Home / DC Solutions / Technical Manuals / Conventional DC Cockpit

Technical Manual · Cockpit Basis

Conventional DC — EPMS & BMS Cockpit — Methodology & Formulas

Every KPI, formula, constant, and cross-page binding behind the Conventional DC EPMS/BMS cockpit. All values derive deterministically from the adopted four-hall basis in js/conv-engine.js (CONV_CALC) — no user inputs, no random seeding, no back-solved constants. The locked operating point is 30 MW IT / 43.5 MW facility; the 40 MW IT / 58 MW facility figures are the declared 100% design point.

Engine CONV_CALC v2.0.0 Campus 4 × 7.5 MW CURRENT Inputs LOCKED Outputs 20+ Accuracy rules 6
▶ Open the simulated Conventional DC Cockpit

01 Purpose & engineering basis

The Conventional DC cockpit is a simulated EPMS/BMS monitoring and anomaly-detection aid for a chilled-water, UPS-backed, generator-protected data centre. It answers five questions within one deterministic scenario: what is the modeled energy balance, is cooling performing within design, how are the UPS modules loaded, how much fuel autonomy remains, and how do site sustainability metrics (PUE/WUE/CUE) compare to design targets. It neither connects to nor controls field equipment.

This page is a cockpit, not a calculator. Its basis of design is fixed: the scenario constants in CONV_MODEL (locked, deep-frozen) drive every displayed number. The governing accuracy contract is the ACCURACY_VALIDATION 6 rules (one source of truth · no Math.random on basis KPIs · explicit denominator on every metric · marketing target ≠ derived value · terminology must match engineering basis · basis chip on every critical KPI), plus the 23 acceptance tests in tools/probe-accuracy-validation.mjs. Basis document: conv/review/09-engineering-basis-and-calculations.md.

02 Inputs — locked basis-of-design

There are no user inputs. The table distinguishes authored/adopted inputs from the derived campus snapshot in CONV_MODEL and CONV_CALC.snapshot. Capacity geometry comes from the governed four-hall design basis; equipment nameplates remain explicitly assumed pending Basis-of-Design confirmation.

ParameterSymbol / keyValueUnitSource
Hall countcampus.hall_count4hallGoverned four-hall design basis; adopted geometry
IT design capacitysite.it_design_kw40 000 campus / 10 000 per hallkWDerived from 4 governed halls
IT load (adopted current)site.it_load_kw30 000 campus / 7 500 per hallkWAdopted normal scenario; simulated, not measured
Rack inventorycampus.racks_total2 000 campus / 500 per hallrackGoverned hall geometry
Rack current / design averagerack_actual_avg_kw / rack_design_avg_kw15 / 20kW/rackDerived current load / governed design basis
Power usage effectivenesspue1.45—doc-09 line 11
Water usage effectivenesswue_l_per_kwh1.20L/kWhdoc-09 line 13
Grid carbon intensitycarbon_kg_per_facility_kwh0.42kgCO₂/kWhdoc-09 line 14, denominator = facility kWh
Cold-aisle average temperatureavg_temp_c22.4°Cdoc-01 §Right-Side Stats Panel; ASHRAE TC9.9 recommended band
Average relative humidityavg_rh_pct48%doc-01/09 environment row; ASHRAE 40–60% band midpoint
Rack-inlet targetrack_inlet_target_c25.4°CAdopted project target
CHW coil approachchw_coil_approach_k6.0KAssumed pending coil selection
CHW supply / returnchws_c / chwr_c19.4 / 27.0°CDerived thermal chain; 7.6 K adopted rise
Chillers running / totalchillers_running / chillers_total7 / 10—Derived at 5,000 kWth/unit and central N+1; unit rating assumed
UPS efficiencyups_efficiency0.96—Retained sourced efficiency; current computed loss is 1,250 kW
UPS module topology (2N)ups_module_count64 total; 32/system × 1 250 kWmodule / kWDerived from 40 MW design and 2N; module rating assumed
EPMS metering tolerancemetering_tolerance_pct2%doc-12 line 9 "within 2%"
Fuel tank capacitytank_capacity_l972 737LAssumed tank sizing to retain the 48 h target at current campus burn
Tank usable fractionusable_fraction0.90—doc-09 line 141
Fuel levellevel_pct85%doc-09 lines 16, 126
Specific fuel consumptionspecific_consumption_l_per_kwh0.356384L/kWhSourced rate retained across the campus rebaseline; the retired fixed burn nameplate is not reused
Accuracy rule 4: None of these values is a marketing target presented as a measured outcome. PUE 1.45 is the engineering basis from doc-09, not a best-in-class aspirational figure. The cockpit displays these as design basis chips, not live telemetry.

