Data-Center Incidents — Case Library
Major data-center and cloud incidents, ranked by magnitude. Each dossier: sequence of events, root cause, correction of errors, lessons, improvements and a scored FMEA you can replay and re-score. Every fact traces to a public post-incident report.
About this library · how to read it
What this is
A root-gated, source-cited engineering reference on major data-center and cloud-infrastructure incidents worldwide — each a structured post-incident dossier (sequence of events, root-cause analysis, correction-of-errors, lessons learnt, engineering improvements). It exists for internal engineering education; every material fact is traced to a public post-incident report, and where an authoritative cause was never published the dossier says so rather than invent one.
How incidents are ranked
By a transparent magnitude composite — a weighted sum of four sourced sub-scores (each 0–10): blast radius 0.35 · users 0.25 · financial 0.20 · duration 0.20. Hover any magnitude bar or a dossier's radar for the exact breakdown. Ranking never uses a hidden score.
What “official RCA” means
The official-RCA filter and the count above mark incidents backed by a genuine vendor post-incident review, regulator/government report, or court record — not press reporting. The provenance gate refuses to set that flag unless such a source is actually cited.
Reading the visualizations
- Where these happened — a real map at each incident's origin site; gold = facility failures (power/cooling/fire), green = network/logical. Co-located incidents are fanned onto a small ring; hover a marker for the brief.
- Ranked bars — magnitude, coloured by severity (red = most severe).
- Risk map — blast radius (x) × outage duration (y); top-right is the worst quadrant. Dots sit at their true scores; hover any dot for its values.
- Semantic map — a projection of the research vector-index: incidents near each other share a failure signature.
- Per dossier — a failure chain and a fishbone drawn by the RZ diagram engine, a magnitude radar, a phased SOE timeline, and the response by role: what each role did on the record, and an analyst playbook per failure mode.
Access
Root-only. The library is excluded from the public sitemap and search index.
Incident Intelligence
Global data-center incident landscape · risk map & semantic analysis
- Critical014%
- High022%
- Medium036%
- Low028%
Incidents linked to their nearest failure-signature neighbours (from the research vector index). Hover a node to trace its cluster.
- Capacity / scaling / quota0mag 6.9
- Fire / battery0mag 6.9
- Power / electrical0mag 6.4
- Software / config / deploy0mag 6.9
- Human error / procedure0mag 7.0
- Network / BGP / DNS0mag 6.9
- Cooling / thermal0mag 6.1
FMEA across the library
Where detection sat
Modes per detection score. Open a row for the modes behind it, worst RPN first.
D 9118Detected only through customer impact
- Dyn (Oracle) 2016 · FM-05Devices accept one of 64 well-known default credential pairs over Telnet, so they are enrolled into the Mirai botnet630
- CrowdStrike 2024 · FM-05Channel File 291 is pushed to all online 7.11+ Windows hosts in one window, with no staged or canary rollout and no customer control over timing540
- NIRS Daejeon 2025 · FM-01A battery sparks for an undetermined reason during relocation work and thermal runaway propagates through the bank, causing an explosion and fire540
- AWS S3 2017 · FM-04Restart plus integrity validation takes hours longer than expected at current scale504
- AWS 2020 · FM-04Restart throughput is capped at a few hundred servers per hour, because shard-map rebuild is metadata-heavy and a faster restart would re-trigger the failure504
- NIRS Daejeon 2025 · FM-07The repository has no backup or external copy, so its destruction in the fire is permanent486
- Meta 2021 · FM-01The command unintentionally takes down every connection in the backbone486
- AWS S3 2017 · FM-01Accepts a mistyped input and removes far more servers than intended486
- Rogers 2022 · FM-01The ACL policy filter is removed from the distribution routers' configuration, letting all possible Internet routes into the core486
- NorthC 2026 · FM-06Critical systems are hosted only at Almere with no failover to a second site486
- CrowdStrike 2024 · FM-02Validates against a 21-input contract while the interpreter receives 20, so the problematic instance passes450
- AT&T Mobility 2024 · FM-02Lab testing and post-installation testing in the maintenance window do not reveal the improper configuration or its potential impact450
- AWS 2025 · FM-05No established operational recovery procedure exists, so engineers improvise cautiously441
- AWS 2021 · FM-03Monitoring and deployment systems run on the network that has failed, so operators lose live telemetry, chase the internal-DNS symptom first and remediate slowly441
- Microsoft Azure 2026 · FM-05Storage validation runs for about 14 hours, constrained by platform limitations and manual, sequential coordination441
- Google Cloud 2024 · FM-01A required input parameter left blank is accepted and silently replaced by an undocumented default fixed one-year term that carries automatic deletion432
- OVHcloud 2021 · FM-06Primary data and its only backups sit in the same building432
- AWS 2025 · FM-02The deleted active plan leaves the automation in an inconsistent state that blocks every subsequent plan update, so the record cannot self-heal432
- Rogers 2022 · FM-04The management VPN to core nodes rides the failed network, so responders lose access432
- AWS 2011 · FM-06Recovery runs for days because failed nodes cannot be reused until every replica on them is re-mirrored and new capacity must be physically relocated432
- British Airways 2017 · FM-05Physically damaged hardware forces rebuild and restore rather than a clean failover, so recovery takes days432
- Google 2022 · FM-04No arc-flash incident-energy study, cabinet label or PPE-adequacy finding exists in the public record432
- CrowdStrike 2024 · FM-06Hosts that crashed re-crash on every boot and cannot fetch the reverted file, so recovery needs hands-on work per machine405
- SK C&C 2022 · FM-06Core functions, including Kakao's sole authentication service, are concentrated at the Pangyo site with no working cross-site failover405
- Meta 2021 · FM-02A bug in the audit tool prevents it from stopping the command405
- Delta Air Lines 2016 · FM-01The routine test transfer ignites a fire in the power-control room405
- Google Cloud 2020 · FM-01Parts of the old quota system are left in place and report the service's usage as 0405
- British Airways 2017 · FM-01A manual override of the UPS drops the whole facility's load at once, bypassing the generators and batteries instead of transferring the load to them405
- British Airways 2017 · FM-03Power is turned back on in an unplanned and uncontrolled fashion, producing a surge that physically damages servers and infrastructure405
- Fastly 2021 · FM-02QA and testing pass a bug that only a rare configuration state exercises, and it dwells in production for about 27 days405
- SK C&C 2022 · FM-02The BMS captures no abnormal warning and reports a steady ~20C while the cell burns378
- AT&T Mobility 2024 · FM-06FirstNet customer notification begins more than three hours after the outage started and nearly an hour after FirstNet was restored378
- AWS 2026 · FM-04Recovery depends on deliberately staged re-cooling and physical hardware repair, which software orchestration cannot route around378
- CrowdStrike 2024 · FM-01The Template Type declares 21 input fields but the integration code supplies only 20360
- CrowdStrike 2024 · FM-04Reads a 21st element from a 20-element input array with no bounds check, faulting the kernel360
- Rogers 2022 · FM-06Rogers mobile users cannot reach 9-1-1, with no inter-carrier emergency-roaming fallback360
