, not just inspecting), lead time (which is what really forces you to stock a critical item), and an estimated annual spend per CDU. Quantities assume one CDU; RECOMMENDED/fleet items are shared across the fleet.

ItemMin stock (per CDU)Typical service lifeLead timeAnnual spend / CDU (EST)
Filter / strainer element CRIT2~1 month (replace at dP)1–2 wk$300–1,440
PG25 fluid REC10–20 % of chargetop-up quarterly · full charge 1–3 yr1–3 wk$350–2,000 amortised
Dry-break QD CRIT25+ yr / on failure2–6 wkin kit
EPDM gasket / O-ring kit CRIT1 kit2–5 yr / on each joint break2–4 wk$100–400
Pump seal kit REC11–3 yr (runtime)2–4 wk$100–300 amortised
Spare pump REC1 / fleet5–10 yr4–12 wkcapex $600–3,500/fleet
Inhibitor / biocide REC1 dose packper quarterly sample1–3 wk$100–400
Flow / dP / temp sensors REC1 of each5–10 yr2–6 wk$100–500 amortised
Leak rope + controller CRIT1 rope spare7–10 yr / on failure2–6 wkon failure
Budget roll-up (EST, per CDU) — recurring consumables (filters, fluid top-up, dosing, amortised seals/sensors) sum to roughly $1,000–4,000 / yr. A one-time on-site critical-spare kit (2× filter, 2× QD, 1× gasket kit, 1× seal kit, 1× leak-rope spare) runs roughly $1,500–6,000, plus a shared fleet spare pump at $600–3,500. These are EST planning bands rolled up from the register above — not a quote; size to your fleet count, runtime hours and OEM service-parts pricing. The dominant driver is usually filter elements (frequency) and fluid (charge volume × $/L).

08 Exploded-view & IPB resources — per CDU type

Exact service-part numbers live in each unit's Illustrated Parts Breakdown (IPB) / service manual — request it from the OEM for your model (it is not public for most CDUs). Below, per CDU type, are the representative manufacturers and where to obtain the exploded-view / parts documentation. Match your unit to a row in the CDU comparison to find its OEM, then pull that OEM's manual.

In-Rack

L2L · in-cabinet 3U–4U

Compact in-rack CDU. Exploded views cover the pump module, plate-HX, filter and QD manifold. Request the model's service manual / IPB.

In-Row

L2L · between-rack cabinet

The density workhorse. IPB covers dual-pump skid, expansion tank, dual-stage filtration, instrumentation & control valve.

Sidecar

L2L · rack-side slim unit

Slim rack-mounted unit. Exploded views focus on the side-mounted HX/pump pack and rack-manifold QDs.

L2L · End-of-Row

L2L · facility-scale

Large facility-coupled CDU (e.g. ≈2.3 MW). IPB covers large plate-HX, N+1 pump bank, facility-water interface & PSV.

L2A · Air-cooled

L2A · room-air reject

Liquid-to-air unit — no facility water. Exploded views add the air-side reject coil, fans & air filter to the standard liquid pack.

External links open the manufacturer's site — navigate to Support / Documentation and request the service manual or IPB for your exact model. These pages may block automated access but open normally in a browser.

09 Symptom → cause → action

Troubleshooting reference. On any active symptom: protect the IT load first (the CDU's N+1 / isolation logic), then diagnose.

SymptomLikely causeImmediate actionCorrective action
High differential pressureFilter clogging; valve throttled; air pocketCheck filter dP; confirm valves open; bleed airReplace filter; re-balance; full de-air
Low / no flowPump fault; closed valve; QD not seated; airlockConfirm standby pump took over (N+1); check valves/QDService/replace pump; reseat QD; purge air
Leak alarmLoose QD; failed seal/gasket; manifold/HX leakAcknowledge → isolate affected zone; locate via rope/zoneTighten/replace QD or seal; pressure-test; refill + de-air
High coolant supply tempFacility water warm/low flow (L2L); HX fouling; high ATDCheck primary supply temp/flow; check ATDRestore CDW; clean HX; verify control setpoint
High room temp (L2A)Room CRAH can't absorb rejected heat; coil dirtyCheck CRAH capacity/airflow; clean coilAdd room cooling / move to L2L; coil service
Rising ATD (approach)Heat-exchanger fouling; reduced flow one sideCompare primary/secondary ΔT; check flowsClean/flush HX; restore flow
Pump fault / vibrationBearing/seal wear; cavitation (low pressure/air)Switch to standby; raise system pressure; de-airReplace pump/seal; correct expansion control
Coolant chemistry out of bandBiology growth; glycol degradation; contaminationSample; dose biocide / inhibitorPartial/full coolant replacement; side-stream filtration
Air in loop (gurgling, unstable dP)Incomplete de-air; make-up drawing air; leakBleed at high points; check make-upFind/seal air ingress; re-fill correctly
Stale / lost telemetrySensor fault; comms loss to BMSTreat values as suspect; local gauge checkReplace sensor; restore comms; re-cal
Condensation / sweating on plates & pipeSupply temp driven below room dew point; dew-point reset disabled / RH sensor faultRaise supply setpoint above room dew point; check RH sensorEnable dew-point-aware reset (≥2–3 °C above dew point); fix humidity sensor; insulate
GPU throttling / hot sledsFlow maldistribution across the manifold; under-provisioned flow vs chip TDPCompare per-branch flow; verify total flow ≥ design L/min/kWBalance manifold (balancing valves / flow restrictors); raise flow setpoint
Two-phase cold-plate dry-out (2-phase)Vapour quality too high in hot sleds; uneven 2-phase distributionCheck refrigerant charge / sub-cooling; inspect distributionRe-balance flow restrictors; restore charge; correct manifold geometry
Frequent make-up / falling levelSlow leak; air being purged; expansion bladder faultTrend make-up rate + level (LT); leak walk-downFind/seal leak; recharge / replace expansion bladder; re-pressurise
Control valve fault (TCV)Actuator demand vs feedback >10%; signal loss → fail to bypass = no coolingSwitch to manual / verify fail-safe position; protect IT loadRe-stroke / replace actuator; re-tune PID (Ziegler-Nichols)
System over-pressureThermal expansion with closed expansion path; PSV not relievingVerify expansion/relief path open; check PT vs component PNRestore expansion control; test/replace PSV; re-set fill pressure

