Operational question
Which utility or generator path is feeding each stream, which breakers are closed/open/tripped, and what downstream equipment is affected?
A testable contract for the source-transfer, breaker, power-flow, telemetry and export behavior in EPMS_Telemetry.html. The page is a simulated teaching cockpit. It is not a live EPMS, protection relay, switching authority or approved operating procedure.
An electrical operator needs a fast read of source availability, transfer state, breaker position, energized paths, load and alarm count without reconstructing topology from a raw point list. A reviewer also needs to know which numbers are engine-bound and which are illustrative simulator values.
Which utility or generator path is feeding each stream, which breakers are closed/open/tripped, and what downstream equipment is affected?
Can the displayed voltage, current, power and site aggregate be reproduced from declared formulas and sources, with simulation clearly separated from metered telemetry?
| Persona | Goal | Primary read | Success condition |
|---|---|---|---|
| Facilities operator | Triage a source loss or breaker trip. | Status strip → one-line → event log. | Names active source, affected stream and breaker state within one scan. |
| Electrical engineer | Review topology, ratings and calculated current. | Source/MV/RMU/TX/LVSB/ATS/UPS/PDU branches and telemetry labels. | Can identify voltage basis, power factor and capacity gaps. |
| Commissioning engineer | Exercise transfer and breaker-state sequences. | Utility/tie controls, breaker gestures, generator state and alarms. | Every action has a deterministic expected state and visible feedback. |
| Design reviewer | Reconcile EPMS totals with the conventional facility basis. | Facility/IT/PUE strip and aggregate rack-group scope. | Top, bottom and terminal roll-ups reconcile without hiding aggregation. |
| Educator / learner | Understand a three-stream protected electrical one-line. | Legend, labels, manual formulas and exports. | Can distinguish a simulated state from an approved switching instruction. |
Every visible control, status family and diagram family is mapped below. Generated equipment instances are covered by their stable ID ranges.
| ID | Visible element / requirement | Acceptance |
|---|---|---|
| FR-01 | Show an engine-bound top strip for Facility Load, IT Load and PUE. | epms-fac, epms-it and epms-pue read a complete CONV_CALC v2.0.0 snapshot: 43.50 MW facility, 30.00 MW current IT and PUE 1.45. |
| FR-01A | Reject missing, legacy, requested-version-mismatched or same-version-incomplete authority. | All engine-owned fields, status chips, drawer values and controls become unavailable/inert without leaking plausible retired values. |
| FR-02 | Show Utility, UPS A/B, generator, trip, data-quality and scenario labels. | Labels remain visible above the one-line and say Simulated rather than Live. |
| FR-03 | Show a five-state line legend: energized, standby, open, alarm/trip and maintenance bypass. | Each state has text plus line sample; meaning is not color-only. |
| FR-04 | Provide Back, Portfolio, PRD and Manual navigation. | All links are keyboard reachable and resolve without changing simulator state. |
| FR-05 | Provide 50%, 75%, 120% and Fit zoom controls. | Each control updates the transform and zoomIndicator. |
| FR-06 | Allow wheel zoom bounded from 15% to 200% and mouse drag pan. | Pointer-centred zoom and pan preserve the selected breaker state. |
| FR-07 | Provide Reset View. | Reset invokes fit-to-screen and records the action in the local log. |
| FR-08 | Provide Export PDF Report, Export CSV Data and Export JSON. | Each action emits current source, generator, breaker and summary state and logs completion. |
| FR-09 | Allow Utility A and Utility B source toggles. | btn-u-a/btn-u-b state, flow and ATS response agree. |
| FR-10 | Allow the MV bus-coupler toggle. | btn-tie and br_mv_tie change together. |
| FR-11 | Show GEN A/B/C status indicators. | Indicators change from standby to running during the associated ATS sequence; they are not presented as manual start controls. |
| FR-12 | Render Utility A/B, streams A/B/C and the A–B MV tie. | Source reachability follows SIM.sources, breaker state and ring/tie logic. |
| FR-13 | Render MV, RMU and transformer groups. | MV_A/B, RMU_A/B/C and TX_A/B/C retain tags, voltage levels and transformer nameplates. |
| FR-14 | Render LVSB, generator and ATS distribution groups. | LVSB_A/B/C, GEN_A/B/C, ATSDB_IT_* and ATSDB_M_* remain connected. |
| FR-15 | Render UPS IT A/B/C and UPS mechanical A/B. | Incoming and downstream paths remain distinct; status labels do not imply metered load. |
| FR-16 | Render ATS panel ties, CDP and mechanical branches. | ATS_PNL1/2, CDP, CH-1…4 and AHU-1/2 appear at stable locations. |