- Delta Air Lines 2016 · FM-06Recovery needs about 500 manual server reboots, and the 52-year-old Deltamatic returns with only its green-screen interface working360
- NorthC 2026 · FM-01A fire breaks out in the emergency-power technical room from an undetermined source360
- Cloudflare 2025 · FM-06No effective global kill switch for Bot Management; recovery needs manually stopping file generation and injecting a known-good file360
- Equinix LD8 2020 · FM-02Both the A and B feeds derive from the same UPS and output switch, so one fault drops both cords together360
- Optus 2023 · FM-04Emergency 000 calls fail for affected customers, with no effective fallback during the IP-core loss360
- Alibaba Cloud 2023 · FM-03Recovery is slow because the permission service may depend on OSS, which itself needs a permission check (reconstructed deadlock, unconfirmed)360
- Cloudflare 2023 · FM-02Batteries begin failing after about 4 minutes instead of the rated 10360
- Cloudflare 2023 · FM-06Kafka and ClickHouse exist only in PDX-04, with dependents in the high-availability cluster, so one site's power loss breaks the control plane360
- CyrusOne 2025 · FM-05Recovery is manual: chillers restart at limited capacity and IT returns in stages360
- Google Cloud 2026 · FM-01Battery units fail, reportedly through a suspected short circuit consistent with lithium-ion thermal runaway, and start a fire360
- Sony PSN 2025 · FM-03Recovery takes most of a day, with no evidence that any failover or DR path engaged360
- Azure 21Vianet 2024 · FM-01An undetermined infrastructure failure takes regional services down360
- Google 2022 · FM-01An arc flash initiates at or inside the cabinet as three electricians access it360
- Google Cloud 2025 · FM-02A policy change containing unintended blank fields is accepted into the tables324
- AWS S3 2017 · FM-05The dashboard's own admin console depends on the S3 it reports on, so status cannot be updated324
- Delta Air Lines 2016 · FM-04About 300 of 7,000 servers are not linked to an alternate power source, and their backups are unpowered too324
- NorthC 2026 · FM-03Primary and backup power elements share one fire compartment, so a single fire destroys transformers and UPS together324
- Microsoft Azure 2023 · FM-02An SOP edited to fix problems from earlier runs goes live without re-testing or proper pre- and post-checks324
- CyrusOne 2025 · FM-02No method statement, supervision or independent verification gates the changeover at the contractor boundary324
- AWS 2026 · FM-06A major customer's systems, designed to tolerate one-AZ failure, do not survive the loss of use1-az4324
- British Airways 2017 · FM-06Live critical-power switching is performed on a bank-holiday Saturday at the start of a peak travel weekend, with unclear ownership between BA and its facilities manager324
- Google Cloud 2026 · FM-01The start permissive reads live line-side voltage on open feeder B and decides a healthy source exists, so no generator start is commanded324
- Google Cloud 2024 · FM-03An operator-triggered deletion sends no customer notification315
- Rogers 2022 · FM-05Staged rebuild is slow and relapses, with prefixes withdrawn again and the core flapping315
- Cloudflare 2023 · FM-07Failover is slow and recovery runs into a second day315
- Google Cloud 2024 · FM-02Term expiry is treated as a deletion instruction and executed unattended, with no alarm during the year-long dwell and no human confirmation288
- Google Cloud 2024 · FM-04A subscription-level delete removes both copies at once288
- Google Cloud 2024 · FM-07Other Private Clouds provisioned the same way carry a latent deletion term288
- Rogers 2022 · FM-07Interac is taken offline by the Rogers outage288
- Dyn (Oracle) 2016 · FM-04Properties delegate all their NS records to Dyn, so Dyn's degradation takes them fully offline288
- Delta Air Lines 2016 · FM-03One event in the power-control room kills a feed and leaves backups unpowered, so failover fails288
- Delta Air Lines 2016 · FM-07No root-cause analysis naming the failed component, its age or its failure mechanism is ever published288
- Alibaba Cloud 2023 · FM-06No root-cause post-mortem is published, so the triggering change and any safeguards remain unverified288
- AWS 2026 · FM-07No post-event summary is published, so the cause and any safeguards remain unverified288
- Google Cloud 2026 · FM-04A tenant's lithium battery installation shares a floor with Google's peering hardware and other tenants' equipment without enough segregation288
- Google Cloud 2026 · FM-07Ignition mechanism, battery specification, detection and suppression performance remain undisclosed; the RCA is not public and the event is framed as force majeure288
- British Airways 2017 · FM-07The independent investigation is never released and the BA/CBRE claim settles privately, so no adjudicated root cause exists288
- Sony PSN 2025 · FM-07No RCA and no start or restore timestamps are published288
- Azure 21Vianet 2024 · FM-02Restoration takes about 50 hours (claimed, unverified)288
- Azure 21Vianet 2024 · FM-04Notices sit only on China-only endpoints outside the standard global-Azure discovery path288
- Azure 21Vianet 2024 · FM-05No post-incident review for the event survives in public hosting288
- Digital Realty 2023 · FM-07No operator or fire-authority root-cause analysis is published and the cause stays 'undetermined'288
- CrowdStrike 2024 · FM-03All 12 static test cases wildcard the 21st field, so no test exercises a non-wildcard 21st input270
- AWS 2021 · FM-05The tooling cannot fail over to its standby region, so public status is not updated270
- AWS 2021 · FM-06Relies on the internal AWS network, so case creation is impaired with it270
- Microsoft Azure 2020 · FM-06No automated pipeline posts a first notice, so timely notification depends on manual steps270
- AWS 2011 · FM-08Updates are slow and vague about which zones and how much is affected270
- AT&T Mobility 2024 · FM-05No 911 call from an AT&T Mobility-served device can be routed to its PSAP while voice is disconnected, and priority calls also fail270
- Cloudflare 2023 · FM-05Flexential does not notify Cloudflare of the generator failover, and Cloudflare's monitoring cannot see the power source270
- Microsoft Azure 2018 · FM-07Fails to scale under incident traffic and returns intermittent HTTP 500 errors270
- Sony PSN 2025 · FM-06Near-silence during the outage: about two posts, no cause, no ETA270
- Digital Realty 2023 · FM-02No early (aspirating or smoke) detection or first-alarm time is on record; the first recorded response is a heat-activated sprinkler270
- Cloudflare 2023 · FM-04Breakers are found faulty on re-energisation252
- Fastly 2021 · FM-05Sites that depend on Fastly alone go dark with it252
- Digital Realty 2025 · FM-05Loss of one UPS room drops platform-serving load, and the outage reaches X users globally252
- Digital Realty 2023 · FM-01Equipment in a specific rack ignites at 01:40 on 21 May 2023252
- Digital Realty 2023 · FM-05Colo 4 stays de-energised for several days252
- AWS 2025 · FM-03EC2's DropletWorkflow Manager and other services hard-depend on the DynamoDB regional endpoint, so its loss propagates region-wide243
- AWS S3 2017 · FM-06Hard dependency on S3 in the same region, so they degrade with it243
- AWS 2021 · FM-04Dependent services share fate with the internal network and fail with it243
- Delta Air Lines 2016 · FM-05Surviving servers cannot communicate with the failed ones and the whole system goes down243
- Microsoft Azure 2023 · FM-03Device-level isolation gives no containment, because the accessible router is still IGP-joined to the whole backbone243
- Alibaba Cloud 2023 · FM-05Every request needs live AK/SK/IAM signature verification against central Auth, so the services fail with it243
- CyrusOne 2025 · FM-06Globally critical matching engines depend on the single Aurora campus, so one plant's thermal failure halts worldwide trading243
