AWS EU West (Dublin) 2011: Transformer Loss and a Generator PLC Halt
Summary
On Sunday 7 August 2011 a utility transformer feeding much of one AWS EU West zone in Dublin failed. A PLC that brings the backup generators onto the bus halted, the UPS drained and the zone went dark. Staff synchronised generators by hand and restored the network by 13:49 PDT, but EBS recovery took until 10 August.
- Users affected
- Almost all EC2 instances and 58% of EBS volumes in one EU West zone; Single-AZ RDS in that zone; regional EC2 launch errors for over an hour.
- Duration
- 3d 10h — Trigger 10:41 PDT 7 Aug → 98% of recovery snapshots delivered 20:25 PDT 10 Aug (3 d 9 h 44 min)
- Financial
- Not disclosed; AWS gave a 10-day 100% credit to customers in the zone
- Scope
- Single Availability Zone, with regional API impact
- Site
- AWS EU West Availability Zone (facility not named) · Dublin, Ireland, eu-west-1
- Services down
- Amazon EC2, Amazon EBS, Amazon RDS, EC2 APIs (EU West)
How the defences failed
One zone plus regional API impact. Duration (8): about 3 days 10 hours from trigger to 98% of recovery snapshots, inside the 3–7 d band; most instances were back the same day.
All 8 impact metrics
| Failed utility transformer | 110 kV, 10 MW |
| EBS volumes in the zone that lost power | 58% |
| Trigger to first generators online | 1 hour 13 minutes (10:41 → 11:54 PDT) |
| Trigger to EC2 APIs recovered in other zones | 1 hour 19 minutes (12:00 PDT) |
| Trigger to zone connectivity restored | 3 hours 8 minutes (13:49 PDT) |
| RDS DNS connectivity restored | within 4 minutes; most failovers within 10 more |
| Recovery snapshots delivered | 38% by 06:04 9 Aug · 85% by 02:37 10 Aug · 98% by 20:25 10 Aug PDT |
| Service credit | 10 days at 100% of EBS, EC2 and RDS usage in the zone |
Sequence of events
- TRIGGER The utility's 110 kV 10 MW transformer fails, cutting supply to every customer on it, including a significant portion of one EU West Availability Zone in Dublin.Utility / grid operator
- CASCADE One of the PLCs that phase-synchronise the backup generators does not complete connecting a portion of them; AWS believes a large ground fault detected by the PLC stopped it.
- CASCADE UPS batteries drain within minutes; power is lost to almost all EC2 instances and 58% of EBS volumes in the zone.
- IMPACT EC2 networking gear loses power, cutting the zone off from the internet and the other zones; API calls aimed at the zone fail.
- CASCADE A DNS connectivity issue blocks RDS Multi-AZ health checks; DNS returns within 4 minutes and most pairs fail over within 10 more, but a software bug stretches failover for a small subset.
- DETECTION Launch delays and API errors are seen in all EU West zones: management servers keep routing to the dead zone and queued launch requests overload them.
- MITIGATION Some backup generators are brought online by manually phase-synchronising the power sources; many instances get power but stay unreachable because most network gear is still dark.Authorised electrical person
- MITIGATION EC2 launches are disabled in the affected zone and the failed management servers are removed; launch times in the other zones recover.Operations lead
- RECOVERY Enough network devices have power to re-establish connectivity to the zone; many instances and volumes become accessible.
- MITIGATION AWS posts frequent Service Health Dashboard updates and staffs up its Support team for forum and Premium Support contacts.Communications lead
- CASCADE Re-mirroring of EBS volumes exhausts the zone's spare capacity; many volumes stay stuck waiting for a new replica.
- RECOVERY AWS brings in additional labour and trucks servers in from another zone to add EBS capacity; night-time logistics add delay.Service recovery lead
- CASCADE Volumes whose every replica lost power are treated as possibly inconsistent and must be rebuilt as recovery snapshots through S3, a slow process.
- IMPACT Almost all Single-AZ RDS databases in the zone are unavailable; customers without automated backups cannot do a point-in-time restore.
- RECOVERY About 38% of recovery snapshots for possibly inconsistent volumes are delivered.
- RECOVERY 85% of recovery snapshots are delivered.
- RESTORED Recovery snapshots are 98% complete; the remaining few need manual attention.
Response by role
What each role did
Roles the sequence of events shows acting; every entry quotes its source line. Select a time to jump to it.
