Sustainability metrics — how the page works

The sustainability page explains the five operational ratios of a data center (PUE, WUE, CUE, ERF, REF) on one facility drawing, with the ISO/IEC 30134 definition of each, the PUE measurement categories, the location and market carbon methods, and a worked 10 MW example whose arithmetic a test recomputes.

Type Reference page Domain Sustainability Engine None — formulas only, test-checked
▶ Open the sustainability page

01 What the page shows

02 How the numbers are kept correct

The page has no engine: every number is either an ISO/IEC 30134 definition or the arithmetic of the worked example on stated inputs. tools/test-pillar-sustainability.py recomputes every result of the example from its inputs, checks that every [S] citation resolves and every source is cited, that the FAQ structured data equals the questions on the page, and that the page equals what its generator writes. tools/test-figure-interact.mjs clicks, hovers, taps and walks both figures in a real browser.

03 References & standards