Azure Southeast Asia 2023: Chillers Hang After a Dip, Then Lock Out
Summary
On 7 February 2023 a voltage dip tripped chillers at an Azure Southeast Asia zone in Singapore. Three chillers, over half the capacity, hung on a control-card fault the procedure did not cover; by the time it was reset the loop was too hot and they locked out. The zone was shut down from 20:19 UTC until the next day, and ARM and BCDR services failed with it.
- Users affected
- Customers in one Southeast Asia zone across about 30 services and the Azure portal; ARM management failures in Southeast Asia and East Asia; Site Recovery, Backup and GRS failover problems.
- Duration
- 32h 11m — Customer impact 20:19 UTC 7 Feb → 04:30 UTC 9 Feb (32 h 11 min)
- Financial
- Not disclosed
- Scope
- One Availability Zone, with control-plane effects in two regions
- Site
- Southeast Asia Availability Zone datacenter (not named) · Singapore, Singapore, southeastasia
- Services down
- Azure Virtual Machines, Azure Storage, Azure SQL Database, Azure Resource Manager, Azure Site Recovery, Azure Backup
How the defences failed
One zone, with management impact in two regions. Duration (7): 32 h 11 min of customer impact, inside the 1–3 d band.
All 8 impact metrics
| Chiller plant | 8 chillers from 2 suppliers: 1–5 give 47% of capacity, 6–8 give 53% |
| Chillers out after the dip | chiller 5 in maintenance; 6, 7, 8 would not start (53% of capacity) |
| Chiller thermal lockout threshold | chilled-water loop above 28°C |
| Control card hard reset | powered off for at least 5 minutes |
| Dip to zone shutdown | 5 hours 2 minutes (15:17 → 20:19 UTC) |
| Zone shutdown to temperatures normal | 17 hours 41 minutes (20:19 7 Feb → 14:00 8 Feb UTC) |
| SQL geo-replication with auto-failover downtime | about 1.5 hours |
| Customer impact window | 20:19 UTC 7 Feb → 04:30 UTC 9 Feb (32 hours 11 minutes) |
Sequence of events
- TRIGGER A utility voltage dip hits one Southeast Asia Availability Zone in Singapore; power systems ride through, but a subset of chillers trips and shuts down.
- CASCADE Chiller 5 is already offline for planned maintenance. Chiller 4 keeps running and chillers 1–3 restart, but chillers 6, 7 and 8 from the second supplier will not start.
- MITIGATION The documented emergency operating procedure is run on the tripped chillers, but the manual restarts fail.Mechanical / cooling engineer
- DETECTION The chiller HMI shows a phase sequence alarm; the compressor control card has stopped responding and needs a hard reset with at least 5 minutes powered off, a step the procedure did not list.
- MITIGATION Non-critical infrastructure is shut down to slow the temperature rise, and technicians from the chiller supplier are dispatched to site.Vendor / upstream provider
- CASCADE By the time the control cards are reset with the supplier, the chilled-water loop is above 28°C and the chillers enter thermal lockout.
- IMPACT Thermal warnings direct a shutdown of critical compute, network and storage in the zone; resources there become unavailable.
- CASCADE ARM in Southeast Asia loses part of its metadata store, a Cosmos DB instance in the failed zone that should have been zone-resilient but was not because of a configuration error.
- CASCADE Azure Site Recovery failovers fail because a recently updated workflow uses a non-zonal Service Bus instance in the failed zone.
- MITIGATION ARM endpoints in Southeast Asia are manually removed from the global Traffic Manager profile.Operations lead
- CASCADE The shifted ARM traffic overloads East Asia, extending management failures to that region.
- MITIGATION The new Site Recovery workflow is disabled in Southeast Asia, ending the Service Bus failures.Service recovery lead
- RECOVERY Augmented cooling is brought in and IT load is reduced until the loop falls below the lockout threshold; chillers 6, 7 and 8 restart.Mechanical / cooling engineer
- MITIGATION Microsoft proactively enables cross-region restore for all Azure Backup customers with geo-redundant vaults; a regional configuration issue then blocks some restores until 15:10.Service recovery lead
- RECOVERY ARM in East Asia is scaled up and fully recovered; Site Recovery failovers work reliably from 09:15.