03 Calculation methodology

All derivations are pure functions inside CONV_CALC. Function names below map one-to-one to js/conv-engine.js. No formula exists outside the engine.

Facility and non-IT load

Facility = IT × PUE → 30 000 × 1.45 = 43 500 kW Non-IT = Facility − IT → 43 500 − 30 000 = 13 500 kW In facilityLoadKw(m), nonItLoadKw(m). Facility is the total metered input to the site; Non-IT covers cooling, lighting, UPS losses, and all ancillaries. Both are rendered on the dashboard energy panel.doc-09 lines 25–28, 32–34

PUE reconciliation

PUE = Facility / IT = 43 500 / 30 000 = 1.45 (identity check) The cockpit renders PUE as the ratio Facility÷IT. The locked value must always reconcile to exactly 1.45 — any other display would violate accuracy rule 1 (one source of truth). Denominator is IT load (not design capacity).doc-09 line 11; ACCURACY_VALIDATION rule 3

UPS losses

UPS loss = IT × (1/η − 1) → 30 000 × (1/0.96 − 1) = 1 250 kW Normal shared system load = IT / 2 → 30 000 / 2 = 15 000 kW/system Normal module load = IT / 64 → 30 000 / 64 = 468.75 kW/module In upsLossKw(m), upsSystemKw(m), upsModuleKw(m). Two independent 2N systems each have 32 × 1,250 kW modules and 40,000 kW rated capacity; each system can carry the full protected load. Normal operation shares 15,000 kW per system, while failover is 30,000 kW on one system. Equipment ratings are assumed pending an approved schedule.governed 2N resilience contract; engine v2.0.0

Chilled-water loop

CRAH supply = rack inlet − supply mixing → 25.4 − 0.0 = 25.4 °C CHWS = CRAH supply − coil approach → 25.4 − 6.0 = 19.4 °C ΔT = CHWR − CHWS → 27.0 − 19.4 = 7.6 K IT sensible-load CHW reference = IT / (Cp × ΔT) → 30 000 / (4.186 × 7.6) = 943.0 L/s Evaporator duty = IT + UPS loss → 30 000 + 1 250 = 31 250 kW Plant-duty CHW reference = Qevap / (Cp × ΔT) → 31 250 / (4.186 × 7.6) = 982.3 L/s Condenser/tower rejection = Qevap + chiller kW → 31 250 + 5 153.4 = 36 403.4 kW In crahSupplyAirC(m), chwsC(m), chwrC(m), chwFlowLps(m) and the historical compatibility function heatRejectionKw(m). Despite that API name, snapshot.cooling.heat_rejection_kw is evaporator duty; true tower rejection is tower_rejection_kw_th. Cp = 4.186 kJ/(kg·K) for water. The 6.0 K coil approach is assumed pending selection. Both flow values are calculated references; measured header flow is UNAVAILABLE. The separate condenser-water loop is 32.0/37.0°C and must not be labelled CHWS/CHWR.governed rack-inlet target; engine v2 thermal chain

Water usage effectiveness (WUE)

WUE = annual cooling makeup water [L] / annual IT energy [kWh] = 1.20 L/kWh Equivalent cooling makeup = (WUE × IT) / 60 → (1.20 × 30 000) / 60 = 600.0 L/min Total treated flow = cooling makeup + domestic/process → 600.0 + 8.0 = 608.0 L/min In waterFlowLpmForWue(m). WUE definition and reporting context follow ISO/IEC 30134-9. The cockpit shows a steady-state equivalent cooling-makeup rate, not a measured instantaneous flow. Domestic/process demand is excluded from WUE.CONV_CALC.snapshot.water.flow_lpm_for_wue; engine v2.0.0; ISO/IEC 30134-9:2022