Role by role
Recorded actions / playbook actions per role. A role with 0 recorded actions does not appear in the sources.
The utility (ESB Networks per DCK), not named in the AWS summary — External owner of the supply: switching at the substation, load shedding, restoration.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
AWS on-site staff — Switching, isolation and lock-out of power sources, and safe re-energisation.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
- FM-01Alarm when generators run but their breakers stay openNFPA 110Contributing factor #2
AWS EC2 operations — Technical lead who diagnoses and drives the fix; the subject-matter expert at the keyboard or the switchboard.
On the record
- Disabled launches in the zone and removed failed management servers
EC2 launches are disabled in the affected zone
Playbook analyst guidance by failure mode, not a record of what happened
- FM-03Fail requests for an unreachable zone at once instead of queuing themSRE incident mgmtCorrection of errors #2
- FM-04Alert when spare capacity falls below what pending re-mirrors needSRE incident mgmtContributing factor #6
- FM-03Alert on per-zone API error rate and queue depthSRE incident mgmtContributing factor #5
- FM-05Alert on any Multi-AZ pair whose failover passes a few minutesSRE incident mgmtContributing factor #8
- FM-02Track which network devices have power while generators come backSRE incident mgmtContributing factor #4
- FM-01Restore network gear first so powered instances can be reachedUptime OSLesson #2
AWS EBS and RDS teams — Restores customer service: failover, workload moves, capacity, backlog drain.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
- FM-04Bring in spare servers from other zones as soon as the shortfall showsISO 22301Correction of errors #9
- FM-03Disable launches in the failed zone and drain its management hostsSRE incident mgmtCorrection of errors #8
- FM-05Decide promotion by hand for pairs the automation cannot settleITIL 4Correction of errors #5
- FM-02Bring instances back once the network path is verifiedSRE incident mgmtLesson #2
AWS Service Health Dashboard and Support — Status page, customer notices, regulators and press; one voice, timed updates.
On the record
- Updated the dashboard often and staffed up Support
AWS posts frequent Service Health Dashboard updates
Playbook analyst guidance by failure mode, not a record of what happened
The PLC supplier, not named — Third party whose product, service or network sits in the failure path.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
- FM-01Analyse the PLC with the supplier before returning it to automatic dutyUptime OSCorrection of errors #1
Failure mode & effects analysis (FMEA)
The zone's utility-to-generator transfer (paralleling PLC, UPS ride-through, network gear power) and the AWS recovery path (EC2 regional API, EBS re-mirroring and recovery snapshots, RDS Multi-AZ failover), from AWS's summary.
- Caught only after impactD ≥ 8
- 0 of 5
- Actions that cut occurrenceO lowered
- 3
- Actions that cut detectionD lowered
- 3
- Actions that cut severityS lowered
- 1
FM-01 The PLC does not complete connecting a portion of the generatorsGenerator paralleling PLC 9·3·7 189 108
- Function
- Synchronise generator phase and close the generators onto the bus after a utility loss
- Effect
- Too little generation; UPS drains; most of the zone loses power
- Cause
- A large ground fault detected by the PLC, as AWS believes; supplier analysis pending
- Prevention in place
- Automatic paralleling with UPS ride-through
- Detection in place
- None before the event
- S 9
- It took almost all instances in a zone offline: 9.
- O 3
- A controller halting at the moment of demand is uncommon: 'remote to infrequent'.
- D 7
- No recorded test failed the controller with live generators.
Corrective action
- Correct PLC isolation and add a cold isolated backup PLC (AWS, committed) Correction of errors #1
After action: S9 · O2 · D6 → RPN 108. A backup PLC removes the single point of failure if it works; AWS has not reported deployment.
Who acts — playbook
- Authorised electrical person Test generator paralleling with the primary controller failed, on a scheduleNFPA 110Correction of errors #1
- Authorised electrical person Alarm when generators run but their breakers stay openNFPA 110Contributing factor #2
- Authorised electrical person Synchronise generators by hand onto the bus using a drilled procedureNFPA 70ECorrection of errors #7
- Vendor / upstream provider Analyse the PLC with the supplier before returning it to automatic dutyUptime OSCorrection of errors #1
- Operations lead Restore network gear first so powered instances can be reachedUptime OSLesson #2
Evidence
- Sequence of events #2“does not complete connecting a portion of them”
- Contributing factor #2A generator-synchronising PLC did not complete connecting part of the generators, believed to be due to a large ground fault (AWS summary).