10 FMECA fault reference — liquid cooling (F11.x)

The five direct-to-chip liquid-cooling fault modes from the site's FMECA knowledge graph, ordered by RPN (Risk Priority Number = Severity × Occurrence × Detectability, per IEC 60812). These are the same faults the Mini-BMS injects and the §07 register stocks against. Higher RPN → act first — but RPN can understate a high-severity, rarely-occurring fault: F11.2 (pump failure) scores S=10 yet RPN=60 because it's detectable and infrequent. Expand a card for component, mechanism, effect chain, detection, and corrective/preventive actions.

STD published code / standard (ASME · OCP) VENDOR vendor data (Vertiv · 3M)
F11.1Coolant chemistry driftRPN 140ASME · HIGH
ComponentCDU coolant / dielectric fluid (C-LQC-005)
MechanismCoolant pH / conductivity drift (M-CHM-005)
EffectpH / conductivity drift → long-term cold-plate corrosion → reduced asset life
DetectionConductivity · pH · TDS · ORP
CorrectiveCoolant change + flush (on detection)
PreventiveInline chemistry monitoring (continuous)
754RPN 140
F11.4Dielectric fluid degradationRPN 1203M · THIN
ComponentDielectric fluid (single-phase) (C-LQC-005)
MechanismDielectric fluid oxidation (M-CHM-006)
EffectViscosity rise · dielectric-strength fall → heat-transfer loss
DetectionFluid sample analysis
CorrectiveFluid replacement (on detection)
PreventiveQuarterly fluid sample
645RPN 120
F11.3Manifold / hose leakRPN 108OCP · MEDIUM
ComponentIn-rack manifold (C-LQC-003)
MechanismHose / fitting leak (M-MEC-009)
EffectCoolant spill → electrical-short risk · rack damage → IT loss + cleanup (24–168 h)
DetectionLeak rope · drip-pan · pressure decay
CorrectiveReplace QD or hose (on detection)
PreventivePressure-decay test (quarterly)
943RPN 108
F11.2CDU pump failure · S=10 catastrophicRPN 60Vertiv · THIN
ComponentCDU canned-rotor pump (C-LQC-001 · ~50,000 h MTBF)
MechanismPump bearing wear (M-WER-007)
EffectFlow loss to cold plates → CPU thermal trip in <10 s → server reboot / damage (0–4 h)
DetectionFlow meter · ΔP · pump vibration
CorrectiveReplace CDU pump (on detection)
PreventiveN+1 pump + vibration test (monthly)
1032RPN 60
F11.5Filter cloggingRPN 60OCP · MEDIUM
ComponentFilter (5–50 µm) (C-LQC-007)
MechanismCDU filter loading (M-FOU-005)
EffectΔP across filter rises → secondary-loop flow loss → ΔT / approach creep
DetectionFilter ΔP
CorrectiveReplace filter (on detection)
PreventiveMonitor filter ΔP (monthly)
562RPN 60
Source. FMECA-KG seed (Lin & Ompusunggu 2026 synthesis; per-fault: ASME J.Electron.Packag. 140 020902 · Vertiv · OCP · 3M) at docs/research/csv/. S·O·D + RPN per IEC 60812; confidence tiers (HIGH / MEDIUM / THIN) reflect data provenance — vendor MTBF is often confidential. Full knowledge base + ML advisory concept: AI Engineering Maintenance.

11 CDU service record — printable form

Fill on-screen and Print / Save as PDF. Captures site identity, readings against the §01 band, checklist pass/fail, and sign-off. Stored on the RZ site as the standard CDU service-record form.

Readings vs target band

ParameterTarget bandReadingPass / Fail
Supply temp (°C)~17–45
ΔT (°C)~8–12
Flow (LPM/kW)~1.0–1.5
Differential pressure (bar)~0.5–3.0
System pressure (bar)~2–6
Coolant pH / cond. / glycol%ASHRAE W1–W4
Filter dP / statusclean range
Leak detection0 leaks
Pump N+1 (duty/standby)both healthy
Disclaimer. Independent educational reference built from publicly available vendor pages and ASHRAE TC 9.9 / OCP guidance. Parameter bands are generic baselines — confirm exact limits, fluid spec, torque/pressure values and PM intervals against the specific CDU's manufacturer manual and your IT hardware spec. Not procurement, safety, or engineering advice; validate with the vendor and a qualified mechanical engineer.