Carbon usage effectiveness (CUE)

CUE = carbon emission rate [kgCO₂/hr] / IT power [kW] Carbon rate = Facility × grid factor → 43 500 × 0.42 = 18 270 kgCO₂/hr CUE (IT-basis) = grid factor × PUE → 0.42 × 1.45 = 0.609 kgCO₂/kWh-IT In carbonKgPerHr(m). CUE per ISO/IEC 30134-8 uses the facility-energy denominator for the grid carbon factor (0.42 kgCO₂/kWh is stated as a facility-energy intensity in doc-09 line 14). The IT-basis form CUE = grid factor × PUE is a derived identity. Denominator must be explicit on every CUE display (accuracy rule 3).doc-09 lines 155–158, 167; ISO/IEC 30134-8

Fuel autonomy

Usable fuel = capacity × usable fraction × fill level = 972 737 × 0.90 × 0.85 = 744 144 L Generator burn = Facility × specific consumption = 43 500 × 0.356384 = 15 503 L/hr Autonomy = usable fuel / generator consumption rate = 744 144 / 15 503 = 48.0 hr In generatorConsumptionLph(m), fuelUsableL(m), fuelAutonomyHr(m). The 48 hr value is this project's assumed tank-sizing result. It does not prove an Uptime Tier or universal minimum; approved generator curves, running-set allocation, refuelling logistics and authority requirements govern operational duration.sourced specific-consumption rate; adopted campus basis

Rack inventory and density

Campus rack inventory = 4 halls × 500 racks/hall = 2 000 racks Current average density = 30 000 kW / 2 000 racks = 15 kW/rack Design average density = 40 000 kW / 2 000 racks = 20 kW/rack The selected hall always retains 500 racks, 7,500 kW current load and 15 kW/rack current average. These are governed geometry and scenario values, not equivalent-rack estimates.governed four-hall rack basis; engine v2.0.0

EPMS power metering

EPMS total = Facility load = 43 500 kW (nominal; tolerance band ±2%) EPMS UPS output = IT load = 30 000 kW (mechanical on gen-backed board) In epmsTotalKw(m), epmsUpsOutputKw(m). Metering tolerance ±2% is a quality flag, not an applied offset — the cockpit shows nominal values. EPMS = Electrical Power Monitoring System.doc-00 line 77; doc-12 line 9

Governed four-hall operating and design points

Current IT = 4 halls × 7.5 MW IT/hall = 30 MW IT Current rack basis = 500 racks/hall × 15 kW/rack average = 7.5 MW IT/hall Design IT = 4 halls × 10 MW IT/hall = 40 MW IT Design rack basis = 500 racks/hall × 20 kW/rack average = 10 MW IT/hall Design facility input = 40 MW IT × dPUE 1.45 = 58 MW at the declared 100% design point The governed RZConvDesignBasis.STUDY supplies the adopted geometry and 100% capacity envelope; CONV_CALC supplies the locked 30 MW operating point. Its rack thermal contract is chilled-water CRAH with a 25.4°C rack-inlet target. As an explicit rejected counterexample only, 200 racks/hall would imply 50 kW/rack and fails that selected air-side contract. The 40 MW/58 MW result is a design point, not current telemetry; part-load performance beyond the adopted point remains unavailable without an approved curve.

04 Constants & data sources

Every constant lives in the deep-frozen CONV_MODEL object with a // source: tag pointing to conv review doc line numbers. The snapshot table confirms all computed intermediates at the locked basis point.

Computed quantityFunctionResultUnit
Facility loadfacilityLoadKw()43 500kW
Non-IT loadnonItLoadKw()13 500kW
UPS lossupsLossKw()1 250kW
CHW ΔTchwDeltaT()7.6K
IT sensible-load CHW referencechwFlowLps()943.0L/s
Plant-duty CHW referenceheatRejectionKw() / (Cp × ΔT)982.3L/s
Measured CHW header flownot boundUNAVAILABLEL/s
Evaporator dutyheatRejectionKw() compatibility API31 250kW
Condenser / tower rejectionsnapshot.cooling.tower_rejection_kw_th36 403.4kW
UPS per-module loadupsModuleKw()468.8kW
UPS per-system loadupsSystemKw()15 000kW
Cooling makeup flowwaterFlowLpmForWue()600.0L/min
Carbon emission ratecarbonKgPerHr()18 270kgCO₂/hr
Usable fuelfuelUsableL()744 144L
Generator fuel burngeneratorConsumptionLph()15 503L/hr
Fuel autonomyfuelAutonomyHr()48.0hr
Accuracy rule 2: None of these values involves Math.random(). Every number is stable on reload, reproducible in Node, and covered by the current tools/test-conv-calc.mjs and campus-model assertions.