| FR-17 | Render ten DAHU branches. | DAHU_A_0…4 and DAHU_B_0…4 each have breaker, path and telemetry. |
| FR-18 | Render ten aggregate rack-group paths. | Each RACK_0…9 has main/catcher PDU, rack ATS, 3,000 kW and 200-position disclosure. |
| FR-19 | Initialize every wire breaker to closed unless its model declares open. | Generator incomers, tie and catcher-panel alternatives start open; all other modeled defaults match WIRES. |
| FR-20 | Support breaker closed/open/trip simulation. | Click toggles open/closed, Alt sets open and Shift sets trip; state is visible in symbol and alarm count. |
| FR-21 | Run ATS transfer logic for streams A, B and C. | Utility loss opens utility breaker, starts the generator and closes generator breaker after the declared simulated delay; restoration reverses the sequence. |
| FR-22 | Animate only energized paths and preserve source identity. | Flow class is derived from reachable source; final rack leg uses the protected downstream color. |
| FR-23 | Show voltage, current and power on every wire not marked noTele. | tele-<wire-id> labels update to zero when de-energized and calculated/assigned values when energized. |
| FR-24 | Show bottom System, Total Load, Power Factor, Frequency, Breakers, Alarms and timestamp. | Seven groups update without shifting layout; units remain visible. |
| FR-25 | Count closed and total breakers. | val-breakers equals a direct roll-up of SIM.breakers. |
| FR-26 | Count tripped breakers as active alarms. | val-alarms and its fault presentation agree with the number of trip states. |
| FR-27 | Show utility-online or generator-mode system state. | Loss of both utility booleans changes val-system to GEN MODE with warning semantics. |
| FR-28 | Maintain a newest-first local event log. | Source, tie, view and export actions prepend readable entries. |
| FR-29 | Keep simulator scope explicit in reports. | Exported data carries a timestamp and current modeled state; product copy never calls it field telemetry. |
| FR-30 | Preserve the public site shell on documentation pages and the existing cockpit gate/state. | Docs remain public; adding links changes no cockpit control or script. |
Rows enumerate every displayed point family. Wildcards identify generated instances and are the canonical point namespace, not an omission of individual equipment.
| Signal | Symbol / ID | Unit | Nominal / semantics | Source binding |
|---|---|---|---|---|
| Facility load | epms-fac | MW | 43.50; engine-bound campus aggregate. | CONV_CALC.snapshot.site.facility_load_kw / 1000. |
| IT load | epms-it | MW | 30.00; engine-bound protected IT aggregate. | snapshot.site.it_load_kw / 1000. |
| PUE | epms-pue | ratio | 1.45; facility/IT basis. | snapshot.site.pue. |
| Utility summary | top-strip Utility | state | Available source count. | SIM.sources via updateEpmsStatusStrip(). |
| UPS summary | top-strip UPS A/B | state | Governed module/system basis. | snapshot.electrical; not a live UPS register. |
| Generator / trip summary | top-strip Gen / Trips | state / count | Running generator count / open breaker count. | Bound to SIM state. |
| Data quality / scenario | top-strip Data / Scenario | quality / mode | GOOD / Simulated under current authority. | Validated snapshot.meta; unavailable on missing provenance. |
| Utility source availability | SIM.sources.A/B, btn-u-a/b | boolean | Active or off. | User toggle in local simulator. |
| Generator running | SIM.genRunning.A/B/C, btn-gen-a/b/c | boolean | Standby or running. | runATSLogic(). |
| Breaker state | SIM.breakers[br_*] | enum | closed / open / trip; trip is fault-red. | WIRES[].br plus user gesture/ATS. |
| Line energized state | flow-w_* | state | Energized by A/B/C utility or generator; de-energized is muted. | calcPowerFlow() graph traversal. |
| MV feeders | tele-w_mv_a/b, tele-w_rmu_a/b, tele-w_mv_tie | V / A / kW | 20,000 V; illustrative power assignment. | WIRES voltage + calcPowerFlow(). |
| Ring / transformer feeders | tele-w_ring_ac/bc, tele-w_tx_a/b/c | V / A / kW | 20 kV upstream; current from assigned kW/PF. | WIRES and 3-phase current formula. |
| LVSB / generator feeders | tele-w_lvsb_*, tele-w_gen_* | V / A / kW | 400 V; utility or generator source path. | WIRES, breaker state and source reachability. |
| IT distribution feeders | tele-w_db_a/b/c, tele-w_ups_a/b/c | V / A / kW | 400 V; engine-derived share of 30,000 kW IT. | EPMS_LADDER plus calcPowerFlow(). |
| Mechanical distribution | tele-w_db_m_*, tele-w_ups_m_*_in, tele-w_ats* | V / A / kW | 400 V; illustrative feeder values. | WIRES and destination-name mapping. |
| Chiller/AHU branches | tele-w_ch1…4, tele-w_ahu1/2 | V / A / kW | 400 V; energized state and assigned load. | WIRES. |
| DAHU branches | tele-w_dahu_a_0…4, tele-w_dahu_b_0…4 | V / A / kW | 400 V; derived share of governed non-IT load. | EPMS_LADDER.dahuKw. |