- Reference #1 · official-postmortem“did not complete the connection of a portion of the generators”
FM-04 Spare capacity runs out during re-mirroring, and volumes that lost every replica need slow recovery snapshots via S3EBS re-mirroring and consistency recovery 8·3·6 144 126
- Function
- Restore every volume quickly and safely after a power loss
- Effect
- Some customers wait until 10 August for their volumes
- Cause
- Recovery capacity and path sized for routine failures, not a zone-wide loss
- Prevention in place
- Replication across nodes plus spare capacity
- Detection in place
- Seen during recovery
- S 8
- Single-zone customers waited up to three days, with no workaround: 8.
- O 3
- Needs a zone-wide power loss: 'remote to infrequent'.
- D 6
- The capacity gap appeared only in the event.
Corrective action
- Recover volumes in place on the EBS servers (AWS, committed) Correction of errors #4
After action: S7 · O3 · D6 → RPN 126. In-place recovery removes the S3 copy and the capacity dependency, which shortens the tail; it is committed but not reported complete.
Who acts — playbook
- Service recovery lead Size re-mirroring spare for a full zone loss, or recover volumes in placeNIST SP 800-34Correction of errors #4
- Operations lead Alert when spare capacity falls below what pending re-mirrors needSRE incident mgmtContributing factor #6
- Service recovery lead Bring in spare servers from other zones as soon as the shortfall showsISO 22301Correction of errors #9
- Communications lead Give each customer the state of each volume and how to use its recovery snapshotITIL 4Correction of errors #6
Evidence
- Sequence of events #11“exhausts the zone's spare capacity”
- Sequence of events #17“98% complete”
- Contributing factor #6Spare EBS capacity was too small for re-mirroring at this scale, and night-time logistics delayed extra servers (AWS summary).
- Contributing factor #7Volumes that lost every replica needed recovery snapshots through S3, a slow process for large volumes (AWS summary).
FM-03 Management servers keep routing to the dead zone and queue launches for it, overloading the regionEC2 regional management API 6·4·4 96 54
- Function
- Serve launches in healthy zones while one zone is down
- Effect
- Launch delays and API errors in every EU West zone until 12:00
- Cause
- No fast removal of failed management hosts; requests queued instead of failed
- Prevention in place
- Management servers in every zone
- Detection in place
- Seen at 11:05 as regional launch delays
- S 6
- It blocked the workaround (launch elsewhere) for over an hour: 6.
- O 4
- Any zone failure tests this path: 'infrequent'.
- D 4
- Errors were visible within 24 minutes; the fix was manual.
Corrective action
- Faster removal of failed API management hosts (AWS, committed) Correction of errors #2
- Per-zone isolation of control-plane components (AWS, in progress) Correction of errors #3
After action: S6 · O3 · D3 → RPN 54. Load balancing and isolation target both the routing and the queue; neither is reported complete.
Who acts — playbook
- Operations lead Fail requests for an unreachable zone at once instead of queuing themSRE incident mgmtCorrection of errors #2
- Operations lead Alert on per-zone API error rate and queue depthSRE incident mgmtContributing factor #5
- Service recovery lead Disable launches in the failed zone and drain its management hostsSRE incident mgmtCorrection of errors #8
- Communications lead Tell customers healthy zones are open for launchesITIL 4Lesson #6
Evidence
- Sequence of events #6“queued launch requests overload them”
- Contributing factor #5EC2 management servers kept routing to the dead zone and queued launches for it, overloading the regional API (AWS summary).
- Metric #4Trigger to EC2 APIs recovered in other zones: 1 hour 19 minutes (12:00 PDT)
FM-05 A DNS issue blocks the health check, and a software bug stretches failover for some pairsRDS Multi-AZ failover 6·3·5 90 48
- Function
- Promote the standby database at once when the primary's zone fails
- Effect
- A small subset of Multi-AZ databases stays unavailable well beyond the usual minutes
- Cause
- Health check depends on DNS; failover bug; cautious split-brain handling needs an engineer
- Prevention in place
- Synchronous standby in another zone
- Detection in place
- Health checks
- S 6
- It failed customers who had paid for the multi-zone design: 6.
- O 3
- Needs the DNS issue plus the bug: 'remote to infrequent'.
- D 5
- Health checks detect the failure, but could not complete here.
Corrective action
- DNS-robust health checks, failover bug fix and automatic retry for split-brain checks (AWS, committed) Correction of errors #5
After action: S6 · O2 · D4 → RPN 48. The bug fix and retry logic target the extended failovers directly; completion not reported.