05 Outputs & cockpit panels

The cockpit surfaces these derived quantities across its dashboard, EPMS, cooling, water, fuel, and sustainability panels. Each KPI carries a basis chip citing its source.

KPICONV_CALC functionUnitPanel
IT loadmodel.site.it_load_kwkWEnergy dashboard
Facility loadfacilityLoadKw()kWEnergy dashboard / EPMS total
Non-IT loadnonItLoadKw()kWEnergy breakdown
PUEFacility / IT (identity)—Sustainability header
WUEmodel.environment.wue_l_per_kwhL/kWhSustainability / water panel
CUE (IT-basis)grid factor × PUEkgCO₂/kWh-ITSustainability panel
Carbon ratecarbonKgPerHr()kgCO₂/hrSustainability panel
UPS lossupsLossKw()kWEPMS electrical panel
UPS per-module kWupsModuleKw()kWEPMS UPS A / UPS B gauges
CHW supply / returnmodel.cooling.chws_c / chwr_c°CCooling panel — primary loop only
CHW ΔTchwDeltaT()KCooling panel
IT sensible-load CHW referencechwFlowLps()L/sCooling panel; calculated, not measured
Plant-duty CHW referenceheatRejectionKw() / (Cp × ΔT)L/sCooling reconciliation; calculated, not measured
Evaporator dutyheatRejectionKw() compatibility APIkWCooling plant duty
Condenser / tower rejectionsnapshot.cooling.tower_rejection_kw_thkWCondenser-water / heat-rejection plane
Chillers running / totalmodel.cooling.chillers_*—Cooling panel status
Water makeup flowwaterFlowLpmForWue()L/minWater panel
Fuel level / usablemodel.fuel.level_pct / fuelUsableL()% / LFuel panel gauge
Fuel autonomyfuelAutonomyHr()hrFuel panel — 48 hr project/model result
Rack inventory / current densitysnapshot.campusrack / kW·rack⁻¹2,000 campus / 500 per hall / 15 kW current average
Avg temperature / RHmodel.environment.avg_temp_c / avg_rh_pct°C / %Environment panel
EPMS metering tolerancemodel.electrical.metering_tolerance_pct%EPMS quality chip
Current Design Studio snapshotCONV_CALC.snapshotkWCurrent scope: locked 30,000 kW campus IT / 43,500 kW facility
Four-hall design-point appendix4 × 10 MW IT; 500 racks/hall; 20 kW/rack design averageMW IT / rack / kW·rack⁻¹Current-plus-study scope: governed 40 MW IT / 58 MW facility design-point study
Release acceptanceExecutable evidenceRequired invariant
Locked calculation chaintools/test-conv-calc.mjs and tools/test-conv-campus-model.mjsThe current snapshot retains 30,000 kW IT, four equal 7,500 kW halls and all documented identities.
Design Studio scopestools/test-rz-design-studio.mjs plus browser/PDF journeyCurrent renders the adopted 30 MW operating point; current-plus-study adds the governed 40 MW/58 MW design-point study without mutating CONV_CALC.snapshot.
EPMS source truthtools/test-epms-ats-rack-color.mjsNormal, tie and generator scenarios derive the final ATS-to-rack conductor from its actual energizing source.
Accessible document flowKeyboard and dialog browser journeyLabeled controls, focus trap, Escape/scrim/close and trigger-focus return remain intact; failures are visible.

06 Worked example — adopted 30 MW campus scenario

Full derivation chain reproducing every primary KPI on the simulated cockpit exactly. All figures match CONV_CALC.snapshot.