| Rack PDU incoming | w_ups_pdu_m_0…9, w_ups_pdu_c_0…9 | state | No telemetry label; topology/energization only. | WIRES[].noTele=true. |
| Rack ATS feeders | tele-w_pdu_ats_m_0…9, tele-w_pdu_ats_c_0…9 | V / A / kW | Intermediate topology allocation derived from the governed IT load. | EPMS_LADDER and generated WIRES. |
| Final rack group | tele-w_ats_rack_0…9 | aggregate kW / count | 3,000 kW and 200 installed positions per group; no invented physical V/A. | site.it_load_kw / 10 and campus.racks_total / 10. |
| CDP feeder | tele-w_cdp | V / A / kW | 230 V; controls load presentation. | WIRES. |
| Total load | val-total-load | kW | 43,500 while a utility source is available; 0 in the modeled dark-site state. | snapshot.electrical.epms_total_kw. |
| Power factor | val-pf | ratio | UNAVAILABLE. | No governed point; no fallback or random value. |
| Frequency | val-freq | Hz | UNAVAILABLE. | No governed point; no fallback or random value. |
| Breaker roll-up | val-breakers | closed / total | Direct state count. | SIM.breakers. |
| Alarm roll-up | val-alarms | count | Number of breakers in trip. | SIM.breakers filter. |
| System mode | val-system | state | ONLINE if either utility boolean is true; otherwise GEN MODE. | updateStatusBar(). |
| Last update | val-timestamp | local time | Browser time, 1 s cadence. | Date().toLocaleTimeString(). |
CONV_CALC v2.0.0 snapshot. Current load is four halls × 7,500 kW; 40,000 kW is planning/design capacity only.| Interaction | Required behavior | Accessibility / failure behavior |
|---|---|---|
| Source / tie selection | State, LED, ATS sequence, flow and log update together. | Controls require button semantics and an accessible pressed/state label; color alone is insufficient. |
| Breaker selection | Click toggles; Alt opens; Shift trips. | Hidden modifier gestures must be documented in-context before production use; focus/keyboard parity is required. |
| Zoom / pan / fit | Viewport remains bounded and fit excludes the fixed sidebar/topbar. | Buttons expose names; reduced motion disables flow animation without hiding energized state. |
| Export | PDF preview and CSV/JSON downloads reflect current simulator state. | Popup/download failure returns visible feedback; exports state that data is simulated. |
| Alarm presentation | A trip changes symbol, count and fault state. | Text and symbol supplement red; unexpected open and trip must remain distinct. |
| Mobile | Toolbar scrolls internally and the document does not overflow horizontally. | Core status and doc links remain reachable at 360 px; desktop diagram scope is disclosed. |
| Reports / log | New actions appear newest first with timestamps where applicable. | No report or log is described as a persistent historian. |
| ID | Given / when / then | Evidence |
|---|---|---|
| AC-01 | Given complete CONV_CALC v2.0.0 authority, when the page loads, then top-strip values are 43.50 MW, 30.00 MW and 1.45. | DOM assertion against engine output. |
| AC-01A | Given missing, legacy or same-version-incomplete authority, then all governed values and the shared basis drawer remain unavailable and no retired current value appears. | Hostile-fixture browser assertions. |
| AC-02 | Given Utility A on, when it is toggled off, then its button and reachable flow become off and an event is logged. | Puppeteer interaction. |
| AC-03 | Given both utilities unavailable, when ATS delays settle, then system mode is GEN MODE and required generator paths close. | Fake-clock state sequence. |
| AC-04 | Given utility restoration, then generator breaker opens before utility breaker closes for that stream. | Fake-clock state sequence. |
| AC-05 | Given an open MV tie, when Tie is selected, then br_mv_tie closes and the control reads active. | State/DOM assertion. |
| AC-06 | Given any breaker, when Shift-clicked, then its state is trip and alarm count increases by one. | Pointer modifier E2E. |
| AC-07 | Given a tripped breaker, when returned to closed/open, then alarm count decreases and symbol leaves trip state. | DOM/state assertion. |
| AC-08 | Given an energized modeled wire, then its flow class is present and its telemetry label is non-zero. | DOM class/text assertion. |
| AC-09 | Given a de-energized wire, then its label reads 0V 0A 0kW. | DOM assertion. |
| AC-10 | Given each zoom preset and Fit, then the indicator and transform change without losing breaker state. | Interaction plus state snapshot. |
| AC-11 | Given a drag and wheel input, then pan/scale stay finite and scale remains 0.15–2.0. | Transform parse assertion. |
| AC-12 | Given each export action, then a report/download is created with current sources, generators and breakers. | Popup/download capture. |