Who acts — playbook
- Service recovery lead Remove DNS from the failover health-check pathSRE incident mgmtCorrection of errors #5
- Operations lead Alert on any Multi-AZ pair whose failover passes a few minutesSRE incident mgmtContributing factor #8
- Service recovery lead Decide promotion by hand for pairs the automation cannot settleITIL 4Correction of errors #5
- Communications lead Point Single-AZ customers to point-in-time restore from backupsITIL 4Lesson #6
Evidence
- Sequence of events #5“a software bug stretches failover for a small subset”
- Contributing factor #8A DNS connectivity issue and a software bug delayed failover of some RDS Multi-AZ databases (AWS summary).
- Metric #6RDS DNS connectivity restored: within 4 minutes; most failovers within 10 more
FM-02 Network gear loses power with the servers and comes back two hours after the first generatorsZone network gear power 8·3·3 72 —
- Function
- Keep the zone's network reachable through a power event
- Effect
- Instances that regained power stay unreachable until 13:49
- Cause
- Network gear shared the failed power path; restoration order not stated
- Prevention in place
- UPS ride-through only
- Detection in place
- Immediate: the zone went dark
- S 8
- It cut the whole zone off from customers and other zones: 8.
- O 3
- Follows from any full power loss of the zone: 'remote to infrequent'.
- D 3
- Loss of connectivity is visible at once.
Corrective action
- None published — residual risk.
Who acts — playbook
- Authorised electrical person Give network gear its own protected supply and first place in restorationUptime OSImprovement #6
- Operations lead Track which network devices have power while generators come backSRE incident mgmtContributing factor #4
- Authorised electrical person Switch restored generator capacity to network gear before computeUptime OSLesson #2
- Service recovery lead Bring instances back once the network path is verifiedSRE incident mgmtLesson #2
On the record at this failure
Evidence
- Sequence of events #4“EC2 networking gear loses power”
- Sequence of events #7“most network gear is still dark”
- Contributing factor #4The zone's network gear lost power too, so instances that regained power stayed unreachable until 13:49 (AWS summary).
Scoring rubric and method
Scales adapted from IEC 60812:2018 and AIAG-VDA. RPN = S × O × D. High: S ≥ 9 with O ≥ 4 or D ≥ 7, or RPN ≥ 300. Medium: RPN ≥ 120 or S ≥ 7. Severity overrides the product: 9 × 2 × 9 = 162 would otherwise hide a region-wide outage nothing could catch. Quotes are checked verbatim against this dossier; a revised score needs a published action. RZ analyst assessment, not an operator document.
Severity
| 10 | Hazard to people, or loss of the facility / several regions |
| 9 | Region-wide or provider-wide outage of a foundational service, no workaround |
| 8 | Full outage of a major service for hours |
| 7 | Major degradation of a major service |
| 6 | Partial outage confined to one zone or one service |
| 5 | Customer-visible degradation |
| 4 | Limited customer impact |
| 3 | Internal impact only |
| 2 | Negligible |
| 1 | No effect |
Occurrence
| 10 | Near certain: the cause is present in normal operation |
| 8 | Frequent: routine work exercises the cause |
| 6 | Occasional: a foreseeable slip or condition, weakly guarded |
| 4 | Infrequent: needs an unusual combination |
| 2 | Remote: guarded by design |
| 1 | Eliminated by design |
Detection
| 10 | No control could detect it |
| 9 | Detected only through customer impact |
| 8 | Detected after impact by internal monitoring |
| 6 | Detected at onset, not prevented |
| 4 | Detected before impact with time to act |
| 2 | Automated interlock almost certainly stops it |
| 1 | Certain to be stopped |
Root cause and contributing factors
Full root-cause narrative
Contributing factors by category
- The utility's 110 kV 10 MW transformer failed; the utility first cited lightning, then said it was not lightning (AWS summary; DCK).
- A generator-synchronising PLC did not complete connecting part of the generators, believed to be due to a large ground fault (AWS summary).
- UPS batteries gave only a short ride-through and drained before generators could be synchronised by hand (AWS summary).
- The zone's network gear lost power too, so instances that regained power stayed unreachable until 13:49 (AWS summary).
- EC2 management servers kept routing to the dead zone and queued launches for it, overloading the regional API (AWS summary).
- Spare EBS capacity was too small for re-mirroring at this scale, and night-time logistics delayed extra servers (AWS summary).