- RECOVERY With all chillers back, temperatures return within operational thresholds.
- RECOVERY Power is restored in phases, storage first and then compute once storage is verified healthy.
- RECOVERY Most customers see platform services recover.
- CASCADE One SQL Database tenant ring does not reform: a BIOS bug stops its hosts recovering, then a Service Fabric heap-memory issue needs manual intervention.
- RESTORED The final SQL Database tenant ring becomes available and the incident ends.
Response by role
What each role did
Roles the sequence of events shows acting; every entry quotes its source line. Select a time to jump to it.
Role by role
Recorded actions / playbook actions per role. A role with 0 recorded actions does not appear in the sources.
Microsoft datacenter operations — Chillers, CRAH/CRAC, pumps, cooling towers and the thermal envelope of the white space.
On the record
- Ran the emergency procedure; restarts failed
The documented emergency operating procedure is run on the tripped chillers
- Cooled the loop below lockout and restarted chillers
Augmented cooling is brought in and IT load is reduced
Playbook analyst guidance by failure mode, not a record of what happened
The chiller supplier's technicians, supplier not named — Third party whose product, service or network sits in the failure path.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
Not named in the PIR — Owns every decision until formally relieved: site duty manager on scene, or the declared IC of a service incident.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
Azure ARM engineering — Technical lead who diagnoses and drives the fix; the subject-matter expert at the keyboard or the switchboard.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
- FM-02Review emergency procedures with the OEM for every alarm the HMI can raiseUptime OSCorrection of errors #2
- FM-04Check automatically that every control-plane store is zone-redundantISO 22301Correction of errors #6
- FM-03Pre-stage temporary cooling whenever a chiller is out for maintenanceChange managementImprovement #5
- FM-01Confirm every chiller is back before restoring IT loadUptime OSLesson #1
Azure Site Recovery, Backup and SQL teams — Restores customer service: failover, workload moves, capacity, backlog drain.
On the record
- Disabled the workflow that tied failover to the failed zone
The new Site Recovery workflow is disabled in Southeast Asia
- Enabled cross-region restore for geo-redundant vaults
Microsoft proactively enables cross-region restore
Playbook analyst guidance by failure mode, not a record of what happened
- FM-05Run zonal-failure fault injection against BCDR services themselvesISO 22301Correction of errors #9
Azure status page and Service Health — Status page, customer notices, regulators and press; one voice, timed updates.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
Failure mode & effects analysis (FMEA)
The chiller plant of the affected facility (control cards, emergency procedure, chilled-water lockout) and Azure's control plane and BCDR services, from Microsoft's PIR.
- Caught only after impactD ≥ 8
- 0 of 5
- Actions that cut occurrenceO lowered
- 4
- Actions that cut detectionD lowered
- 4
- Actions that cut severityblast radius unchanged
- 0
FM-02 The procedure lacks the cold-reset step, so manual restarts failEmergency operating procedure 8·3·7 168 64
- Function
- Get tripped chillers running again quickly
- Effect
- Hours lost until supplier technicians arrive
- Cause
- Procedure incomplete for this failure
- Prevention in place
- Documented EOP
- Detection in place
- Found when the EOP failed
- S 8
- Its gap let the loop reach lockout: 8.
- O 3
- Rare fault, rarely rehearsed: 'remote to infrequent'.
- D 7
- No drill exposed the missing step.
Corrective action
- Cold restart added to procedures (completed) Correction of errors #2
- OEM training for operations staff (completed) Correction of errors #3
After action: S8 · O2 · D4 → RPN 64. Both actions are reported completed and directly close the gap.
Who acts — playbook
- Operations lead Review emergency procedures with the OEM for every alarm the HMI can raiseUptime OSCorrection of errors #2
- Mechanical / cooling engineer Escalate to the OEM as soon as a documented restart failsUptime OSLesson #1
- Vendor / upstream provider Keep OEM technicians on call with a response time shorter than lockoutUptime OSCorrection of errors #3
- Incident commander Record the working fix and update the procedure before closingISO 22301Correction of errors #2
On the record at this failure
Evidence
- Sequence of events #3“the manual restarts fail”
- Contributing factor #2Compressor control cards on chillers 6–8 stopped responding and needed a cold reset that the emergency procedure did not list (Azure PIR).