  1. Facility load: 30 000 × 1.45 = 43 500 kW
  2. Non-IT load: 43 500 − 30 000 = 13 500 kW
  3. PUE reconciliation: 43 500 / 30 000 = 1.45 ✓ (identity holds)
  4. UPS loss: 30 000 × (1/0.96 − 1) = 1 250 kW · normal system load: 30 000 / 2 = 15 000 kW · module load: 30 000 / 64 = 468.75 kW
  5. CHW references: 27.0 − 19.4 = 7.6 K · IT sensible-load reference: 30 000 / (4.186 × 7.6) = 943.0 L/s · evaporator-duty reference: 31 250 / (4.186 × 7.6) = 982.3 L/s · measured header flow: UNAVAILABLE
  6. Thermal duties: evaporator: 30 000 + 1 250 = 31 250 kW · condenser/tower: 31 250 + 5 153.4 = 36 403.4 kW
  7. WUE check: 1.20 L/kWh (basis) · equivalent cooling makeup: (1.20 × 30 000) / 60 = 600.0 L/min
  8. Carbon rate: 43 500 × 0.42 = 18 270 kgCO₂/hr · CUE (IT-basis): 0.42 × 1.45 = 0.609 kgCO₂/kWh-IT
  9. Usable fuel: 972 737 × 0.90 × 0.85 = 744 144 L · burn: 43 500 × 0.356384 = 15 503 L/hr · autonomy: 744 144 / 15 503 = 48.0 hr
  10. Rack reconciliation: 4 × 500 = 2 000 racks · 30 000 / 2 000 = 15 kW/rack current average
Engineering reading: the cockpit operates at 75% of modeled IT design capacity (30,000/40,000 kW), equally allocated as 7,500 kW across four 500-rack halls. PUE 1.45 and 48 h autonomy are declared scenario values, not universal quality grades, code baselines or Tier evidence. Operational targets require an approved metering boundary, load profile, climate basis, risk policy and certification review.

07 References & standards

08 Assumptions & limitations

The cockpit models a single fixed engineering scenario. It is not a design calculator and cannot be parameterised. Key assumptions and scope boundaries:

CHW loop: The adopted warm-water chilled-water loop is 19.4/27.0°C at 7.6 K rise. CHWS derives from the 25.4°C rack-inlet target and an assumed 6.0 K coil approach pending equipment selection. The separate condenser-water loop is 32.0/37.0°C and is never labelled CHWS/CHWR.

UPS topology: The 2N model has two independent systems, each rated 40,000 kW using 32 × 1,250 kW assumed modules. Normal load is 15,000 kW/system and 468.8 kW/module; failover places 30,000 kW on one system. Static bypass and detailed fault selectivity require an approved topology study.

Fuel consumption: 15,503 L/hr derives from 43,500 kW facility load × 0.356384 L/kWh. It is an engineering sizing assumption, not a live meter or a substitute for vendor part-load curves and running-set allocation.

WUE and water flow: The 600.0 L/min figure is the steady-state equivalent cooling makeup derived from annual WUE. Actual cooling-tower blowdown, drift loss and basin makeup vary with ambient wet-bulb temperature. Domestic/process demand adds 8.0 L/min but is excluded from WUE.

Carbon intensity: 0.42 kgCO₂/kWh is a fixed grid-average factor from the engineering basis. Real-time grid decarbonisation, marginal emissions, and Scope 2 market-based accounting are out of scope.

Capacity planning: Four 500-rack halls are adopted: each hall carries 7.5 MW current IT at 15 kW/rack average and has 10 MW design IT at 20 kW/rack average. The 30 MW current scenario is simulated/adopted, not installed, energized, commissioned or measured evidence. The 40 MW IT / 58 MW facility values remain the 100% design point.

Design-point efficiency: 1.45 is the declared PUE at the adopted operating point and dPUE at 100% design, not an approved part-load curve or annual measured PUE. Other operating points fail closed until an approved monotonic curve is supplied.

Design Studio: The current scope is generated from the captured 30 MW CONV_CALC.snapshot. The current-plus-study scope appends the governed 40 MW/58 MW design-point study; changing scope does not change cockpit data.

This manual and the cockpit are an engineering education and operational reference aid. They do not substitute for a live DCIM/EPMS/BMS with calibrated sensors, metered telemetry, and alarm setpoints set by a qualified controls engineer to the site authority having jurisdiction.