- British Airways 2017 · FM-04The peer site also collapses instead of taking over243
- NorthC 2026 · FM-07Ignition source, chemistry, detection timeline and suppression status remain undisclosed, with only a draft cause report due ~4.5 months after the fire216
- Cloudflare 2025 · FM-08Hard dependency on the failing core proxy, so the products fail with it216
- Equinix LD8 2020 · FM-06First public statement comes about seven and a half hours after onset, and no formal RCA is published216
- Equinix LD8 2020 · FM-07Members connected only at the LD8 PoP lose peering when LD8's power domain fails216
- Microsoft Azure 2018 · FM-05Primary metadata site in South Central US with no automatic failover, so management operations fail outside the region216
- Cloudflare 2022 · FM-04One prefix withdrawal removes inbound reachability, outbound reachability to origins and east-west forwarding together216
- Sony PSN 2025 · FM-05Features that need online verification, including registration for physical media, stop working with PSN216
- Google & Oracle 2022 · FM-07Neither operator releases equipment make, model, age, refrigerant, plant type or maintenance/test history216
- Azure 21Vianet 2024 · FM-03No in-country failover, so the customer absorbs the full regional outage216
- Digital Realty 2024 · FM-06Only an early finding is public; the fault mechanism and battery details remain undisclosed216
- Google 2022 · FM-06No equipment identity, incident energy, PPE finding or de-energisation status is published, and the OSHA accident abstract cannot be retrieved216
- Digital Realty 2023 · FM-06The operator gives no substantive statement or recovery ETA through a multi-day outage216
- Google Cloud 2025 · FM-07Workers KV, backed by a third-party cloud provider, loses availability with the Google Cloud failure189
- Google Cloud 2020 · FM-04Dependent services fail their data-plane requests along with authentication189
- AWS 2011 · FM-07A previously un-encountered bug stops automatic failover for some multi-AZ instances189
- Cloudflare 2025 · FM-05Fails silently: the oversized file does not crash the proxy but every request receives a bot score of zero180
- Dyn (Oracle) 2016 · FM-06Dyn's analysis is offline after the Oracle acquisition, so figures and corrective actions survive only through secondary reproduction162
D 8100Detected after impact by internal monitoring
- AWS 2020 · FM-01Per-server thread demand crosses the OS-configured maximum on every server at once after a small capacity addition, and shard-map construction fails504
- AT&T Mobility 2024 · FM-04All devices try to re-register simultaneously and the registration attempts far exceed what network management systems can handle504
- AT&T Mobility 2024 · FM-01A new network element whose configuration did not conform to procedure is loaded into production without the required peer review480
- SK C&C 2022 · FM-04The UPS feeding the fire zone also feeds the whole center, cabling runs over the batteries and some UPS units are not partitioned from the battery room, so selective isolation is impossible432
- NIRS Daejeon 2025 · FM-02Batteries are moved while an auxiliary power system to the UPS battery backup remains energised and the cells sit at about 80-90% charge, without the required insulation materials432
- OVHcloud 2021 · FM-04The building stays live for well over an hour after the cut order432
- Azure Front Door 2025 · FM-01A valid sequence of changes processed across two coexisting build versions emits incompatible metadata432
- Cloudflare 2025 · FM-01A permissions change that made implicit table access explicit is deployed without analysis of its effect on the Bot Management metadata query432
- Microsoft Azure 2023 · FM-01The command's default action on this platform is global, so every IGP-joined router in the backbone recomputes its topology and cannot forward packets correctly meanwhile432
- AWS 2011 · FM-01Traffic is shifted onto the lower-capacity redundant EBS network instead, which saturates while the primary path is withdrawn432
- CyrusOne 2025 · FM-01Onsite staff and contractors do not follow standard procedures when draining the cooling towers ahead of a hard freeze432
- Google 2022 · FM-02Work proceeds with workers inside the arc-flash boundary of an energized cabinet; isolation and lockout status are not disclosed432
- AWS 2020 · FM-02No alarm exists on thread consumption, so the first signal is downstream error rates and the cause takes hours to identify392
- NIRS Daejeon 2025 · FM-03The relocation is illegally subcontracted to crews with no battery-relocation experience, and battery manufacturers are excluded to cut costs384
- OVHcloud 2021 · FM-05Water supply is far below what a building-scale fire needs384
- AWS 2025 · FM-04Attempts to re-establish every lease at once, times out and retries, and enters congestive collapse384
- Azure Front Door 2025 · FM-06Recovery takes about 4.5 hours and dominates the impact window384
- NorthC 2026 · FM-02No source shows an automatic suppression system discharging or holding the fire; detection technology and first-alarm time are undisclosed384
- Optus 2023 · FM-03Tripped sessions do not re-establish on their own, and restoration proceeds by manual reconnection and reboot384
- Google Cloud 2026 · FM-03No fixed suppression discharge is evidenced; the fire is fought manually by the fire service for several hours384
- Cloudflare 2022 · FM-01A reorder moves the site-local advertisement terms below the REJECT-THE-REST catch-all, so first-match evaluation rejects and withdraws the site-local prefixes384
- Google 2022 · FM-03The job briefing / existing-conditions determination required by 29 CFR 1926.950(b)(1)(i) is found deficient384
- AWS S3 2017 · FM-02Servers scoped to billing also carry the index and placement subsystems, so a billing-scoped action starves the request path360
- Cloudflare 2025 · FM-03The generated file is trusted and pushed network-wide every few minutes with no size or row sanity check360
- Optus 2023 · FM-01A software upgrade at a North American Singtel exchange makes one router disconnect, and the resulting flood of ~940,000 BGP announcements in an hour reaches Optus unfiltered360
- Optus 2023 · FM-02The same Cisco default threshold trips on ~90 PE routers near-simultaneously and each tears down its BGP sessions, so the protective action isolates the whole IP core360
- Alibaba Cloud 2023 · FM-02A change to the shared control plane takes effect everywhere at once, with no staged rollout or blast-radius cap recorded360
- Sony PSN 2025 · FM-01An undisclosed backend fault, described by Sony only as 'an operational issue', takes PSN services down globally360
- SK C&C 2022 · FM-05No detailed large-scale emergency plan or whole-center power-loss drills exist, and staff cannot identify in time which switches would isolate only the fire zone336
- NIRS Daejeon 2025 · FM-04No battery off-gas or thermal-runaway early warning is disclosed; the event is noticed by people336
- Microsoft Azure 2023 · FM-04On-call is alerted within minutes but the executing engineer is not informed, and the same command is run on a second Madrid router336
- Microsoft Azure 2023 · FM-05Investigation starts on DNS, tries Azure Front Door and an unrelated IPv6 revert, and per-farm alert noise hides the single service-wide event336
- Optus 2023 · FM-05An upstream upgrade proceeds with no recorded joint staged rollout, blast-radius review or coordinated rollback, and ownership of the change is disputed afterwards336
- Cloudflare 2023 · FM-03Restart is delayed because the access-control system is off battery backup and, per unconfirmed employee accounts, the overnight shift lacks an experienced electrical operator336
- Google Cloud 2026 · FM-02No automated detection or sensed-alarm time is documented; the only detection event is a human emergency call336