- Metric #4Control card hard reset: powered off for at least 5 minutes
FM-01 The control cards stop responding after the dip and block restartChiller compressor control cards (chillers 6–8) 8·3·6 144 64
- Function
- Restart the chillers automatically after a power dip
- Effect
- 53% of cooling capacity unavailable
- Cause
- Control-card fault with a phase sequence alarm; OEM investigating
- Prevention in place
- Automatic restart after a trip
- Detection in place
- HMI alarm log, read during the event
- S 8
- Led to the shutdown of a zone: 8.
- O 3
- Needs a dip and this card fault: 'remote to infrequent'.
- D 6
- The alarm was visible but its meaning was not in the procedure.
Corrective action
- OEM engagement on prevention and recovery (completed) Correction of errors #1
After action: S8 · O2 · D4 → RPN 64. OEM follow-up is reported completed, and the cold-restart step makes the alarm actionable; the fault itself may still occur.
Who acts — playbook
- Vendor / upstream provider Have the OEM confirm control-card behaviour under voltage dips and fix itASHRAE TC 9.9Correction of errors #1
- Mechanical / cooling engineer Map each chiller alarm code to its recovery step in the procedureASHRAE TC 9.9Correction of errors #2
- Mechanical / cooling engineer Cold-restart hung control cards at once, power off for at least five minutesASHRAE TC 9.9Correction of errors #2
- Operations lead Confirm every chiller is back before restoring IT loadUptime OSLesson #1
Evidence
- Sequence of events #2“will not start”
- Sequence of events #4“the compressor control card has stopped responding”
- Contributing factor #2Compressor control cards on chillers 6–8 stopped responding and needed a cold reset that the emergency procedure did not list (Azure PIR).
FM-04 Metadata store not zone-resilient; traffic shifted to East Asia overloads itARM regional control plane 7·3·6 126 56
- Function
- Keep management working in the region and its neighbours during a zone failure
- Effect
- Management failures in two regions; customers cannot run their continuity plans
- Cause
- Regional configuration error; no spare capacity in the neighbour region
- Prevention in place
- Zone-resilient design by intent
- Detection in place
- Seen during the event
- S 7
- Blocked recovery actions in two regions: 7.
- O 3
- A configuration error in one region: 'remote to infrequent'.
- D 6
- The mis-configuration was not found until the zone failed.
Corrective action
- ARM configuration and redundancy validated (completed) Correction of errors #4
- ARM spare capacity in all regions (completed) Correction of errors #5
After action: S7 · O2 · D4 → RPN 56. Both fixes are reported completed; the daily dependency walk improves detection.
Who acts — playbook
- Operations lead Check automatically that every control-plane store is zone-redundantISO 22301Correction of errors #6
- Operations lead Alert on control-plane errors per region as soon as a zone dropsSRE incident mgmtContributing factor #5
- Service recovery lead Scale the receiving region before shifting traffic into itSRE incident mgmtCorrection of errors #5
- Communications lead Tell customers when management actions are safe to retryITIL 4Correction of errors #10
Evidence
- Sequence of events #8“configuration error”
- Sequence of events #11“overloads East Asia”
- Contributing factor #5ARM's metadata store in the region was not zone-resilient because of a configuration error (Azure PIR).
- Contributing factor #6Moving ARM traffic to East Asia exceeded its capacity, spreading impact to a second region (Azure PIR).
FM-05 Site Recovery depends on a non-zonal Service Bus; Backup and storage failover hit configuration and check faultsBCDR services (Site Recovery, Backup, GRS failover) 7·3·6 126 70
- Function
- Let customers fail over or restore when a zone or region fails
- Effect
- Customer continuity plans fail or are delayed
- Cause
- Recent workflow update and regional configuration errors
- Prevention in place
- BCDR services designed for zonal and regional incidents
- Detection in place
- Customer failures
- S 7
- Defeated the customers' own resilience plans: 7.
- O 3
- Configuration drift in one region: 'remote to infrequent'.
- D 6
- Found only when customers used them.
Corrective action
- Backup restore configuration and Site Recovery workflow corrected (completed) Correction of errors #7
- Storage failover safety checks adjusted (completed) Correction of errors #8
After action: S7 · O2 · D5 → RPN 70. The specific faults are reported fixed; the planned Chaos Studio zonal tests would further improve detection.