09 Cockpit controls & telemetry map

The dashboard is a facility overview rather than a command HMI. Its controls navigate, explain or report the locked scenario; none writes to BMS/EPMS equipment.

Control / surfaceHookExpected behaviorData or safety boundary
Portfolio / DC Solutions / PRD / Manual.back-btnNavigate without changing CONV_CALC.snapshot.PRD and Manual are public; cockpit access remains tier-controlled.
Generate Design / Design StudiogenDesignTrigConv, RZDesignStudioOpen the shared dialog, show captured snapshot/provenance, and select current or current-plus-study before generating the approved document type.The design-point study appendix cannot mutate current values; focus is trapped and returned, and generation failure remains visible.
FAQfaqTrigConvOpen ten explanatory questions; close by button, scrim or Escape.Answers disclose locked, simulated and non-procurement scope.
ThemethemeToggleSwitch/persist light or dark theme.Never changes values or threshold results.
Subsystem routes.nav-menu-itemOpen EPMS, Data Hall, Chiller, Fire, Fuel, Water or ICT pages.Status copy in this overview is not a substitute for subsystem detail.
EPMS source-truth pathw_ats_rack_* in EPMS_Telemetry.htmlCarry the actual selected source state through the ATS and its final rack conductor in normal, tie and generator scenarios.Feed A is red/A and Feed B is green/B; source/state text supplements color, and no click issues a field command.
Alarm stripalarmStripShow overall state, critical, warning, maintenance/bypass, comms, stale, last update, quality and scenario first.Counts are evaluated from a frozen model; Last Update is browser time.
PUE basis.kpi-card[data-basis-param="site.pue"]Open formula, 30,000 kW IT / 43,500 kW facility / 13,500 kW non-IT inputs, scope, denominator and source.1.45 is the adopted design-point ratio and facility load reconciles as IT × PUE; ≤1.5 is a target.
WUE basisdata-basis-param="environment.wue_l_per_kwh"Explain annual definition, IT denominator and 600.0 L/min equivalent cooling makeup.Equivalent steady-state rate is not an instantaneous tower meter.
Grid-factor basisdata-basis-param="environment.carbon_kg_per_facility_kwh"Separate 0.42 kgCO₂/kWh facility from CUE_IT and 18,270 kgCO₂/h current rate.Factor needs geography/date/version before reporting.
IT-load basisdata-basis-param="site.it_load_kw"Show 30,000/40,000 kW campus, 75% utilization and selected-hall scope.Simulated/adopted BOD, not a meter stream.
Uptime basisdata-basis="uptime"Explain — / UNAVAILABLE and the required downtime event log.No numeric or healthy-state placeholder is allowed until an authenticated outage ledger is bound.
Temperature basisdata-basis="temp"Explain 22.4°C against the referenced thermal band.Simulated aggregate, not a sensor roll-up.
Chiller basisdata-basis-param="cooling.chillers_running"Explain 7/10 operation, 5,000 kWth/unit assumption and central N+1 sizing.Three non-running units include capacity headroom and are not automatically maintenance/bypass events.
KPI keyboard path.kpi-card[data-basis-param]Enter/Space opens; Escape, scrim and Close dismiss; focus returns.All meaning remains textual, not color-only.
Facility image calloutscPue, cIt, cChw, cTemp, cFuel, cRhShow the six operational values on their physical context image.Image is contextual; right panel and basis drawers are authoritative for scope.
Right statistics panels* IDs plus static rowsGroup Efficiency, Power, Cooling, Reliability, Environment, Safety and Fuel.Engine-bound and static presentation rows must remain visibly distinguishable.
Scroll to topscrollTopBtnReturn to header without changing the scenario.Respect reduced-motion preference.
Sign inrootLoginBtn / shared gateOpen the shared authentication/upgrade flow for an unauthorized cockpit user.It grants no access to public docs because they are already public.

10 Alarm, quality & operating interpretation

Primary arithmetic is deterministic. Several context rows remain static placeholders. The following map prevents a reader from assigning the same trust level to both classes.