- Cloudflare 2022 · FM-05No commit-confirm auto-revert exists, so recovery is fully manual336
- Google & Oracle 2022 · FM-05Engineers inadvertently reroute internal-service traffic away from all three europe-west2 zones instead of europe-west2-a alone336
- Digital Realty 2024 · FM-04Fire-safety protocol keeps O&M engineers out of the building, so damage assessment, controlled shutdown and drying of wet hardware are delayed336
- Meta 2021 · FM-05Remote access is impossible and on-site access is slowed by secure-access protocols and hardware designed to be hard to modify320
- Microsoft Azure 2020 · FM-03Rollback fails because the deployment metadata it depends on has been corrupted320
- Equinix LD8 2020 · FM-01The output static switch fails in service, emits smoke and forces the UPS offline320
- Equinix LD8 2020 · FM-04No fast alternate-energisation path: load has to be migrated onto newly commissioned infrastructure320
- CyrusOne 2025 · FM-03One procedural lapse trips multiple cooling units together and no backup cooling path carries the load320
- Cloudflare 2022 · FM-02The stagger includes no MCP data center until the final step, so the change reaches all MCP spines at once320
- Digital Realty 2024 · FM-01An electrical fault in one battery room initiates lithium-ion thermal runaway320
- AWS 2025 · FM-01A delayed Enactor overwrites the current plan with a much older one, and a second Enactor's clean-up then deletes that plan, leaving an empty DNS record288
- Rogers 2022 · FM-02Core routers accept the route flood and crash within minutes288
- Rogers 2022 · FM-03Wireless and wireline share one IP core, so a single core failure takes down every service together288
- Azure Front Door 2025 · FM-03Judges health before the asynchronous crash registers and lets the corrupt configuration advance288
- AWS 2021 · FM-01A latent defect stops clients backing off, so rising latency produces more retries and a self-reinforcing retry storm288
- Cloudflare 2025 · FM-02The query on system.columns has no database-name filter, so it returns one row per visible database and duplicates every feature288
- Microsoft Azure 2020 · FM-01A latent defect in SDP sends a validation-ring update straight into global production, bypassing validation288
- AWS 2011 · FM-04A flood of Create Volume and re-mirror negotiation calls from one zone starves the shared control plane's threads288
- Cloudflare 2023 · FM-01The protective trip that clears the ground fault also shuts down all ten generators288
- Sony PSN 2025 · FM-02Acts as one shared failure domain, so its fault fails every PSN category at the same time (inferred, not confirmed by Sony)288
- Microsoft Azure 2026 · FM-06Weak tooling makes it hard to identify devices in protective states and prioritise foundational infrastructure288
- Microsoft Azure 2026 · FM-07Log Analytics cannot self-recover from transient initialisation failures and depends on a single cluster288
- Digital Realty 2025 · FM-04The cabinet is still energised when the fire service arrives, and full suppression waits on isolation288
- SK C&C 2022 · FM-07The fire-damaged electrical room cannot be re-energised immediately and ~32,000 servers must be restarted and re-synced at one site280
- Dyn (Oracle) 2016 · FM-03Re-steering assumes a region-biased attack and fails when the second wave arrives from every region at once256
- Microsoft Azure 2023 · FM-06Full prefix reconvergence takes about 1 h 40 min and two routers fail to recover automatically, leaving residual packet loss256
- Microsoft Azure 2018 · FM-04Failover is rejected because it would lose data, forcing a slow recover-in-place256
- Cloudflare 2022 · FM-03The change pipeline has no MCP-specific test, so an edit that is inert elsewhere is not checked on the tier where it is destructive256
- Cloudflare 2025 · FM-07Recover-then-fail flapping and a coincidental status-page failure lead responders to a hyper-scale DDoS hypothesis240
- NIRS Daejeon 2025 · FM-08Restoration runs for weeks: ~32.5% of systems back mid-recovery and 70.5% of services by 24 October224
- Google Cloud 2024 · FM-06Rebuild from backups takes nine days224
- Meta 2021 · FM-04The tools depend on the production DNS that failed, so they break with it224
- AWS 2025 · FM-06Health checks flap on new instances whose network state has not propagated, and automatic AZ failover repeatedly removes healthy capacity224
- Delta Air Lines 2016 · FM-02The fire destroys a transformer before it is controlled; no detection or fixed suppression system is documented224
- AAE-1/EIG/Seacom 2024 · FM-01A disabled, abandoned vessel drifts with its anchor down across the corridor and, under the leading hypothesis, the dragging anchor shears the cables224
- Fastly 2021 · FM-04No automatic suppression: the cause has to be found and disabled by hand224
- Google Cloud 2026 · FM-02Row 3's transfer trips an overload protection breaker and the row loses both feeds224
- Meta 2021 · FM-03With the whole backbone gone, every DNS location declares itself unhealthy and withdraws at once, removing authoritative DNS from the internet216
- Azure Front Door 2025 · FM-02A latent bug crashes data-plane instances during asynchronous processing of the incompatible metadata216
- Azure Front Door 2025 · FM-04Propagates the corrupt configuration to the whole fleet with no cell boundary216
- Azure Front Door 2025 · FM-05Configuration processing runs on the same instances that serve live traffic, so a configuration crash takes serving down216
- AWS 2021 · FM-02Overwhelmed by a surge of connection activity and held in persistent congestion216
- Microsoft Azure 2020 · FM-02The update crashes the Azure AD backend service on startup216
- AWS 2011 · FM-02Sized only for inter-node control and backup traffic, so it cannot sustain primary load and fails when traffic lands on it216
- Sony PSN 2025 · FM-04Load from a concurrent event exceeds backend capacity (unconfirmed hypothesis)216
- AWS 2016 · FM-01During a long voltage sag the breakers do not open fast enough and the flywheel energy drains into the grid216
- Equinix LD8 2020 · FM-05Access control goes dark with the outage200
- OVHcloud 2021 · FM-07A second fire breaks out in a battery room of SBG1192
- AWS 2025 · FM-07A large propagation backlog after DWFM recovery leaves new instances without connectivity192
- AWS 2020 · FM-05Buffers toward Kinesis back up with no back-pressure ceiling, so dependents block or exhaust host memory and fail in turn192
- Microsoft Azure 2020 · FM-04Manual recovery takes hours to reach normal operation192
- AAE-1/EIG/Seacom 2024 · FM-06No instrumented fault forensics are published: no fault coordinates, depths, anchor marks or anchor-track match192
- Cloudflare 2022 · FM-06Direct access depends on the site-local prefixes the fault withdrew, so engineers are locked out of the sites they need to fix192
- AWS 2019 · FM-02The PLCs hang, and their air handlers shut down instead of going to maximum cooling192
- AWS 2019 · FM-03Purge cannot be activated because it still runs through the hung PLCs192
- NoVA Data Centers 2022 · FM-07Failed components and fault details stay undisclosed; the 2026 review is incomplete192
- Azure Front Door 2025 · FM-07The Portal depends on AFD and goes down with it until manually failed away168
- Microsoft Azure 2018 · FM-06Authentication degrades while traffic reroutes; scale-ahead depends on the impaired ASM API and throttling causes failures and timeouts168
- Google Cloud 2025 · FM-06The status infrastructure shares fate with the failing system and is down in the outage160
- Microsoft Azure 2023 · FM-07A BitLocker / Shared Cache race condition after restarts leaves CAFE components degraded while still taking traffic160
- Google & Oracle 2022 · FM-02Multiple redundant cooling systems fail simultaneously, so the redundancy does not deliver (attributed to Google's fuller report via The Register)160