Who acts — playbook
- Service recovery lead Run zonal-failure fault injection against BCDR services themselvesISO 22301Correction of errors #9
- Operations lead Watch BCDR failover success rates from the first minutes of a zone lossSRE incident mgmtContributing factor #7
- Service recovery lead Disable a recent workflow change that ties failover to the failed zoneChange managementCorrection of errors #7
- Communications lead Give customers a recoverability timeline so they can decide whether to invoke BCDRITIL 4Correction of errors #10
On the record at this failure
Evidence
- Sequence of events #9“non-zonal Service Bus instance”
- Sequence of events #14“a regional configuration issue then blocks some restores”
- Contributing factor #7Site Recovery depended on a non-zonal Service Bus instance in the failed zone after a recent update (Azure PIR).
FM-03 The loop passes 28°C and the chillers lock outChilled-water loop and thermal lockout 9·3·4 108 —
- Function
- Keep the loop cool enough for chillers to restart
- Effect
- Even repaired chillers cannot start; the zone is shut down
- Cause
- Too little running capacity with chiller 5 already in maintenance
- Prevention in place
- Spare chillers; shedding non-critical load
- Detection in place
- Loop temperature
- S 9
- Forced a full zone shutdown lasting into the next day: 9.
- O 3
- Needs a long restart failure: 'remote to infrequent'.
- D 4
- Loop temperature is measured; the limit was reached anyway.
Corrective action
- None published — residual risk.
Who acts — playbook
- Operations lead Pre-stage temporary cooling whenever a chiller is out for maintenanceChange managementImprovement #5
- Mechanical / cooling engineer Alarm on loop temperature well below the lockout limitASHRAE TC 9.9Contributing factor #4
- Incident commander Shed IT load early to keep the loop under the lockout limitNIMS / ICSLesson #3
- Mechanical / cooling engineer Bring in temporary cooling to pull the loop below lockoutASHRAE TC 9.9Lesson #3
Evidence
- Sequence of events #6“the chilled-water loop is above 28°C”
- Metric #3Chiller thermal lockout threshold: chilled-water loop above 28°C
- Contributing factor #3Chiller 5 was already offline for planned maintenance, reducing spare capacity (Azure PIR).
- Contributing factor #4Once the loop exceeded 28°C the chillers entered thermal lockout and could not restart (Azure PIR).
Scoring rubric and method
Scales adapted from IEC 60812:2018 and AIAG-VDA. RPN = S × O × D. High: S ≥ 9 with O ≥ 4 or D ≥ 7, or RPN ≥ 300. Medium: RPN ≥ 120 or S ≥ 7. Severity overrides the product: 9 × 2 × 9 = 162 would otherwise hide a region-wide outage nothing could catch. Quotes are checked verbatim against this dossier; a revised score needs a published action. RZ analyst assessment, not an operator document.
Severity
| 10 | Hazard to people, or loss of the facility / several regions |
| 9 | Region-wide or provider-wide outage of a foundational service, no workaround |
| 8 | Full outage of a major service for hours |
| 7 | Major degradation of a major service |
| 6 | Partial outage confined to one zone or one service |
| 5 | Customer-visible degradation |
| 4 | Limited customer impact |
| 3 | Internal impact only |
| 2 | Negligible |
| 1 | No effect |
Occurrence
| 10 | Near certain: the cause is present in normal operation |
| 8 | Frequent: routine work exercises the cause |
| 6 | Occasional: a foreseeable slip or condition, weakly guarded |
| 4 | Infrequent: needs an unusual combination |
| 2 | Remote: guarded by design |
| 1 | Eliminated by design |
Detection
| 10 | No control could detect it |
| 9 | Detected only through customer impact |
| 8 | Detected after impact by internal monitoring |
| 6 | Detected at onset, not prevented |
| 4 | Detected before impact with time to act |
| 2 | Automated interlock almost certainly stops it |
| 1 | Certain to be stopped |
Root cause and contributing factors
Full root-cause narrative
Contributing factors by category
- A utility voltage dip tripped a subset of chillers (Azure PIR).
- Compressor control cards on chillers 6–8 stopped responding and needed a cold reset that the emergency procedure did not list (Azure PIR).