- Volumes that lost every replica needed recovery snapshots through S3, a slow process for large volumes (AWS summary).
- A DNS connectivity issue and a software bug delayed failover of some RDS Multi-AZ databases (AWS summary).
Analysis
One controller between the generators and the load
The generators started; the PLC that brings them onto the bus did not finish. That turned a routine utility loss into a zone outage. AWS's answer, a cold isolated backup PLC, accepts that the controller is itself a single point of failure.
Power returned before service did
Generators were online at 11:54 but most network gear stayed dark until 13:49, so powered instances could not be reached. Restoration order matters as much as restoration.
A zone failure that leaked into the region
Management servers in healthy zones kept sending and queuing work for the dead zone, so launches slowed across EU West until AWS removed the failed servers at 12:00.
The three-day tail
EBS spare capacity ran out during re-mirroring, and volumes that lost all replicas had to be rebuilt via S3. Recovery snapshots reached 98% only on the evening of 10 August.
A second, unrelated failure
In the same week an EBS snapshot-cleanup bug deleted blocks still referenced by some snapshots. AWS paused that recovery to fight the power event, then finished it on 8 August.
Dating the event
The summary says only 'August 7th' and 'Sunday'. The AWS summaries index lists it under 2014, but 7 August was a Sunday in 2011, not 2014, and Data Center Knowledge reported the outage on 7 August 2011.
Technical deep-dive
Corrective actions and lessons
Correction of errors
| Action | Owner | Status |
|---|---|---|
| Correct the isolation of the primary PLC and deploy a cold, environmentally isolated backup PLC with vendors | AWS | Committed, 'as rapidly as possible' (completion not reported) |
| Better load balancing to take failed API management hosts out of service quickly | AWS | Committed (completion not reported) |
| Further isolate EC2 control-plane components per Availability Zone | AWS | In progress; several more months at the time of the summary |
| Recover EBS volumes directly on the servers after power returns instead of via S3 snapshots | AWS | Committed (completion not reported) |
| RDS: health checks robust to DNS issues, fix the failover bug, and let the healthy member retry instead of waiting for an engineer | AWS | Committed (completion not reported) |
| Communication: staff Support faster, expose per-resource impairment through the APIs, clearer recovery-snapshot instructions | AWS | Committed; impairment tools expected within months |
| Manual phase synchronisation of backup generators | AWS on-site staff | Done during the event, from 11:54 PDT |
| Disable launches in the affected zone and remove the failed management servers | AWS | Done during the event, 12:00 PDT |
| Add EBS capacity with extra labour and servers trucked from another zone | AWS | Done during the event |
| Snapshot cleanup: alarm on unusual findings and a longer recoverable holding state before deletion | AWS | Changes made per the summary |
Lessons learnt
- A generator fleet is only as available as the controller that parallels it. A single PLC must not be able to keep healthy generators off the bus.
- Network gear needs power as surely as servers: restored instances were useless for two hours while the network stayed dark.
- Regional control planes must stop routing to a failed zone at once; queuing work for it spreads the failure to every zone.
- Recovery capacity must be sized for the zone-wide case, not for routine node failures.
- Being conservative about data consistency was right, but the slow recovery path turned a three-hour power event into three days for some customers.
- Customers running independently in several zones saw no interruption.
Improvements
- Power: correct PLC isolation and add a cold, isolated backup PLC (AWS committed).
- Control plane: faster removal of failed API hosts and per-zone isolation (AWS committed / in progress).
- Storage: recover EBS volumes in place after power returns (AWS committed).
- Database: RDS Multi-AZ health checks and edge-case handling (AWS committed).
- Communication: faster Support staffing and per-resource impairment visibility (AWS committed).
- Analyst recommendation (not in the summary): test generator paralleling with the PLC failed, and give network gear its own protected supply priority.
References and provenance
- official-postmortem AWS Post-Event Summary: Summary of the Amazon EC2, Amazon EBS, and Amazon RDS Service Event in the EU West Region“one of the PLCs did not complete the connection of a portion of the generators”https://aws.amazon.com/message/2329B7/
- news Data Center Knowledge: Outage in Dublin Knocks Amazon, Microsoft Data Centers Offline (7 Aug 2011)“lightning was not the cause”https://www.datacenterknowledge.com/hyperscalers/outage-in-dublin-knocks-amazon-microsoft-data-centers-offline
Quotes are short, attributed, and for provenance only; the analysis is original. Last verified 2026-11-11.