- Google & Oracle 2022 · FM-04The abrupt power-down leaves replicated Persistent Disks in single-redundant mode and HDD-backed volumes with IO errors160
- AWS 2011 · FM-05A latent, low-probability race condition makes nodes fail when closing many replication requests at once144
- AWS 2026 · FM-05Traffic is shifted away from use1-az4 and the impairment stays inside the zone, but services depending on the hall's EC2 and EBS are impaired144
- Digital Realty 2025 · FM-07The investigation fixes the origin but cannot determine the ignition source144
D 711Between 6 and 8
- OVHcloud 2021 · FM-01Near-simultaneous electrical faults on inverter ASI2 and on the lead-acid batteries, in two separate rooms, ignite a fire350
- Google Cloud 2026 · FM-02The site runs on feed A alone for six days with no proof that generator auto-start works in that line-up280
- Google Cloud 2026 · FM-04The redundant source is out of service for known construction work when the primary plant stops280
- Azure 2023 · FM-01A timing defect stops 13 chillers restarting after the voltage sag224
- Google Cloud 2026 · FM-01The DRUPS fails to take over the side A load because of electrical component failures224
- Digital Realty 2025 · FM-01An internal fault, electrical or mechanical, ignites the cabinet on 22 May 2025196
- AWS 2011 · FM-01The PLC does not complete connecting a portion of the generators189
- AWS 2016 · FM-02Both line-ups fail together because they share the same DRUPS design and weakness189
- Azure 2023 · FM-02The procedure lacks the cold-reset step, so manual restarts fail168
- AWS 2016 · FM-03A latent bug stops automatic recovery of part of the fleet168
- AWS 2019 · FM-01The failover triggers a third-party bug and the control system becomes unresponsive147
D 667Detected at onset, not prevented
- SK C&C 2022 · FM-01An aged cell develops an internal short and enters thermal runaway, igniting a fire on the UPS battery rack360
- Microsoft Azure 2018 · FM-01A lightning-scale voltage swell and sag shuts down and locks out the chillers despite surge suppressors324
- OVHcloud 2021 · FM-02No automatic suppression exists, so a detected fire cannot be fought until the building is de-energised and the fire service commits water300
- SK C&C 2022 · FM-03The gas system discharges correctly within about a minute but cannot extinguish a Li-ion thermal-runaway fire, and the room has no water suppression288
- NIRS Daejeon 2025 · FM-05Gas/CO2 cannot arrest the self-oxidising runaway and water is held back to protect the servers, so the fire re-ignites and burns for hours288
- Microsoft Azure 2026 · FM-01Under voltage sag/swell the utility stays present but unstable, and transfer is inconsistent: some datacenters move to generator, others do not288
- Microsoft Azure 2026 · FM-02Protection latches into full lockout, with no staged or degraded operation and no automatic return once voltage is normal288
- OVHcloud 2021 · FM-03The free-cooling envelope lets fire and smoke climb vertically at high speed, and passive barriers are degraded270
- Google Cloud 2025 · FM-01The new path dereferences blank policy fields, the null pointer crashes the binary, and Service Control enters a global crash loop270
- AWS 2011 · FM-03Every reconnected node searches for free space at once with no back-pressure or jitter, exhausting cluster capacity and looping on retries270
- Microsoft Azure 2018 · FM-02Does not take over: automatic failover was in manual mode and the cooling alerts were not actioned in time270
- AAE-1/EIG/Seacom 2024 · FM-04Repair permits are refused, stalling the repair for months252
- AT&T Mobility 2024 · FM-03Downstream elements lack controls specific to the error, so the only available containment is an automated shutdown of all network connections240
- NIRS Daejeon 2025 · FM-06The fire knocks out the room's HVAC/CRAC and NIRS powers down all 647 systems to prevent overheating216
- Dyn (Oracle) 2016 · FM-01The port-53 flood from a Mirai botnet overwhelms the authoritative DNS infrastructure, so customer names stop resolving216
- Google Cloud 2020 · FM-02When the grace period expires, the automation acts on the zero-usage signal and cuts the account database's quota globally at once216
- Cloudflare 2025 · FM-04Exceeding the hardcoded 200-feature limit returns an error that an unguarded unwrap() turns into a worker-thread panic216
- Alibaba Cloud 2023 · FM-01Runs as one globally-shared failure domain, so its failure stops Auth-gated services in every region at the same instant216
- AAE-1/EIG/Seacom 2024 · FM-05Dispatch is held back by active missile and drone threat, war-risk insurance and naval-security constraints216
- Fastly 2021 · FM-01A latent bug, triggered by a valid customer configuration under specific circumstances, makes about 85% of the network return errors216
- Microsoft Azure 2026 · FM-04Recovery depends on manual diagnosis and restoration under a process the PIR treats as needing better documentation216
- Digital Realty 2024 · FM-03Firefighting and sprinkler water drains from the third-floor battery rooms into the server halls, forcing an emergency power shutdown of the building216
- Dyn (Oracle) 2016 · FM-02Pseudo-random-subdomain attack queries cannot be told apart from legitimate retries, so retries amplify the load and filtering by source risks dropping real lookups210
- AAE-1/EIG/Seacom 2024 · FM-02Three systems sharing one narrow corridor are severed together by a single event210
- NoVA Data Centers 2022 · FM-03Individually reasonable settings trip dozens of facilities simultaneously onto backup power210
- Digital Realty 2024 · FM-02Water suppression cools but cannot stop cell-to-cell thermal-runaway propagation, so the fire persists and the operation runs over two days192
- Cloudflare 2022 · FM-07Engineers overwrite each other's changes and revert previous reverts180
- Digital Realty 2025 · FM-02The cabinet's own plastic internals catch and sustain the fire180
- Digital Realty 2025 · FM-03No fixed suppression is evidenced to discharge; the fire is held by hand180
- Google Cloud 2025 · FM-05Recovering tasks without randomized exponential backoff stampede the underlying infrastructure (herd effect)168
- NorthC 2026 · FM-05Restoration needs a temporary power train built from scratch and weeks of transformer and UPS reinstallation168
- Equinix LD8 2020 · FM-03The fire alarm from a smoking switch leads to a procedural power-down of all systems on levels 1-4 and evacuation of the IBX168
- Alibaba Cloud 2023 · FM-04Authenticates every operator action through the same failed Auth layer, so management is lost along with the gated services168
- AWS 2026 · FM-01Multiple cooling units fail near-simultaneously, and hall cooling capacity drops sharply168
- Azure 2023 · FM-04Fault-code resets, slow tooling, wrong health marking and one failed SQL ring stretch recovery to days168
- Digital Realty 2024 · FM-05The availability zone depends on one building, so one battery-room fire takes it offline and the outage reaches downstream services168
- Google Cloud 2025 · FM-03Metadata replicates globally within seconds with no canary or staged propagation162
- Google Cloud 2025 · FM-04Service Control fails closed: the whole binary crash-loops and dependent APIs return 503s162
- AWS S3 2017 · FM-03Runs as one regional failure domain, so losing it stalls every read and write at once162
- Google Cloud 2020 · FM-03With the Paxos leader unable to write, most reads become outdated and authentication lookups fail162
- AWS 2020 · FM-03The front-end fleet is not cellularized, so the thread-limit breach reaches every server at the same moment162
- British Airways 2017 · FM-02The backup sources are stranded rather than picking up the load162
- Fastly 2021 · FM-03A single valid configuration change reaches the fleet almost simultaneously, with no canary, staged rollout or circuit-breaker162