- Chiller 5 was already offline for planned maintenance, reducing spare capacity (Azure PIR).
- Once the loop exceeded 28°C the chillers entered thermal lockout and could not restart (Azure PIR).
- ARM's metadata store in the region was not zone-resilient because of a configuration error (Azure PIR).
- Moving ARM traffic to East Asia exceeded its capacity, spreading impact to a second region (Azure PIR).
- Site Recovery depended on a non-zonal Service Bus instance in the failed zone after a recent update (Azure PIR).
- A BIOS bug and a Service Fabric memory issue kept one SQL tenant ring down until 04:30 on 9 February (Azure PIR).
Analysis
Half the plant would not start
Chillers 6–8 supplied 53% of capacity and hung on the same control-card fault. With chiller 5 in maintenance, the four running units could not hold the hall.
A missing line in the procedure
The fix, power the control card off for at least five minutes, was known to the OEM but not in the emergency procedure. Finding it cost the time in which the loop passed 28°C and locked the chillers out.
Lockout needs heat removed another way
Escaping lockout required temporary cooling and shutting equipment down. Temperatures were back in range only at 14:00 the next day.
Resilience services failed first
ARM, Site Recovery and Backup each had a configuration or dependency that tied them to the failed zone, so customers trying to execute their continuity plans hit errors, some in East Asia as well.
What the PIR does not say
It does not name the facility, the chiller suppliers or models, peak hall temperature, or cost. Most actions are reported completed; the Chaos Studio expansion was due December 2023.
Technical deep-dive
Corrective actions and lessons
Correction of errors
| Action | Owner | Status |
|---|---|---|
| Work with the chiller OEM to prevent, shorten and reliably recover these events | Microsoft datacenter team | Completed |
| Add the manual cold restart of chillers to the procedures, as the OEM recommends | Microsoft | Completed |
| OEM training for datacenter operations staff on the updated procedures | Microsoft | Completed |
| Validate ARM configuration in Southeast Asia and that all ARM instances are zone/region redundant | Microsoft | Completed |
| Ensure ARM capacity in all regions can absorb traffic from zonal or regional failures | Microsoft | Completed |
| Daily automated walk of the dependency graph of zonal services to close single points of failure | Microsoft | Ongoing |
| Correct the Backup cross-region-restore configuration in all regions; return Site Recovery to a zone-resilient workflow | Microsoft | Completed |
| Adjust safety-check thresholds for customer-initiated GRS storage failover | Microsoft | Completed |
| Expand Chaos Studio zonal-failure scenarios | Microsoft | Planned for December 2023 (completion not reported) |
| Give a recoverability expectation and timeline in incident communications | Microsoft | Completed |
Lessons learnt
- An emergency procedure is only as good as its rarest step; the cold reset the chillers needed was not written down.
- Running a plant with a chiller out for maintenance removes the margin that would absorb a restart failure.
- Thermal lockout turns minutes into hours; bring temporary cooling and shed load before the loop reaches the lockout limit.
- Business-continuity services must be the most zone-resilient part of the platform, not the least.
- Shifting a control plane to a neighbour region needs headroom there, or the failure moves with the traffic.
- Zone-redundant workloads stayed largely available; regional services with hidden zonal dependencies did not.
Improvements
- Cooling: OEM cold-restart step added to procedures, with training (Microsoft, completed).
- Control plane: ARM zone redundancy validated and spare capacity in all regions (Microsoft, completed).
- BCDR: Site Recovery workflow and Backup restore configuration fixed; storage failover checks adjusted (Microsoft, completed).
- Architecture: daily dependency-graph walk for zonal services (Microsoft, ongoing).
- Analyst recommendation (not in the PIR): treat a chiller out for maintenance as a reduced-redundancy state with a pre-staged temporary cooling plan.
References and provenance
- official-postmortem Azure status history, Post Incident Review VN11-JD8: Southeast Asia and East Asia, cooling failure in one Availability Zone“This condition is referred to as a thermal lockout.”https://azure.status.microsoft/en-us/status/history/?trackingId=VN11-JD8
- vendor-status Azure Incident Retrospective video VN11-JD8“Azure Incident Retrospective”https://aka.ms/AIR/VN11-JD8
Quotes are short, attributed, and for provenance only; the analysis is original. Last verified 2026-11-11.