| AC-13 | Given the default simulator, then breaker roll-up equals the model count and alarm count is zero. | Direct JavaScript/DOM comparison. |
| AC-14 | Given 360 px width, then page scroll width does not exceed viewport width and PRD/Manual links remain reachable. | Responsive render measurement. |
| AC-15 | Given reduced-motion preference, then energized state remains legible without animated dash flow. | Computed-style screenshot. |
| AC-16 | Given PRD and Manual pages, then neither is access-gated and both load shared shell/RZExplain scripts. | Static contract and browser load. |
| AC-17 | Given cockpit link injection, then the diff contains exactly two added anchor lines and no deleted cockpit line. | git diff --unified=0. |
| AC-18 | Given the full interaction journey, then no uncaught console error occurs. | Captured console/page error stream. |
CONV_CALC is unavailable, show an explicit unavailable quality state rather than silently trusting fallback numerals.| Source | Governs | Binding / use |
|---|---|---|
EPMS_Telemetry.html | Visible topology, controls, state machine, telemetry assignment and exports. | Primary implementation source. |
js/conv-engine.js | CONV_CALC v2.0.0: four halls, 30,000 kW current IT, 43,500 kW facility, PUE 1.45 and 2,000 installed rack positions. | Top status strip through a schema-complete snapshot; 40 MW IT remains planning/design capacity. |
| EPMS Technical Manual | Electrical formulas, transfer sequence, point interpretation and worked examples. | Human-readable methodology. |
| IEC 60364 | Low-voltage installation principles and conductor/protection context. | Design reference only; simulator is not a compliance calculation. |
| IEC 60909 | Short-circuit current calculation framework. | Future study boundary; no fault level is currently calculated. |
| IEC 61850 / IEC 60870-5-104 | Substation communication and telemetry concepts. | Future integration context; no live protocol client exists. |
| IEEE C37.2 | Device function numbering for protection/control nomenclature. | Recommended detail for future breaker inspector. |
| NFPA 70E / IEEE 1584 | Electrical safety and arc-flash study context. | Explicit non-goal until project-specific study data exists. |
| Conventional review docs 00, 02, 09 and 12 | Cross-page reconciliation, EPMS gaps, engineering basis and acceptance criteria. | Risk and target-state source. |
| Risk / open question | Current evidence | Required resolution |
|---|---|---|
| Site aggregate is a modeled authority, not a field meter. | Top and bottom both bind to 43.50 MW from CONV_CALC v2.0.0. | Add physical meter identity, timestamp and tolerance before any live-operations claim. |
| Ten terminal symbols are aggregate rack groups. | Ten × 3,000 kW = 30 MW and ten × 200 positions = 2,000 positions. | Keep the aggregate label explicit; do not present a group as one cabinet or feeder. |
| Intermediate wire kW is topology-class allocation. | Values derive from site IT/non-IT totals and drawn branch counts, not a solved network. | Replace with a bus-conserving load-flow/allocation model if detailed feeder design is required. |
| Rack-group V/A is not governed. | Final group labels show only aggregate kW and rack count. | Publish branch phase/voltage/conductor topology before exposing physical current. |
| Source colors conflict with alarm semantics. | Stream A is fault-red and stream C is purple even when normal. | Move source identity to labels/markers; reserve red for trip and avoid purple as primary operational chrome. |
| Point-level freshness is absent. | Top source/gen/trip state is bound, while quality remains snapshot-level. | Expose acquisition timestamp, stale threshold and quality per point. |
| Breaker gestures are undiscoverable and lack confirmation. | Alt/Shift behavior exists only in code; any diagram click changes state. | Add explicit training controls, keyboard semantics and confirmation for destructive/safety-like actions. |
| ATS timing is illustrative. | 1 s restoration and 2 s generator start are browser timers, not equipment curves/interlocks. | Label simulated timing and model sync/check permissives before any operational claim. |
| Generator/capacity duty is not reconciled. | Three 2.5 MW sets cannot establish capacity for the governed 43.50 MW facility load. | Keep adequacy unavailable until fleet quantity, derating, dispatch, N+1 and the 15,503 L/h fuel basis are governed together. |
| Data quality is snapshot-level. | The shared telemetry banner and metadata validate authority, but individual wires have no sample age. | Adopt point-level freshness and bad-quality state before a live integration. |
| Export omits simulation provenance. | Files contain current values but not a formal data-mode field. | Add schema/version/data-mode and units without changing existing behavior until separately approved. |