- NoVA Data Centers 2022 · FM-05Frequency excursion from an instantaneous multi-GW load swing150
- Google Cloud 2020 · FM-05Recovery depends on engineers finding the cause and disabling quota enforcement by hand, one datacenter and then all144
- NorthC 2026 · FM-04The compartment becomes too unstable and damaged to enter, so crews must demolish facade sections with cranes and use a drone for interior imaging144
- Microsoft Azure 2020 · FM-05Covers only some workloads, so failover masks only part of the outage144
- Microsoft Azure 2018 · FM-03Temperatures rise faster than shutdown in some zones, so hardware is damaged before it powers off144
- Google Cloud 2026 · FM-05The emergency power shutdown of networking equipment isolates one POP, and its loss reduces capacity enough to degrade ingress across three metros144
- Azure 2023 · FM-01The control cards stop responding after the dip and block restart144
- AWS 2011 · FM-04Spare capacity runs out during re-mirroring, and volumes that lost every replica need slow recovery snapshots via S3144
- Microsoft Azure 2026 · FM-03With cooling locked out, hall temperatures exceed safe thresholds within about 10–16 minutes and infrastructure shuts down across two availability zones144
- Google & Oracle 2022 · FM-01Cooling capacity collapses on a 40.3C day and the building cannot maintain a safe operating temperature144
- Google & Oracle 2022 · FM-03The protective power-down terminates VMs abruptly rather than draining or migrating them144
- Google & Oracle 2022 · FM-06A subset of cooling infrastructure fails under unseasonal temperatures144
- Digital Realty 2023 · FM-03The sprinkler contains the fire but discharges water onto energised servers in row 4 and adjacent rows144
- NoVA Data Centers 2022 · FM-02A line component fails and causes a fast voltage transient across the pocket144
- AWS 2026 · FM-02Remaining cooling capacity cannot carry the hall's load, so thresholds are breached126
- Azure 2023 · FM-04Metadata store not zone-resilient; traffic shifted to East Asia overloads it126
- Azure 2023 · FM-05Site Recovery depends on a non-zonal Service Bus; Backup and storage failover hit configuration and check faults126
- CyrusOne 2025 · FM-04No automated link from thermal alarms to IT load-shed is recorded; protection depends on the tenant halting its own systems120
- Google Cloud 2026 · FM-06Full restoration waits on fire and structural safety clearance before Google can re-access and re-energise its equipment120
- Digital Realty 2023 · FM-04Power is cut to both Colo 3 and Colo 4, including Colo 3 which a tenant reported 'appears to be safe'120
- AWS 2026 · FM-03Shutdown works as designed but de-energises the affected racks, and some hardware is physically damaged by the power loss108
- Meta 2021 · FM-07Resolvers issue and cache SERVFAIL while clients worldwide retry relentlessly96
- Google 2022 · FM-05No electrical, thermal or smoke detection activates; notification depends on a human report of a large explosion96
- NoVA Data Centers 2022 · FM-04Transfer to backup power fails, so IT load drops84
D 54Between 4 and 6
- Azure 2023 · FM-02Restarts follow an adjacent sequence, so the last chillers are reached after their loop is too hot160
- Azure 2023 · FM-05ARM storage, the AKS queue database and a SQL gateway are not zone-redundant140
- AWS 2011 · FM-05A DNS issue blocks the health check, and a software bug stretches failover for some pairs90
- AWS 2016 · FM-04Hard drives fail on several storage servers; volumes with both replicas on failed servers cannot be restored automatically70
D 412Detected before impact with time to act
- Google Cloud 2026 · FM-03The chiller controller drops offline on the transient; pumps stop and do not restart, and chiller A shuts down144
- Google Cloud 2026 · FM-03About five minutes of battery autonomy runs out before the team can complete a manual transfer128
- NoVA Data Centers 2022 · FM-01Transmission build-out falls behind concentrated data-center load growth, creating a 'pinch point'128
- Azure 2023 · FM-03The loop passes 28°C and the chillers lock out108
- Azure 2023 · FM-03Equipment shuts down piecemeal from 10:30; full controlled shutdown waits until 11:3496
- AWS 2011 · FM-03Management servers keep routing to the dead zone and queue launches for it, overloading the region96
- AWS 2016 · FM-05Launch and scaling calls fail until the APIs are failed away from the degraded zone by hand96
- AAE-1/EIG/Seacom 2024 · FM-03Surviving cables and terrestrial paths lack the headroom to carry the diverted load84
- Meta 2021 · FM-06A sudden reversal of the power dips could put electrical systems and caches at risk, so restoration has to be staged80
- NoVA Data Centers 2022 · FM-06Demand-side heat stress brings the utility close to moving every Ashburn data center to backup generation80
- AWS 2019 · FM-04Launches using the idempotency token fail across the Region72
- Google Cloud 2024 · FM-05Backups share fate with the deleted object, leaving no copy to rebuild from64
D 34Between 2 and 4
- Google Cloud 2026 · FM-05Failover is limited by capacity in surviving zones and slow storage recovery; regional services see queueing and 500/503 errors105
- Google Cloud 2026 · FM-05Shutdown is manual and recovery needs an onsite technician for console servers105
- AWS 2011 · FM-02Network gear loses power with the servers and comes back two hours after the first generators72
- Digital Realty 2025 · FM-06People exposed to a burning, energised cabinet60
D 22Automated interlock almost certainly stops it
What the published actions moved
- Modes with a published actionrevised score allowed
- 113 of 318
- Action lowers occurrenceO
- 68
- Action lowers detectionD
- 47
- Action lowers severityS — blast radius
- 29
By incident category
| Category | Incidents | Modes | Median RPN | After impact | No action | RPN cut |
|---|---|---|---|---|---|---|
| Power | 12 | 73 | 243 | 59% | 64% | 15% |
| Network | 11 | 72 | 288 | 85% | 72% | 15% |
| Software | 10 | 62 | 248 | 77% | 39% | 34% |
| Fire | 8 | 57 | 288 | 63% | 96% | 2% |
| Cooling | 7 | 41 | 168 | 46% | 56% | 18% |
| Human | 2 | 13 | 288 | 85% | 31% | 51% |
Most risk still standing
Total RPN after every published action. Thin bar: as found.
- NIRS Daejeon Government Data Center: UPS Lithium-Ion Battery Fire During Relocation Work2906 of 2906 · 8/8 residual
- Rogers Communications Canada Nationwide Network Outage (July 2022)2425 of 2457 · 6/7 residual
- SK C&C Pangyo Data Center Fire and the National Kakao/Naver Outage2344 of 2479 · 6/7 residual
- British Airways Boadicea House Power Surge: A 15-Minute Fault That Grounded Heathrow and Gatwick for Days2259 of 2259 · 7/7 residual
- OVHcloud SBG2 Strasbourg Data-Center Fire (10 March 2021)2180 of 2400 · 7/8 residual
- Delta Air Lines Atlanta Data Center Power Failure Grounds the Global Fleet2132 of 2132 · 7/7 residual
- NorthC Almere Data Center Fire: A Compartment Blaze That Took Out the Facility Power Plant and Rippled Across Dutch Public Services2082 of 2082 · 7/7 residual
- PlayStation Network ~24-Hour Global Outage (February 2025)1998 of 1998 · 7/7 residual
- AT&T Nationwide Wireless Outage — Network Misconfiguration (February 22, 2024)1986 of 2322 · 4/6 residual
- Google Cloud India Disruption After STT GDC Delhi Data-Center Fire1920 of 1920 · 7/7 residual
Response by role across the library
Recorded = what the sources show a role doing. A role is "silent" when the dossier declares it but no source line shows it acting — a gap in the record, sometimes in the response.
Who is first on the record at detection
No detection by a person or team on the record10
SK C&C 2022, AWS 2021, Microsoft Azure 2018, Google Cloud 2026, Azure 2023, Microsoft Azure 2026, Azure 21Vianet 2024, Digital Realty 2024, AWS 2019, Digital Realty 2023
First responder6
OVHcloud 2021, Azure Front Door 2025, Dyn (Oracle) 2016, Cloudflare 2025, AWS 2020, Alibaba Cloud 2023