Point familyRepresentative hookSource classInterpretation / threshold
PUE / WUE / grid / IT / facilitykpiPue, kpiWue, kpiCarbon, kpiIt, sTotalLoadLocked or derived from CONV_CALC.snapshot.Stable on reload; PUE warns above 1.5.
CHWS / CHWR / environment / fuelsChwSup, sChwRet, sTempAvg, sRhAvg, sFuelMainLocked BOD/simulated aggregate.Temperature warns outside 18–27°C and critical above 32°C; RH warns outside 20–80%; fuel warns below 24 h and critical below 12 h autonomy.
Maintenance / bypassas-maintDerived as 10 installed − 7 running chillers.Current value 3 includes capacity headroom; it is not proof of three maintenance events.
Comms / staleas-comms, as-staleModel-integrity check.Comms OK means a versioned local snapshot exists; stale 0 means the frozen scenario has no acquisition-age concept.
Last Updateas-updateBrowser clock.Display time, not field sample time.
UPS A/BsUpsA, sUpsBDerived from two 40,000 kW-rated systems, 32 × 1,250 kW modules/system.15,000 kW/system normal (37.5%); 30,000 kW failover (75%); nameplates remain assumed pending approved schedule.
ChillersChillers row / shared basis drawer7/10 derived from current 31,250 kW evaporator duty, 5,000 kWth/unit and central N+1.Per-hall allocation remains unavailable until the hydronic distribution design exists.
Network / topology / uptimeNetwork, UPS Topology, Uptime rowsUNAVAILABLE.No dedicated network/topology authority or authenticated downtime event log is bound on the overview.
Environment DPDifferential Pressure rowUNAVAILABLE.No pressure-sensor source, timestamp or alarm threshold is currently bound.
FACP / VESDASafety rowsUNAVAILABLE.The overview has no bound fire-panel authority; the dedicated Fire cockpit owns validated fire state.
Day tankDay Tank rowUNAVAILABLE.Bulk-tank 85%/48 h arithmetic does not validate a separate per-genset buffer value.
Data Quality / Scenarioas-dq, as-scnSnapshot metadata.GOOD describes internal model availability; Simulated is the governing provenance.
EPMS final rack pathw_ats_rack_*Modeled topology state in EPMS_Telemetry.html.The conductor inherits its actual energizing source; red/green never replaces source and energized-state text.
Four-hall design-point appendixDesign Studio current-plus-studyGoverned planning-study envelope paired with the adopted operating snapshot.4 × 10 MW = 40 MW IT and 58 MW facility are the design-point study; current remains 4 × 7.5 MW = 30 MW IT.
Alarm sequence: critical count has priority over warning. The current model does not implement acknowledgement, shelving, suppression, cause/effect or an event historian. A future field implementation should follow the ISA-18 series and IEC 62682:2022, with point-level freshness and quality. These references define direction and terminology, not current conformance.

11 Glossary & RZExplain

Marked terms are discoverable through the shared RZExplain scanner. Definitions below use the exact denominator and scope implemented by this cockpit.

TermCockpit meaningCommon misread
PUEFacility power / IT power = 43,500 / 30,000 = 1.45.Target efficiency or cooling-only ratio.
WUEAnnual cooling makeup water litres / annual IT kWh = 1.20 L/kWh.All site water or instantaneous tower flow.
CUECarbon per IT energy = grid factor × PUE = 0.609 kgCO₂/kWh IT.The raw 0.42 facility-kWh grid factor.
CHWS / CHWRWarm-water chilled-water supply/return at 19.4/27.0°C.The separate 32.0/37.0°C condenser-water loop.
EPMSElectrical Power Monitoring System; route from the subsystem rail.A control authorization or protection study.
BMSBuilding Management System context for cooling/environment/safety integration.A live field connection in this page.
2NTwo independent UPS paths, each able to carry the protected load.Two modules whose combined capacity alone meets load.
Facility loadAll site input power inside the PUE boundary.IT output alone.
Non-IT loadFacility − IT = cooling, losses and auxiliary demand.Only chiller compressor power.
Locked / derived / placeholderImmutable assumption / formula output / value awaiting authoritative history or sensor source.Equivalent forms of live telemetry.
▶ Open the simulated Conventional DC EPMS/BMS Cockpit