Utility / grid operator6
Cloudflare 2023, AWS 2011, Google Cloud 2026, Google Cloud 2026, AWS 2016, NoVA Data Centers 2022
Operations lead2
Authorised electrical person2
Safety officer2
Customer2
Communications lead2
Mechanical / cooling engineer1
Fire & rescue commander1
Practice the playbook cites
- SRE incident mgmt415
- ITIL 4213
- Change management164
- ISO 22301103
- Uptime OS98
- NIMS / ICS79
- ASHRAE TC 9.967
- NFPA 70E54
- NIST SP 800-3453
- NFPA 11040
- NFPA 85539
- NFPA 156134
- NIST SP 800-6120
- NFPA 7216
- NFPA 7513
- EN 50110-19
- ISO/IEC 270358
- NFPA 763
All incidents
| Incident ID | Title | Severity | Status | Data center / region | Start | Duration | Blast | Impact | Tags | |
|---|---|---|---|---|---|---|---|---|---|---|
| INC-2024-001 | CrowdStrike Falcon Channel File 291: The Global Windows BSOD Outage of July 2024 On 19 July 2024 CrowdStrike pushed a Rapid Response Content update to Channel File 291 t… | Critical | Official RCA | 🌐Global Windows fleet (all clouGlobal | 2024-07-19 | 10d 20h | 10.0/10 | |||
| INC-2022-002 | SK C&C Pangyo Data Center Fire and the National Kakao/Naver Outage On 15 October 2022, a lithium-ion UPS battery on the third basement level (B3) of the SK… | Critical | Official RCA | 🇰🇷SK C&C Pangyo Data CenterSeongnam (Pangyo), South Korea | 2022-10-15 | 5d 4h | 10.0/10 | |||
| INC-2025-003 | NIRS Daejeon Government Data Center: UPS Lithium-Ion Battery Fire During Relocation Work On the evening of 26 September 2025, a lithium-ion UPS battery that had been disconnecte… | Critical | Official RCA | 🇰🇷NIRS Daejeon National InformatDaejeon, South Korea | 2025-09-26 | — | 10.0/10 | |||
| INC-2024-004 | Google Cloud Accidentally Deletes UniSuper's Entire GCVE Private Cloud During the initial provisioning of UniSuper's Google Cloud VMware Engine (GCVE) Private … | Critical | Official RCA | 🇦🇺Google Cloud VMware Engine (GCAustralia | 2024-05-02 | 9d | 10.0/10 | |||
| INC-2021-005 | Meta Global BGP + DNS Outage — Backbone Self-Disconnection Takes Facebook, Instagram & WhatsApp Offline Worldwide On 4 October 2021 a single command issued during routine backbone maintenance — intended… | Critical | Official RCA | 🇺🇸Facebook Global Backbone / AutMenlo Park, USA | 2021-10-04 | 5h 49m | 10.0/10 | |||
| INC-2021-006 | OVHcloud SBG2 Strasbourg Data-Center Fire (10 March 2021) In the early hours of 10 March 2021 a fire broke out in a ground-floor energy room at OV… | Critical | Official RCA | 🇫🇷SBG2 (Strasbourg campus)Strasbourg, France | 2021-03-10 | — | 9.0/10 | |||
| INC-2025-007 | AWS US-EAST-1 DynamoDB DNS Race Condition Cascades Across the Internet A latent race condition in DynamoDB's automated DNS management system left two DNS Enact… | Critical | Official RCA | 🇺🇸US-EAST-1 (Northern Virginia)Ashburn, United States | 2025-10-20 | 14h 32m | 10.0/10 | |||
| INC-2025-008 | Google Cloud Global Service Control / IAM Outage — June 12, 2025 A latent, unguarded code path in Google Cloud's Service Control quota system — added on … | High | Official RCA | 🇺🇸Google Cloud — Service ControlUSA | 2025-06-12 | 1h 39m | 10.0/10 | |||
| INC-2017-009 | AWS S3 US-EAST-1 Service Disruption An authorized S3 engineer running an established capacity-removal playbook mistyped one … | High | Official RCA | 🇺🇸US-EAST-1 region (Northern VirAshburn (approx.), United States | 2017-02-28 | 4h 17m | 10.0/10 | |||
| INC-2022-010 | Rogers Communications Canada Nationwide Network Outage (July 2022) A maintenance change to Rogers' core IP network removed a routing filter, flooding the r… | High | Official RCA | 🇨🇦Rogers national IP core networToronto, Canada | 2022-07-08 | 26h 2m | 9.0/10 | |||
| INC-2025-011 | Azure Front Door Global Outage: Inadvertent Cross-Build Config Change Trips Latent Data-Plane Crash Bug (29 Oct 2025) On 29 October 2025 an inadvertent customer configuration change to Azure Front Door (AFD… | High | Official RCA | 🌐Azure Front Door global edge fGlobal | 2025-10-29 | 8h 24m | 10.0/10 | |||
| INC-2016-012 | Dyn Managed DNS Outage — Mirai IoT Botnet DDoS (October 21, 2016) On Friday 21 October 2016, Dyn's managed (authoritative) DNS platform was hit by a large… | High | Official RCA | 🇺🇸Dyn Managed DNS Platform (authManchester, USA | 2016-10-21 | 5h 50m | 10.0/10 | |||
| INC-2021-013 | AWS US-EAST-1 Internal Network Congestion Outage (December 7, 2021) On December 7, 2021, an automated capacity-scaling operation on a service hosted in AWS'… | High | Official RCA | 🇺🇸AWS US-EAST-1 (Northern VirginAshburn, USA | 2021-12-07 | 6h 52m | 9.0/10 | |||
| INC-2016-014 | Delta Air Lines Atlanta Data Center Power Failure Grounds the Global Fleet In the early hours of 8 August 2016, a routine scheduled transfer of load onto a backup … | High | Press-sourced | 🇺🇸Delta Technology Data Center, Atlanta, United States | 2016-08-08 | 6h 0m | 9.0/10 | |||
| INC-2020-015 | Google Global Authentication Outage — User ID Service Quota Collapse (Dec 14, 2020) On December 14, 2020, an automated quota-management system wrongly cut capacity on the a… | High | Official RCA | 🇺🇸Google global identity (User IUSA | 2020-12-14 | 47m | 10.0/10 | |||
| INC-2026-016 | NorthC Almere Data Center Fire: A Compartment Blaze That Took Out the Facility Power Plant and Rippled Across Dutch Public Services On 7 May 2026 (around 08:45 local time) a fire broke out in a rear technical compartment… | High | Press-sourced | 🇳🇱NorthC Almere (Rondebeltweg)Almere, Netherlands | 2026-05-07 | 6d 1h | 9.0/10 | |||
| INC-2025-017 | Cloudflare Global Outage: Oversized Bot Management Feature File (November 18, 2025) On 18 November 2025 an 11:05 UTC ClickHouse database permissions change exposed r0-datab… | High | Official RCA | 🌐Cloudflare global edge networkGlobal | 2025-11-18 | 3h 2m | 9.0/10 | |||
| INC-2020-018 | AWS Kinesis OS Thread-Limit Cascade — US-EAST-1 (Nov 25, 2020) A small addition of capacity to the Kinesis Data Streams front-end fleet in US-EAST-1 pu… | High | Official RCA | 🇺🇸AWS US-EAST-1 (Kinesis Data StAshburn, USA | 2020-11-25 | 11h 0m | 9.0/10 | |||
| INC-2023-019 | Microsoft Azure / Microsoft 365 Global WAN Outage — IGP-Purge Command Cascade (Jan 25 2023) A single IGP-database-purge command, added to a WAN change procedure that was never re-t… | Medium | Official RCA | 🌐Global WAN backbone (Madrid caMadrid, Spain | 2023-01-25 | 4h 22m | 9.0/10 | |||
| INC-2020-020 | Azure Active Directory Global Authentication Outage (September 28, 2020) On 28 September 2020 a service update meant only for an internal Azure AD validation tes… | Medium | Official RCA | 🇺🇸Azure Active Directory — globaUSA | 2020-09-28 | 2h 58m | 9.0/10 | |||
| INC-2020-021 | Equinix LD8 Docklands UPS Failure: ~17.5-Hour Power Outage Disrupts LINX and ~150 Members On 18 August 2020 a faulty UPS system at Equinix's LD8 Docklands data centre — home to t… | Medium | Official RCA | 🇬🇧LD8 (Docklands)London, United Kingdom | 2020-08-18 | 9h 18m | 9.0/10 | |||
| INC-2011-022 | AWS EBS Re-Mirroring Storm and Stuck Volumes in US-East-1 A routine network-capacity upgrade in one US-East-1 Availability Zone was executed incor… | Medium | Official RCA | 🇺🇸US-East-1 (Northern Virginia)Ashburn area, Northern Virginia, USA | 2011-04-21 | 35h 43m | 7.0/10 | |||
| INC-2024-023 | AT&T Nationwide Wireless Outage — Network Misconfiguration (February 22, 2024) During a network expansion, an AT&T engineer used an incorrect process that introduced a… | Medium | Official RCA | 🇺🇸AT&T national wireless core neDallas, Texas, United States | 2024-02-22 | 12h 0m | 8.0/10 | |||
| INC-2023-024 | Optus Australia Nationwide Outage — Routing Change Cascade (November 8, 2023) Following a routine Singtel-network software upgrade, a large, unexpected flood of routi… | Medium | Press-sourced | 🇦🇺Optus national network coreSydney, Australia | 2023-11-08 | 8h 55m | 8.0/10 | |||
| INC-2023-025 | Alibaba Cloud Global All-Region Outage — Auth Control-Plane Failure On 12 November 2023 Alibaba Cloud's shared global authentication/authorization (Auth) co… | Medium | Press-sourced | 🇨🇳Global control plane (Auth/IAMHangzhou, China | 2023-11-12 | 3h 27m | 9.0/10 | |||
| INC-2023-026 | Cloudflare Control-Plane & Analytics Outage — Flexential PDX-04 Power Failure (Nov 2023) On 2 November 2023 a Portland General Electric (PGE) unplanned maintenance event dropped… | Medium | Official RCA | 🇺🇸Flexential PDX-04Hillsboro, United States | 2023-11-02 | 40h 41m | 8.0/10 | |||
| INC-2024-027 | Red Sea Subsea Cable Cuts — Rubymar Anchor Severs AAE-1, Seacom/TGN-EA and EIG off Yemen On 24 February 2024 three submarine cable systems — Seacom (which Kentik groups with TGN… | Medium | Press-sourced | 🇾🇪Red Sea cable corridor (Bab-elBab-el-Mandeb, Yemen | 2024-02-24 | — | 8.0/10 | |||
| INC-2018-028 | Azure South Central US: Lightning-Induced Cooling Loss and Automated Integrity Shutdown (September 2018) On 4 September 2018, a high-energy thunderstorm with lightning struck southern Texas nea… | Medium | Official RCA | 🇺🇸South Central US region (San ASan Antonio, United States | 2018-09-04 | 25h 31m | 7.0/10 | |||
| INC-2025-029 | CyrusOne Aurora Cooling Failure Halts CME Group Trading (November 2025) A human-error cooling-tower switchover during a cold-weather changeover triggered a chil… | Medium | Press-sourced | 🇺🇸CyrusOne Aurora (Chicago-area)Aurora, Illinois, United States | 2025-11-27 | 11h 0m | 7.0/10 | |||
| INC-2026-030 | AWS US-EAST-1 Cooling/Thermal Event and use1-az4 Power Loss On 7 May 2026 cooling systems failed in AWS's use1-az4 availability zone in US-EAST-1 (N… | Medium | Press-sourced | 🇺🇸US-EAST-1 (use1-az4), NorthernAshburn, United States | 2026-05-07 | 27h 44m | 6.0/10 | |||
| INC-2023-031 | Azure Australia East 2023: Voltage Sag, Chillers That Would Not Restart On 30 August 2023 a lightning-induced voltage sag tripped chillers at an Azure Australia… | Medium | Official RCA | 🇦🇺Australia East Availability ZoSydney, Australia | 2023-08-30 | 4d 10h | 6.0/10 | |||
| INC-2026-032 | Google Cloud India Disruption After STT GDC Delhi Data-Center Fire On or about 5 June 2026, a fire at a third-party data-center facility in New Delhi force… | Medium | Official RCA | 🇮🇳Third-party colocation facilitNew Delhi, India | 2026-06-05 | 21d 22h | 6.0/10 | |||
| INC-2017-033 | British Airways Boadicea House Power Surge: A 15-Minute Fault That Grounded Heathrow and Gatwick for Days On the morning of Saturday 27 May 2017, an engineer working inside British Airways' Boad… | Medium | Press-sourced | 🇬🇧Boadicea House (BoHo) data cenLondon, United Kingdom | 2017-05-27 | — | 7.0/10 | |||
| INC-2022-034 | Cloudflare June 2022 Outage — Config Change Withdraws 19 Core Data Centers A network-configuration change during a resilience upgrade to Cloudflare's Multi-Colo Po… | Medium | Official RCA | 🌐Cloudflare 19 busiest core datGlobal, Global | 2022-06-21 | 1h 15m | 8.0/10 | |||
| INC-2021-035 | Fastly Global CDN Outage — Latent Software Bug (June 8, 2021) An undiscovered software bug introduced in a mid-May Fastly software deployment lay dorm… | Medium | Official RCA | 🌐Fastly global edge CDN networkGlobal, Global | 2021-06-08 | 1h 13m | 8.0/10 | |||
| INC-2023-036 | Azure Southeast Asia 2023: Chillers Hang After a Dip, Then Lock Out On 7 February 2023 a voltage dip tripped chillers at an Azure Southeast Asia zone in Sin… | Medium | Official RCA | 🇸🇬Southeast Asia Availability ZoSingapore, Singapore | 2023-02-07 | 32h 11m | 6.0/10 | |||
| INC-2011-037 | AWS EU West (Dublin) 2011: Transformer Loss and a Generator PLC Halt On Sunday 7 August 2011 a utility transformer feeding much of one AWS EU West zone in Du… | Low | Official RCA | 🌐AWS EU West Availability Zone Dublin, Ireland | 2011-08-07 | 3d 10h | 5.0/10 | |||
| INC-2025-038 | PlayStation Network ~24-Hour Global Outage (February 2025) An approximately 24-hour global PlayStation Network outage on 7–8 February 2025 locked m… | Low | Press-sourced | 🇺🇸PlayStation Network backend seSan Mateo, California, United States | 2025-02-07 | — | 6.0/10 | |||
| INC-2026-039 | Azure West US 2 Grid-Disturbance Cooling Loss and Thermal Shutdown (May 2026) A grid power-quality disturbance reduced cooling capacity across multiple Azure West US … | Low | Official RCA | 🇺🇸Azure West US 2 (Quincy, WashiQuincy, Washington, United States | 2026-05-29 | 7h 36m | 6.0/10 | |||
| INC-2025-040 | X (Twitter) Oregon Data-Center Power-Cabinet Fire (May 2025) A fire that began inside a power cabinet at a Digital Realty Oregon facility hosting X (… | Low | Official RCA | 🇺🇸Digital Realty Oregon facilityHillsboro, Oregon, United States | 2025-05-22 | 23h 35m | 6.0/10 | |||
| INC-2026-041 | Google Cloud europe-west2-b Power Loss: PLC Logic Stops Generator Start On 20 Oct 2026 a utility cable fault took out the only live feed to the UK facility host… | Low | Official RCA | 🇬🇧Facility hosting zone europe-wSite not named, United Kingdom | 2026-10-20 | 6h 8m | 6.0/10 | |||
| INC-2022-042 | London Heatwave Cooling Failures — Google Cloud & Oracle (July 2022) During a record UK heatwave with temperatures above 40°C, cooling systems failed at Goog… | Low | Official RCA | 🇬🇧Google Cloud europe-west2 & OrLondon, United Kingdom | 2022-07-19 | 14h 10m | 6.0/10 | |||
| INC-2026-043 | Google Cloud europe-west4-a: Grid Transient, DRUPS Failure and Chiller Shutdown On 15 July 2026 a 3 ms grid transient tripped both utility feeds at the facility hosting… | Low | Official RCA | 🇳🇱Facility hosting zone europe-wSite not named, Netherlands | 2026-07-15 | 14h 55m | 4.0/10 | |||
| INC-2024-044 | Azure China North 3 ~50-Hour Regional Outage (2024) A power/cooling failure in Azure China North 3 (operated by 21Vianet) caused a roughly 5… | Low | Press-sourced | 🇨🇳Azure China North 3 region (HeHebei, China | 2024-11-01 | — | 4.0/10 | |||
| INC-2024-045 | Digital Realty Singapore Lithium-Ion UPS Fire (2024) A lithium-ion UPS battery fire at a Singapore data center forced an emergency power shut… | Low | Press-sourced | 🇸🇬Digital Realty Singapore data Singapore, Singapore | 2024-09-10 | — | 5.0/10 | |||
| INC-2016-046 | AWS Sydney 2016: Voltage Sag Drains the Rotary UPS, One Zone Loses Power On 4 June 2016 (5 June in Sydney) storms took out a substation and the grid sagged rathe… | Low | Official RCA | 🇦🇺AWS facility in the Sydney RegSydney, Australia | 2016-06-04 | 9h 35m | 4.0/10 | |||
| INC-2019-047 | AWS Tokyo 2019: Cooling Control Failover Bug Overheats Part of a Zone On 23 August 2019 a bug in third-party cooling-control software hung the control system … | Low | Official RCA | 🇯🇵AWS ap-northeast-1 AvailabilitTokyo, Japan | 2019-08-23 | 5h 54m | 4.0/10 | |||
| INC-2022-048 | Google Council Bluffs (Iowa) Electrical Explosion / Arc-Flash (August 2022) An electrical explosion (arc-flash) at Google's Council Bluffs, Iowa data center injured… | Low | Official RCA | 🇺🇸Google Council Bluffs data cenCouncil Bluffs, Iowa, United States | 2022-08-08 | — | 5.0/10 | |||
| INC-2023-049 | Digital Realty Los Angeles (El Segundo) Data-Center Fire (May 2023) A fire in server/equipment space at Digital Realty's Los Angeles (El Segundo) data cente… | Low | Press-sourced | 🇺🇸Digital Realty LAX (El SegundoEl Segundo, California, United States | 2023-05-21 | — | 4.0/10 | |||
| INC-2022-050 | Northern Virginia 'Data Center Alley': Transmission Constraint and Mass Data-Center Load Loss (2022–2026) Not a cooling failure. In July 2022 Dominion Energy told data-center customers that a tr… | Low | Press-sourced | 🇺🇸Northern Virginia data-center Ashburn (Loudoun), Virginia, United States | 2022-07-29 | — | 6.0/10 |
Ranking is a transparent composite of sourced sub-scores (blast radius 35% · users 25% · financial 20% · duration 20%). Summaries are original; quoted excerpts are short, attributed, and for provenance only.